DA01328A_A_and_E_CDs_REV0_FINAL_CDs_030521_UNCERT - zoning set_v1.ADM APP.033521• • T 0 Mobile •
T-MOBILE SITE NUMBER: DA01328A
T-MOBILE SITE NAME: CROWN #876558
SITE TYPE:
TOWER HEIGHT:
SITE INFORMATION
CROWN CASTLE USA INC.
SITE NAME:
F3 - COPPELL MIDDLE S
SITE ADDRESS:
1301 WRANGLER
COPPELL, TX 75017
COUNTY:
DALLAS
MAP/PARCEL #:
65005640510050000
AREA OF CONSTRUCTION:
EXISTING
LATITUDE:
32° 56' 05.32"
LONGITUDE:
-97° 00' 05.83"
LAT/LONG TYPE:
NAD83
GROUND ELEVATION:
528 FT (GOOGLE EARTH)
CURRENT ZONING:
PD-289-C C
JURISDICTION:
CITY OF COPPELL
OCCUPANCY CLASSIFICATION:
U
TYPE OF CONSTRUCTION:
IIB
A.D.A. COMPLIANCE:
FACILITY IS UNMANNED AND NOT FOR
HUMAN HABITATION
PROPERTY OWNER:
COPPELL ISD
200 S. DENTON TAP ROAD
COPPELL, TX 75019
TOWER OWNER:
CROWN CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
CARRIER/APPLICANT:
T-MOBILE
7668 WARREN PARKWAY
FRISCO, TX 75034
CROWN CASTLE USA INC.
APPLICATION ID:
540860
ELECTRIC PROVIDER:
TBD
TELCO PROVIDER: TBD
r PROJECT TEAM
A&E FIRM: GPD GROUP, PROFESSIONAL CORPORATION
520 S. MAIN STREET
AKRON, OH 44311
CROWN CASTLE CONTACTS: 6191 N STATE HIGHWAY 161, SUITE 300
IRVING, TX 75038
BILL WRIGHT - PROJECT MANAGER
BILL. WRIGHT@CROWNCASTLE. COM
(972) 374-4275
MOHAMMED JAVAID - A&E SPECIALIST
MOH A MMFD.JAVAID@CROWNCASTLE.COM
(713) 570-3054
T-MOBILE CONTACTS: 7668 WARREN PARKWAY
FRISCO, TX 75034
SHAMROSE ALI - PROJECT MANAGER
SHAMROSE.ALI109@T-MOBILE.COM
(505) 250-7489
MONOPOLE
701-911
BUSINESS UNIT #:
APPLICATION ID #:
SITE ADDRESS:
COUNTY:
JURISDICTION:
PROJECT: T-MOBILE ANCHOR
DRAWING INDEX
SHEET # SHEET DESCRIPTION
T-1 TITLE SHEET
T-2 GENERAL NOTES
T-3 GENERAL NOTES
C-1.1 OVERALL SITE PLAN
C-1.2 FINAL EQUIPMENT PLAN
C-2 FINAL TOWER ELEVATION & ANTENNA LAYOUTS
C-3 REDS
C-4 CONFIGURATION DIAGRAM
C-5 EQUIPMENT SPECIFICATIONS
C-6 EQUIPMENT SPECIFICATIONS
C-7 EQUIPMENT SPECIFICATIONS
C-8 EQUIPMENT SPECIFICATIONS
C-9 EQUIPMENT SPECIFICATIONS
C-10 BATTERY SPECS & BATTERY DATA CHART
G-1 EQUIPMENT GROUNDING PLAN
G-2 GROUNDING DETAILS
G-3 GROUNDING DETAILS
ALL DRAWINGSCONTAL HEREINAREPORDIATTEDFOR22"X34".CON'TRACTORSHALLVLRIPYALLPLANSANDEHISTING
DIDffiNSIONS AND CONDITTONS ON THEJOR SITE Ai SHALL L}LMEDIATELY NOTIFY THE ENGRVLEI MNWRITEVG OFAN}'
DISCREPANCI& BEFORE PROCEEDIN(; W'CCH THE WORK OR RE RESPONSIBLE FOR SAME.
APPROVALS
APPROVAL SIGNATURE DATE
PROPERTY OWNER OR REP.
LAND USE PLANNER
T-MOBILE
OPERATIONS
RF
NETWORK
BACKHAUL
CONSTRUCTION MANAGER
NOTES:
PRIOR TO ACCESSING/ENTERING THE SITE YOU MUST CONTACT
THE CROWN NOC AT 800-788-7011 & CROWN CONSTRUCTION
THE HEIGHT OF THE TOWER WILL NOT BE INCREASED; NOR WILL
THERE BE AN EXPANSION OF THE GROUND/LEASE AREA
THE PARTIES ABOVE HEREBY APPROVE AND ACCEPT THESE
DOCUMENTS AND AUTHORIZE THE CONTRACTOR TO PROCEED
WITH THE CONSTRUCTION DESCRIBED HEREIN. ALL
CONSTRUCTION DOCUMENTS ARE SUBJECT TO REVIEW BY THE
LOCAL BUILDING DEPARTMENT AND ANY CHANGES AND
MODIFICATIONS THEY MAY IMPOSE.
876558
540860
1301 WRANGLER
COPPELL, TX 75017
DALLAS
CITY OF COPPELL
APPLICABLE CODES/REFEREN(
DOCUMENTS
ALL WORK SHALL BE PERFORMED AND MATERIALS INSTALLED IN
ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING
CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES.
NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK
NOT CONFORMING TO THESE CODES:
CODE TYPE CODE
BUILDING 2015IBC
MECHANICAL 2015IMC
ELECTRICAL 2014 NEC
REFERENCE DOCUMENTS:
STRUCTURAL ANALYSIS: B+T GROUP
01/22/2021
MOUNT ANALYSIS: INFINIGY ENGINEERING, PLLC
01/28/2021
CALL TEXAS ONE CALL
(800) DIG-TESS
CALL 3 WORKING DAYS
BEFORE YOU DIG'
PROJECT DESCRIPTION
THE PURPOSE OF THIS PROJECT IS TO PROPOSE AN ANTENNA
MODIFICATION ON AN EXISTING WIRELESS SITE.
FINAL TOWER CONFIGURATION:
• (12) ANTENNAS
• (9) RRUs
• (3) HCS PART 1
• (3) HCS 2.0 PART 3 (1-1/2")
• (3) TMAs
• (12) 7/8" COAX
• (3) 8' ANTENNA PIPES
FINAL GROUND CONFIGURATION:
• (1) DELTA 40OA/V1/FUTURE 600A SSC+SB3
• (1) FCOA
• (3) BOTTOM JUNCTION BOXES
• (6) DIPLEXERS
DESIGN PACKAGE BASED ON
THE APPLICATION ID: 540860
REVISION: 0
DESIGN PACKAGE BASED ON
RF DATA SHEET VERSION: 30
ISSUED:12/18/2020
• w T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
CCCROWN
CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, S111.2531
Akron, OH 44311
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
l GPD JOB NUMBER: 2020724.78.876558.01 I
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIARNARY
NfRL
0
03/05/2021
DTC
FINAL CDs
MRL
tE OFT 1
tP ...........fegi411
t 131RISTOPHER J. SCHEKS i
119636 f"f
9at.'••. rICENSe�.+'��
03/05/2021
GPD Grwp, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIItECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
IN
REVISION:
T-1
0
CROWN CASTLE USA INC. SITE ACTIVITY REQUIREMENTS:
GENERAL NOTES:
1. NOTICE TO PROCEED- NO WORK SHALL COMMENCE PRIOR TO CROWN CASTLE USA INC. WRITTEN NOTICE TO PROCEED (NTP) AND
THE ISSUANCE OF A PURCHASE ORDER. PRIOR TO ACCESSING/ENTERING THE SITE YOU MUST CONTACT THE CROWN CASTLE USA
INC. Noe AT 800-788-7011 & THE CROWN CASTLE USA INC. CONSTRUCTION MANAGER.
2. "LOOK UP" - CROWN CASTLE USA INC. SAFETY CLIMB REQUIREMENT:
THE INTEGRITY OF THE SAFETY CLIMB AND ALL COMPONENTS OF THE CLIMBING FACILITY SHALL BE CONSIDERED DURING ALL
STAGES OF DESIGN, INSTALLATION, AND INSPECTION. TOWER MODIFICATION, MOUNT REINFORCEMENTS, AND/OR EQUIPMENT
INSTALLATIONS SHALL NOT COMPROMISE THE INTEGRITY OR FUNCTIONAL USE OF THE SAFETY CLIMB OR ANY COMPONENTS OF
THE CLIMBING FACILITY ON THE STRUCTURE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO: PINCHING OF THE WIRE ROPE, BENDING
OF THE WIRE ROPE FROM ITS SUPPORTS, DIRECT CONTACT OR CLOSE PROXIMITY TO THE WIRE ROPE WHICH MAY CAUSE
FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE POINTS IN ANY WAY, OR TO IMPEDE/BLOCK ITS INTENDED USE. ANY COMPROMISED
SAFETY CLIMB, INCLUDING EXISTING CONDITIONS MUST BE TAGGED OUT AND REPORTED TO YOUR CROWN CASTLE USA INC. Poe
OR CALL THE NOC TO GENERATE A SAFETY CLIMB MAINTENANCE AND CONTRACTOR NOTICE TICKET.
3. PRIOR TO THE START OF CONSTRUCTION, ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED. THIS INCLUDES, BUT IS
NOT LIMITED TO, BUILDING, ELECTRICAL, MECHANICAL, FIRE, FLOOD ZONE, ENVIRONMENTAL, AND ZONING. AFTER ONSITE
ACTIVITIES AND CONSTRUCTION ARE COMPLETED, ALL REQUIRED PERMITS SHALL BE SATISFIED AND CLOSED OUT ACCORDING TO
LOCAL JURISDICTIONAL REQUIREMENTS.
4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, RIGGING PLANS, CLIMBING PLANS,
AND RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE
WORK CONTAINED HEREIN, AND SHALL MEET ANSI/ASSE A10.48 (LATEST EDITION); FEDERAL, STATE, AND LOCAL REGULATIONS; AND
ANY APPLICABLE INDUSTRY CONSENSUS STANDARDS RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL
RIGGING PLANS SHALL ADHERE TO ANSI/ASSE A10.48 (LATEST EDITION) AND CROWN CASTLE USA INC. STANDARD CED-STD-10253,
INCLUDING THE REQUIRED INVOLVEMENT OF AQUALIFIED ENGINEER FOR CLASS IV CONSTRUCTION, TO CERTIFY THE SUPPORTING
STRUCTURE(S) IN ACCORDANCE WITH ANSI/TIA-322 (LATEST EDITION).
5. ALL SITE WORK TO COMPLY WITH QAS-STD-10068 "INSTALLATION STANDARDS FOR CONSTRUCTION ACTIVITIES ON CROWN CASTLE
USA INC. TOWER SITE" AND LATEST VERSION OF ANSIMA-1019-A-2012 "STANDARD FOR INSTALLATION, ALTERATION, AND
MAINTENANCE OF ANTENNA SUPPORTING STRUCTURES AND ANTENNAS."
6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL PROPOSE AN
ALTERNATIVE INSTALLATION FOR APPROVAL BY CROWN CASTLE USA INC. PRIOR TO PROCEEDING WITH ANY SUCH CHANGE OF
INSTALLATION.
7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS AND
ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES,
REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK
CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL
JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS
UNLESS SPECIFICALLY STATED OTHERWISE.
9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION.
10. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE WORK, SHALL BE
PROTECTED AT ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY CONSTRUCTION MANAGER. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN EXCAVATING OR
DRILLING PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL
INCLUDE BUT NOT BE LIMITED TO A) FALL PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION
E) CONSTRUCTION SAFETY PROCEDURES.
11. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT SPECIFICATIONS, LATEST
APPROVED REVISION.
12. CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL, DEBRIS, AND TRASH AT THE COMPLETION OF
THE WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER REFUSE SHALL BE REMOVED FROM THE SITE
AND DISPOSED OF LEGALLY.
13. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH THE EXECUTION OF THE
WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE
WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL OF CONTRACTOR, TOWER OWNER, CROWN CASTLE USA INC.,
AND/OR LOCAL UTILITIES.
14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR SITE SIGNAGE
REQUIRED BY LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF EQUIPMENT, ROOMS, AND SHELTERS.
15. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT AND TOWER AREAS.
16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED SURFACE APPLICATION.
17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER, EQUIPMENT OR DRIVEWAY,
SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS
AND/OR PROJECT SPECIFICATIONS.
18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL MEASURES, IF
REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES FOR EROSION AND SEDIMENT
CONTROL.
19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY
DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF OWNER.
20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND OTHER ITEMS
REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S DESIGNATED LOCATION.
21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON A DAILY
BASIS.
22. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOW OR ICE SHALL NOT BE
PLACED IN ANY FILL OR EMBANKMENT.
1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION
CARRIER: T-MOBILE
TOWEROWNER: CROWN CASTLE USA INC.
2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY EXERCISED
UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS ASSUMED THAT THE WORK
DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE WHO HAVE A WORKING KNOWLEDGE OF
THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT
EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL USE INDUSTRY
ACCEPTED STANDARD GOOD PRACTICE FOR MISCELLANEOUS WORK NOT EXPLICITLY SHOWN.
3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF CONSTRUCTION.
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, AND
PROCEDURES. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY FOR PROTECTION OF LIFE AND PROPERTY DURING
CONSTRUCTION. SUCH MEASURES SHALL INCLUDE BUT NOT BE LIMITED TO BRACING FORMWORK SHORING ETC. SITE VISITS BY
THE ENGINEER OR HIS REPRESENTATIVE WILL NOT INCLUDE INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION
OF THE FINISHED STRUCTURE ONLY.
4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT, AND/OR AS PROVIDED FOR
IN THE CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL NOTES, AND
SPECIFICATIONS, THE GREATER, MORE STRICT REQUIREMENTS, SHALL GOVERN. IF FURTHER CLARIFICATION IS REQUIRED
CONTACT THE ENGINEER OF RECORD.
5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE DIMENSIONS AND MEASUREMENTS ON THE DRAWINGS TO ASSIST IN
THE FABRICATION AND/OR PLACEMENT OF CONSTRUCTION ELEMENTS BUT IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR
TO FIELD VERIFY THE DIMENSIONS, MEASUREMENTS, AND/OR CLEARANCES SHOWN IN THE CONSTRUCTION DRAWINGS PRIOR TO
FABRICATION OR CUTTING OF ANY NEW OR EXISTING CONSTRUCTION ELEMENTS. IF IT IS DETERMINED THAT THERE ARE
DISCREPANCIES AND/OR CONFLICTS WITH THE CONSTRUCTION DRAWINGS THE ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON
AS POSSIBLE.
6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE EXISTING
CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION DRAWINGS. ANY
DISCREPANCY FOUND SHALL BE BROUGHT TO THE ATTENTION OF CROWN CASTLE.
7. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND LABOR
NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS
UNLESS SPECIFICALLY STATED OTHERWISE.
9. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL PROPOSE AN
ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CARRIER AND CROWN CASTLE PRIOR TO PROCEEDING WITH ANY SUCH
CHANGE OF INSTALLATION.
10. CONTRACTOR IS TO PERFORM A SITE INVESTIGATION AND IS TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR POWER,
AND TELCO AND FOR GROUNDING CABLES AS SHOWN IN THE POWER, TELCO, AND GROUNDING PLAN DRAWINGS.
• m T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH -11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
ABBREVIATIONS: QTY QUANTITY
REST RECTIFIER
EXISTING 70t_�11 MONOPOLE
ANT ANTENNA RIBS RADIO BASE STATION
(E) EXISTING PET REMOTE ELECTRIC TILT
FIF FACILITY INTERFACE FRAME RFDS RADIO FREQUENCY DATA SHEET
GEN GENERATOR RRH REMOTE RADIO HEAD
GPS GLOBAL POSITIONING SYSTEM RRU REMOTE RADIO UNIT
GPD JOB NUMBER: 2020724.78.876558.01
GSM GLOBAL SYSTEM FOR MOBILE SIAD SMART INTEGRATED DEVICE
LTE LONG TERM EVOLUTION TMA TOWER MOUNTED AMPLIFIER
MGB MASTER GROUND BAR TYP TYPICAL
ISSUED FOR:
MW MICROWAVE UMTS UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM
(N) NEW W.P. WORK POINT
REV
DATE
DRWN
DESCRIPTION
DES./Q
NEC NATIONAL ELECTRIC CODE
(P) PROPOSED
0
02/09/2021
DTC
PRELIMINARY
MRL
PP POWER PLANT
0
03/05/2021
DTC
FINAL CDs
MRL
:ij
t5tt OF.r'
CHRISTOPHER J. SCHEKS i
oi, 111I836 :�•
94e••.��ceNse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
ST-2 HEET NUMBER: REVISI0ON:
ELECTRICAL INSTALLATION NOTES:
GROUNDING NOTES:
1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE
FEDERAL, STATE, AND LOCAL CODES/ORDINANCES.
2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT
BLOCKED AND TRIP HAZARDS ARE ELIMINATED.
3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO
REQUIREMENT OF THE NATIONAL ELECTRICAL CODE.
4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT
CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 20,000 AIC MINIMUM. VERYIFY AVAILABLE SHORT CIRCUIT CURRENT
DOES NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST
CURRENT ADOPTED CODE PRE THE GOVERNING JURISDICTION.
5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE
LABELED WITH COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV
PROTECTION, OR EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA.
6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE
CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i.e. PANEL BOARD
AND CIRCUIT ID'S).
7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
8. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES.
9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER)
WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH
TYPE THHW THWN THWN-2 XHHW XHHW-2 THW THW-2 RHW OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI -CONDUCTOR TYPE SOOW CORD LARGER OR #14 UNLESS
( )
OTHERWISE SPECIFIED.
12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI -CONDUCTOR, TYPE TC CABLE (#14 OR LARGER), WITH
TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS
AND BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75- C (90" C IF AVAILABLE).
14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND
NEC.
15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR
EXPOSED INDOOR LOCATIONS.
16. ELECTRICAL METALLIC TUBING (EMT) OR METAL -CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE
GRADE PVC CONDUIT.
18. LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION
OCCURS OR FLEXIBILITY IS NEEDED.
19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET
SCREW FITTINGS ARE NOT ACCEPTABLE.
20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, UL, ANSI/IEEE AND
THE NEC.
21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
(WIREMOLD SPECMATE WIREWAY).
22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL).
23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE
DEVICES (i.e. POWDER -ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE
LINES OF THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES.
CHANGES IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE
INSTALLED IN A NEAT AND WORKMANLIKE MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES.
ALL CONDUIT SHALL BE FISHED TO CLEAR OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO
FINISH GRADE TO PREVENT CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES
BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE.
24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY -COATED SHEET
STEEL. SHALL MEET OR EXCEED UL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3R (OR BETTER)
FOR EXTERIOR LOCATIONS.
25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY -COATED OR NON -CORRODING; SHALL MEET OR
EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP
OR BETTER) FOR EXTERIOR LOCATIONS.
26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE
RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR CROWN CASTLE USA
INC. BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS.
28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN
ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY.
29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW "T-MOBILE".
30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
CONDUCTOR COLOR CODE
SYSTEM
CONDUCTOR
COLOR
120/240V, 10
A PHASE
BLACK
B PHASE
RED
NEUTRAL
WHITE
GROUND
GREEN
120/208V, 30
A PHASE
BLACK
B PHASE
RED
C PHASE
BLUE
NEUTRAL
WHITE
GROUND
GREEN
277/480V, 30
A PHASE
BROWN
B PHASE
ORANGE OR
PURPLE
C PHASE
YELLOW
NEUTRAL
GREY
GROUND
GREEN
DC VOLTAGE
POS (+)
RED'"
NEG (-)
BLACK"`
' SEE NEC 210.5(C)(1) AND (2)
'" POLARITY MARKED AT TERMINATION
1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION
AND AC POWER GES'S) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER
BONDING CONDUCTORS IN ACCORDANCE WITH THE NEC.
2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE
1100 AND 81) FOR GROUND ELECTRODE SYSTEMS, THE CONTRACTOR SHALL FURNISH AND INSTALL
SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND
CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR
DAMAGE TO THE CONDUIT AND PROVIDE TESTING RESULTS.
4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED
BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH #6 COPPER WIRE UL APPROVED
GROUNDING TYPE CONDUIT CLAMPS.
5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR.
STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC,
SHALL BE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS EQUIPMENT.
6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN
INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, #6 STRANDED COPPER OR LARGER FOR
INDOOR BTS; #2 BARE SOLID TINNED COPPER FOR OUTDOOR BTS.
7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK
CONNECTIONS ON OPPOSITE SIDE OF THE GROUND BUS ARE PERMITTED.
8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING
SHALL BE #2 SOLID TINNED COPPER UNLESS OTHERWISE INDICATED.
9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING
CONNECTIONS.
10. USE OF 90° BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45° BENDS
CAN BE ADEQUATELY SUPPORTED.
11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE.
12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH
PRESS CRIMPS.
13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS.
14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE
AND THE TOWER GROUND BAR.
15. APPROVED ANTIOXIDANT COATINGS (i.e. CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL
COMPRESSION AND BOLTED GROUND CONNECTIONS.
16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL.
17. MISCELLANEOUS ELECTRICAL AND NON -ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE
BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC.
18. BOND ALL METALLIC OBJECTS WITHIN 6It OF MAIN GROUND RING WITH (1) #2 BARE SOLID TINNED
COPPER GROUND CONDUCTOR.
19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS
SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR,
SUCH AS METALLIC CONDUITS, METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS.
WHEN IT IS REQURED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL
CONDITIONS, NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE USED. WHERE USE OF METAL
CONDUIT IS UNAVOIDABLE (i.e., NONMETALLIC CONDUIT PROHIBITED BY LOCAL CODE) THE GROUND
CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT.
20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID
TINNED COPPER IN 3/4" NON-METALLIC, FLEXIBLE CONDUIT FROM 24- BELOW GRADE TO WITHIN 3" TO V.
OF CAD -WELD TERMINATION POINT. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH
SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL).
21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE, THE
CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP, TOWERS, AND
WATER TOWERS GROUNDING RING, TO THE EXISTING GROUNDING SYSTEM, THE GROUNDING
CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE
BONDED TO THE EXISTING GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS, LIGHTNING
PROTECTION SYSTEM, AND BUILDING MAIN WATER LINE (FERROUS OR NONFERROUS METAL PIPING
ONLY).
M
• w T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4 11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
L GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
AIRE
0
03/05/2021
DTC
FINAL CDs
MRL
9 1
hto
i STEVEN P SCHAUB i
rrl q.. 114023 ¢i
03/05/2021
GPD Group, Professional Corporation
Texas Registration No. 16477
ELECTRICAL SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
ST-3 HEET NUMBER: REVISI0ON:
INSTALLER NOTE: USE EXISTING CONDUIT IF IT
MEETS CURRENT STANDARDS.
�x
�x x
X X -*Ax X _X x �—
X
X X
(E) OTHER CARRIER
EQUIPMENT PAD
x �x x �x x �x x �x x rx x �x
x X X X X x X X X X x X X X X x
X
X
+ +
+ +
+ +
+ +
(E)OTHERCARRIER
+
EQUIPMENT PAD
+
X
X
+ +
+ +
+ +
+ +
+ +
+ + + +
X
+ + + +
+ + + +
+ + + +
+
+
+
+
+ +
+ +
X
X
+
+
+ +
+
+
+
+
+
+ +
(E) T-MOBILE
+
+
(E)T-MOBILE DIPLEXERS TO BE
+ +
FCOACABINETTO
+
+
RELOCATED TO REMAINING
+ +
BE REMOVED —
+
+
FCOA CABINET LOCATION
+ +
X
+
+
+
+
(6 TOTAL)
T
+ +
+ +
+
+
+
+ +
+ +
+
+
+
+
+
- (E) T-MOBILE HCS 1.0
+ +
+ +
+
+
+
+
+
COVP TO BE REMOVED
+
+ +
+
X
+
+
+ + + t�
+ +
+
+ +
+
+
+
(E) T-MOBILE FEEDLINES TO REMAIN
+ +
+ +
+
+
+
+ +
+
(RE-ROUTE TO RELOCATED
+ +
+
+
+
DIPLEXER LOCATION)
+
+
+
+ +
+
X
(12) 7/8., COAX
+
+ +
+
(E) T-MOBILE HCS 1.0 HYBRID +
+
+ + +
+ +
CABLE TO BE REMOVED
+
+
+
+
+ +
+
X
+
(E) T-MOBILE
BATTERY CABINET
TO BE REMOVED -
(E) CHAIN LINK FENCE
X�
I
X
/ x
(E)T-MOBILEFCOA X
CABINET TO BE
RELOCATED
(E) T-MOBILE HCS 1.0
COVP TO BE REMOVED
X
+ + + + + + + + + + + + + + + + + + + + + + + +
+ + + + + + + } + + } + + + + } + + } + +
+ + + + + + + + + + + +
+ + + + + + + } + + + + + + + } + + + + + X
+ + +
+ + + + + + + + + + + + + + + + + + + + + + + +
+ + + + + + + + + + + + + + + + + + + + + + + + + 16'-0"
+ + + + + + + + + + + + + + + + + + + + + + + +
+ + + + + + + + + + + + + + + + + + + + + + X X X X X X — X X X
— X X X X
(E) 70'-9- MONOPOLE (E) T-MOBILE SSC (E) T-MOBILE
CABINET TO BE REMOVED ICE BRIDGE
(E) T-MOBILE HCS 1.0 HYBRID
CABLE TO BE REMOVED
�-� OVERALL SITE PLAN
SCALE. &8"=1'1-'-0'(11UL(FLx17)SIZE) N
2' 1' 0 2' 3/ifi•=
(E) OTHER CARRIER
EQUIPMENT PAD
(E) T-MOBILE METER
(E) T-MOBILE DISCONNECT
(E) T-MOBILE PPC CABINET
(E) T-MOBILE CIENA
Planning
Administrative Approval
COFFELL
03/25/2021
• m T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
, AA�w
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4 11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIARNARY
AIRE
0
03/05/2021
DTC
FINAL CDs
MRL
1P,itt•OF.r "SShI,
CHRISTOPHER J. SCHEKs i
oi, 111I836 :�•
94e••.��ceNse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-1.1 0
INSTALLER NOTE: USE EXISTING CONDUIT IF IT
MEETS CURRENTSTANDARDS. KEYED NOTES:
FINAL EQUIPMENT INSIDE FCOA CABINET, HP
LARGE 3 CABINET & AMIA UNITS:
(1) EX. FSME
(1) EX. ESMB
(3) EX. FRIAs
(1) EX. FXFB
(3) AMIA.
(3) ASIBs
(2) ASIKs
(5) ABIAs
(3) ABICs
(6) ABILs
AMIA AIRSCALE SUBRACK HOUSES UP TO (2)
ASI(x) & (6) ABI(x) UNITS.
(E) 70'-9- MONOPOLE
FROM OLD DIPLEXER LOCATION
(12) 7/8" COAX CABLES
X X X X X X- X X X X
FROM OLD FCOA LOCATION
X X X X
�� FINAL EQUIPMENT PLAN
�/ SCALE. 3l4"=1'-0"(FULL SIZE) 131
1' 6" a 1' 3I8'=1'-0"(11z17) IV
X
X X X X X
OPROPOSED (2) 2" RIGID CONDUITS TO BE ROUTED
FROM THE FCOA CABINET TO HP LARGE CABINET 3
FOR FIBER CABLES & DC POWER CONDUCTORS
FOR PROPOSED UNITS
PROPOSED (2)1-1/2" RIGID CONDUITS TO BE
ROUTED FROM THE HP LARGE CABINET 3 TO AMIA
UNITS FOR FIBER CABLES & DC POWER
CONDUCTORS FOR PROPOSED UNITS.
(E) T-MOBILE METER
(E) T-MOBILE DISCONNECT
(E) T-MOBILE PPC CABINET
(E) T-MOBILE CIENA
Planning
Administrative Approval
COPPELL
03I25I2021
• w T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH —11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
IGPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
LITE
PRELIMINARY
AIRE
0
03/05/2021
DTC
FINAL CDs
MRL
1p�E'F.r' s
CHRISTOPHER J. SCHEO i
119838
94e••.��ceNse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
INSTALLER NOTE:
SHEETNUM
REVISION:
CONTRACTOR SHALL RESPONSIBLE FORCIRCUIT
SELECTION ANN D WIRE SIZING FOR NEWCABINETS
C-1.2
0
BASED ON MANUFACTURER
RECOMMENDATIONS AND NEC REQUIREMENTS.
OVERALL SI
HEIGHT = 79
y
T-MOBILE M
CL = 73'-0'
TOP OF TOV
41 HEIGHT=70
OTHER CAR
C
OTHER CAI
CL = 55'-0"
OTHER CAR
C
(P) T-MOE
(3) 1-1/2"
(E) T-MOE
(12) 7/B"
(E) 70,_g.
1/
1 I FINAL TOWER ELEVATION
�/ SCALE: NOT TO SCALE
=NNA
ATFORM
R 7'�o7sT7N
30oa S79 22 q (E) 70._9„
/T OS 7pp
oR@�q2N
(E) T-MOBILE ECC1920-VPUB DIPLEXERs
TO BE REMOVED
(24 TOTAL, 4 PER SECTOR)
G�P01,
�
Jy1O�0�p°° � OFl
j
J�1p15 -X1��t.�
OeA \ O /
(E) T-MOBILE TMAT1921 B78-21A
TMAS TO BE REMOVED
(6 TOTAL, 2 PER A/B/C SECTORS)
(E) T-MOBILE FRLB RRU TO BE REMOVED
(3 TOTAL, 1 PER A/B/C SECTORS)
(E) 70'-9" MONOPOLE
�7'STi
N@ �790 NG
�P3 0,33 �9�27 �TF
/TOOS
RF7�M
(P) T-MOBILE AHFIG RRU
Y/
(6 TOTAL, 1 PER SECTOR)
PT -MOBILE AHLOA RRU
TOTAL, 1 PER A/B/C
SECTORS)
lea FOR
1
RQQQ-
OQOgE a O�
ey"
(P) HANDRAIL KIT
(SITEPRO1 - HRK12) TO
REPLACE EXISTING —
¢oN0
¢jNQ
a�
;i
¢mom
¢mH
mm
0
tx~xii ort
xx� o
�'x
Wo=N
¢
j
�® „`u"
Ak—
e/I
4i
0
O.oT
m v+Nm
z�oz
'C\NO�pJyP�jtN
19pO 3�' OR
(E) T-MOBILE FHFB RRU TO BE REMOVED
(6 TOTAL, 1 PER SECTOR)
(E) T-MOBILE FRIG RRU TO BE REMOVED
(6 TOTAL, 1 PER SECTOR)
(E) T-MOBILE HCS 1.0 COVP TO BE REMOVED
(2 TOTAL)
RF'yo
,,- 1/ EXISTING ANTENNA LAYOUT
�2 SCALE: NOT TO SCALE N
xam �
¢NUo
¢.mo
zo0
yo
Nam>
yNXno�
o-21
o
O�>�
w mN
x
am`
m
x
� oz
Ayom
Z z
p�V"(P
I'll
eps���,t
9
\ae 6O
0 VA
Py
(N) T-MOBILE HCS 2.0
PENDANT (3 TOTAL)
°R
Op0
s
0
.g2'9Fy 2SOo Tq
720>
�T�/C pRO.o
F wO
�NSoo@O@F
�h��330�s@FTA
20, 7go 00
?O S
RF�M
N/
FINAL ANTENNA LAYOUT
J SCALE: NOT TO SCALE
N
TOWER & ANTENNA STANDARD NOTES:
A. TOWER STRUCTURAL ANALYSIS BY B+T GROUP, DATED 01/22/2021. NO NEW ANTENNAS OR
EQUIPMENT INSTALLED WITHOUT APPROVAL OF STRUCTURAL ENGINEER AND CROWN
CASTLE USA INC.
B. MOUNT ANALYSIS AND COMPLIANCE PERFORMED BY INFINIGY ENGINEERING, PLLC, DATED
01/28/2021. NO NEW ANTENNAS OR EQUIPMENT INSTALLED ON MOUNTS WITHOUT THE
APPROVAL OF A STRUCTURAL ENGINEER.
C. INSTALLED EQUIPMENT MUST HAVE A MATCHING CROWN CASTLE USA INC. APPLICATION
AND STRUCTURAL ANALYSIS.
D. PRIOR TO ATTACHING ANTENNAS AND MOUNTING SECTIONS, (E) TOWER AND TOWER
FOUNDATION MUST BE ANALYZED BY A LICENSED STRUCTURAL ENGINEER TO VERIFY
TOWER IS CAPABLE OF SUPPORTING THE PROPOSED LOADS. REFER TO STRUCTURAL
ANALYSIS BY OTHERS.
E. NEW EQUIPMENT CANNOT BE MOUNTED TO TOWER. RELOCATE EXISTING TOWER
MOUNTED EQUIPMENT TO CUSTOMER MOUNT.
F. DURING INSTALLATION, THE RADIOS ARE NOT TO EXCEED 5'-0" FROM THE WORKING
SURFACE TO THE TOP OF RADIOS.
G. DIRECT TOWER MOUNTED EQUIPMENT MUST NOT TRAP OR INTERFERE W/CLIMBING
PEGS/STEPS AND SAFETY CLIMB.
H. VERIFY AZIMUTHS WITH RFDS.
I. 2' ANTENNA SEPARATION REQUIRED. CONTRACTOR TO MOVE (E) ANTENNAS TO ENDS OF
MOUNT AS REQUIRED.
J. PROPOSED ANTENNA PLACEMENT LOCATION TO BE FIELD VERIFIED BY GENERAL
CONTRACTOR PRIOR TO CONSTRUCTION TO AVOID ANY INTERFERENCE OR SHADOWING OF
EXISTING ANTENNAS. IF INTERFERENCE OR SHADOWING OF EXISTING ANTENNAS IS
DISCOVERED DURING FIELD VERIFICATION, PLEASE CONTACT (A&E VENDOR) FOR DESIGN
REVISION PRIOR TO ANY NEW ANTENNA INSTALLATION.
K. DO NOT OBSTRUCT BEACON IF TOWER LIT.
L. TOPSIDE FIBERS TO BE SLEEVED IN FLEXIBLE INNERDUCT TYPE OR SPLIT CONDUIT TO
PREVENT BIRDS FROM DAMAGING FIBER OPTIC CABLE.
M. TOP AND BOTTOM OF ALL COAX RUNS ARE TO BE LABELED WITH A BRASS TAG ID WITH
NAME OF THE LESSEE ON IT.
INSTALLER NOTE:
INSTALLER NOTE:
ALL EXISTING AND PROPOSED T-MOBILE
EQUIPMENT MOUNTED TO THE TOWER SHALL • NEW EQUIPMENT CANNOT BE MOUNTED TO
BE RELOCATED TO CUSTOMER MOUNT PER TOWER.
CROWN CASTLE USA INC. LATEST • RELOCATE EXISTING TOWER MOUNTED
STANDARDS EQUIPMENT TO CUSTOMER MOUNT.
INSTALLER NOTE: INSTALLER NOTE:
CONTRACTOR TO VERIFY ALL ANTENNA TIP I DIRECT TOWER MOUNTED EQUIPMENT MUST
HEIGHTS DO NOT EXCEED BEACON BASE NOT TRAP OR INTERFERE W/ CLIMBING
HEIGHT. PEGS/STEPS AND SAFETY CLIMB.
Planning
Administrative Approval
COPPELL
? .'�wse
03/25/2021
• m T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
, AA�w
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH —11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE I
L GPD JOB NUMBER: 2020724.78.876558.01
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
MRL
0
03/05/2021
DTC
FINAL CDs
MRL
1P,itt•OF.r "SSh
CHRISTOPHER J. SCHEKS i
oi, 111I836 :�•
94e••.��ceNse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISI
C-2 0ON:
MANUFACTURER DELTA
MODEL: HPL3 SITE SUPPORT
CABINET
WEIGHT. 551 LBS (WITHOUT
EQUIPMENT)
NOTE.
• CORRECT KNOCKOUT TOOL REQUIRED
FOR PUNCHING KNOCKOUTS DO NOT
DRILL KNOCKOUTS THROUGH
• CONDUIT MUST BE PROPERLY SECURED
TO PREVENT DAMAGE TO CABINETS
AND/OR CABLING
RACK ASSIGNMENT
RU SLOT DESCRIPTION DESCRIPTION
21
26
2S
24 AIRSCALE
23
22 FIBER Mlx
21
20 AIRSCALE
19 �U
18 FIBER M/K
IT
16 AIRSCALE
Is
14 FIBER MTX
13
12 AMSCALE
II
10 FIBEEll MTX
9
6 LEGACY
BASEBAND
T
6
S LEGACY
BASEBAFD
3
2 LEGACY
T BASEBAND
BACK PANEL
FOLDS OUT -
SKIT. 33554 DELTA 6• PLINTH
SHOP• G,HOOKS TO
BE REMOVED AFTER
CABf — - --
ISO VIEW N.T.S.
22 T
REAR VIEW
AK TSn
FOR CM94E T
ATTACHMENT
FRONT VIEW
3, 3
X R
ACCESS PLATES
-USE III TOR),
w
0
26 tr
„4
SKU# 33554 DELTA 61n PLINTH SKU# 33554 DELTA 61N PLINTH
PLAN VIEW
SIDE VIEW
BATTERY CABLE ROUTE
--
11I r LB OR LL (L.L PREFT:.RAED)
KNOCKOUT WITH THE FOLED
b
FOR THE OC WIRE RUNNING
PBATTERY CABLE
PROVIDEDD THIS THE ONLY
PROVIDED
FROM THE DC RECTIFIER TO
O ,
OO
THE COUP FOR "CS 20 THERE
ARE (3) PARS FOR A B. G
KNOCKOUT YOU CAN
AN LOSE. —
(1 )4• RIGID CONDUIT
FOR
THIS PANEL OF KNOCKOUTS(WATER•TKWn
ROUTING BATTERY CAKE
INTENDED FOR RUNNING DC
THE T
TO THE RECTKER
WIRES TO THE COUP
rnroR2•1truOR
WATER -TIGHT GROMMET IS USED
HERE FOR THE BOTTON FIBER
JUMPERS TO 6 FROM TFE COUP
FIBER ROUTE OPTIONS
INItNDto#ORAC
INPl1T WINES FROM PPO--�
LEFT VIEW
I• KNOCnWT3 ARE
INTENDED FOR (I)OC POWER
TO THE CIENA (2)ETHER►ET
OR FIBER CABLE FROM THE
C*NA OR TELCO. WI ALARM
CABO!51 ROM IHe PVC
1 i 1 T LL IS USED FROM A
FLExSLE TO RIGID CONDL
THAT RUNS ALL THE WAY
THE PPC FOR AC WIRES
THAT TERINfWLTES TO THE
CABNNETS AC TERMINALS
L` I
ru
RIGHT VIEW
.1.
��_LTIYII��T�
Mid
133554 DELTA W PLINTH
Xt
CH DRAIN
DC BREAKER
PROPOSED
VERTICAL BA
IRU FIBER
MUXOEMUx
PROPCISI. D
GROUNDING
BAALOCATK
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
INTERNAL ROUTING
FRONT VIEW
(OPEN)
ACCESS
PANEL
RECtIrIERS
CSR SAW SAS
ROUTER
MRSCALE
BASESANO
HORIZONTAL
CABLE
MANAGEMENT
BAR
LEGACY
BASESAND
T B Mobile
7668 WARREN PARKWAY
FRISCO, TX 75034
CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4 11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
LITE
PRELIMINARY
MRL
0
03/05/2021
DTC
FINAL CDs
MRL
Planning
Administrative Approval
copPEii
03/25/20
CHRISTOPHfiR J. SCHEKS
oi, 111a030.....:�•
94e •.TrceNse°..�A
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
1 UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-5 0
MANUFACTURER: DELTA
MODEL: SB3 BATTERY SUPPORT CABINET
WEIGHT: 310 LBS (WITHOUT EOUIPMENT)
DIMENSIONS: 15 0'x35.0'x72.0'
NOTE:
• CORRECT KNOCKOUT TOOL REQUIRED FOR
PUNCHING KNOCKOUTS. DO NOT DRILL
KNOCKOUTSTHROUGH
• CONDUIT MUST BE PROPERLY SECURED TO
PREVENT DAMAGE TO CABINETS ANWOR
CABLING
b
N
FRONT VIEW
SIDE VIEW
PLAN VIEW
ISO VIEW
PLAN VIEW
(ANCHORAGE)
S• REAR
CLEMMrCF
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
BATTERY
BRACKET
15, or
I u ul
o o
Ll
0 0 0 0
I L—T
00
0 0 0 0 4x BATTERY SHELVES
iATTER'Y VIlRAT1t)N
SKLI# 33936
MOIMT
SKLI# 33936
DELTA SB3 61N
DELTA SB3 61N
PLINTH
PLINTH
PLAN VIEW
SIDE VIEW
SKU• 37f4T0 OEITA SBJ
I
M
SKU# 33931- DELTA SB3 BATTERY
7Ti34- SCALE N
SUPPORT CABINET
T S I t 1l1 T wALE N.T. S
• T • -Mobile
7668 WARREN PARKWAY
FRISCO, TX 75034
I
CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4 11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
LGPD JOB NUMBER: 2020724.78.876558.01�JOB NUMBER: 2020724.78.876558.011
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
MRL
0
03/05/2021
DTC
FINAL CDs
MRL
,1p`I. E OF.r "SShI,
CHii. T FHER J. SCHEKS l
1191M
A4e••.ticegse°.�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISI
C-6 0ON:
II
I
I
I
I
I
I
I
I
I
I
Mile nm taTA w 1L1TIM PM wu w-
IWO "M pdTA V RJM 1a 93
N
ON
SIDE VIEW
Pi10P0 IE0 DELTA SM BATTERY CANDOET
ITiI1TH PROPOSED DELTA WU GM DC
CABINET A (2) R)TURE CAB I ET$ BEYONM
♦'
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
74r IN tT Zr r 11 7.6' r t'-T
4.
MANGE �_____— ,______—
I I I I
I I I
IRJTURE) I I IPUTUREI I PIIOPOBPROPOBEO
OC CA TA DELTA BB3
NP4T BtIBA oc CA61ET "TTERY
I I I CAMW
I I I
L_____J L_____J
I
I
I
L-------------------------------
PLAN VIEW
Jnvs JJJLJ - NCL I A J7rLJ 011 C JVrrVK I L#ADIMC I *ZJ LA TWU I
11
2rxm-w.ALE.N.Ts T1'1l PILT.s.
A EDDELTA
PRO3EDOELB�T_
P_ROPOSIIIIIIIII
HP3 SOA DC CABO* T S07 BATTERY
CABI
_ _ _ _ _ _ _ _ _
I F- - - - - -
IIIIIIIII
OUTUM) OUTLINE)
I
+ I I I I
j I I I slw. xiooB oaTA
BorPL.+It'
I I I
j I
Planning
— — Administrative Approval
COPPELL
rr e• Z4r a r•e• r T•-r
11••T WORIONG CLEARANCE -
FRONT VIEW 3" JMU DELTA 6* PLM(TH o3/zs/zozl
SKU9 33929 - DELTA NPL3 SITE SUPPORT CABINET S83 LAYOUT
2
Zrx34' SCALE N I S 11911T SCALE N 1
T • Mobile -
7668 WARREN PARKWAY
FRISCO, TX 75034
CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH —11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
AIRE
0
03/05/2021
DTC
FINAL CDs
MRL
,1p`E OF.r "SShI,
CHRISTOPHER J. SCHEK9 i
oi, 111I836 :�•
94e••.��ceNse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C 7 0-0
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
0
WEIGHT (WITHOUT MOUNTING HARDWARE): 124.6 LBS
SIZE (HxWxD): 95.9x25.2x9.3 IN.
1 OCTO PORT ANTENNA
SCALE: NOT TO SCALE
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
BASED BOX ASSEMBLY
HEAT SHRINK TU
BRID CABLE
WEIGHT (WITHOUT MOUNTING HARDWARE): 23.5 LBS.
SIZE (HxWxD): 14.Oxi6.Ox8.0 IN.
A� PENDANT DETAIL
SCALE: NOT TO SCALE
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIMS) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
WEIGHT (WITHOUT MOUNTING HARDWARE): 108.0 LBS
SIZE (HxWxD): 38.2x21.5x5.9 IN.
n
SCAAEHC SPECIFICATIONS
L LE: NOT TO SCALE
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
WEIGHT (FULLY EQUIPPED): 83.8 LBS
SIZE (HxWxD): 22.1x12.1x7.4 IN.
CONNECTOR TYPE: 4.3-1 FEMALE
r� SCALEAHLOA RRU DETAIL
`� : NOT TO SCALE
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
FRONT
SIDE
0
TOP
WEIGHT (WITHOUT MOUNTING HARDWARE): 23.5 LBS.
SIZE (HxWxD): 14.0x16.Ox8.O IN.
JUNCTION BOX DETAIL
`� SCALE: NOT TO SCALE
THIS DETAIL HAS NOT BEEN REVIEWED BYTHE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISKAND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
WEIGHT (FULLY EQUIPPED): 70.5 LBS
SIZE (HxWxD): 27.3xl2.ix5.2 IN.
CONNECTOR TYPE: 4.3-1 FEMALE
AHFIG RRU DETAIL
v SCALE: NOT TO SCALE
Planning
Administrative Approval
COFFELL
T
03/25/2021
• III T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH —11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
L GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
AIRE
0
03/05/2021
DTC
FINAL CDs
MRL
tpI �F.r'
CHRISTOPHER J. SCHEKS i
oi, 111I836 :�•
94e••. ��ceNse°..�A'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET CNUMBER: REVISION:
8 0
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
AirScale Architecture
Nokia AirScale Subrack (AMIA)
Nokia Air Scale Subrack (AIItIA) rnain properties
-It supports up to two AirScale Common plug-in units
•It supports up to six AirScale Capacity plug-in units
•IP20 ingress protected
-Operating temperature range from -51C to •551C
-It might be installed inside a 19-inch wide rack or cabinet r "
The AirScale Subrack Ak11A includes
-Subrack frame
•Backplane for high bandwidth interconnect between AirScale Common and -
AirScale Capacty plug-in units
-Fans with changeable airflow direction
-Blind-units to prevent cooling airflow leakage
�.d. In a ...,/ t w .
w�rF rr4 � 11nt a y
Mt Mwr ^/� t ■ 1,it .. �Y�
M.
�-� AMIA SPECIFICATIONS
i SCALE: NOT TO SCALE
DETAIL NOT USED
J SCALE: NOT TO SCALE
n� DETAIL NOT USED
SCALE: NOT TO SCALE
A� DETAIL NOT USED
SCALE: NOT TO SCALE
Planning
Administrative Approval
COFFELL
03125/2021
• III T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4 11
330.572.2100 Fax 330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 70'-9" MONOPOLE
L GPD JOB NUMBER: 2020724.78.876558.01 J
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
MRL
0
03/05/2021
DTC
FINAL CDs
MRL
CHRISTOPHER J. SCHEKS i
oi, 111xi36 :�•
is ......
03/05/2021
GPD Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-9 0
A
SBS IingtTBrmiral
�•• TP.rP. .f VI',V`ll`!r'f.3fi0i15 fJFF.""fnrmfiieT°
Ti po'ryaeCef� EL.`. rraz Terriri 3l battarftaHYar aier,tls the
teenrl,ml Ie. darg„v rrma vvwsaat3 ses Baran• r.rga,
PweerGafe 5'�5 Nrnt-ennlrq rlorohlors Iota In the Lei�ita a'
Thin FIl'o P-L, 7PPL)trchnology cuchac Irnglifc,high
pnFrgf can=_ry an7 sunen rr sren ure-Trey a �r re r.re�
etseddmal cycicrarf ormanre In bath float arc `Bet the rqe
aprl Intiors, cv51 Ir the aottcsl and harshasl opa�.ting
arwrrnmrrn;
Vl;ee nlmRicreltielr Peyulat::t Leetl Acid IJFiV.1l
4bccrboi Glo oc 41at W.GMI 6otton� rtruAOc-o c7ac dr'kL homy
onnlrlev ard-reraEnt porvar cutecas, amrn7 ege Ir'r'L
techno cyx nah; P>rrei�af:: SB^u battxri::e tle perteR Soletior -ol
th 1,II B p N g -d,i olt ay -I nlJ-
netw rk
Pw Sr Si5hll 'i d'y '.Ili,1'g fy ill
sI d 't -ii Unrqp' p dii,q
llPg' 91 III 9 P r
'rAi bll I' ThDie IIo substlthte for Poty &ale SEE-rort Term nal
batleri e:.
FhaNmsard Bcaeloa
• Cepe�i 'a nye _1-19oA1
• 121,'monoeloe ton`OJYOII]i:
• N1 III'nn'101ira11rrF avallahla
T- year :hell Ii-e
5 H�•1'['.a corrpllart
• Pr rvxllin L'. ;xlilrxl IN
iah e, I, l::rs ty end c,: Ing caplbllN
�'
RF4F EVF
L'13t do d yky,-r-yl-i PC1'NER� PoLtuuI111a. JI3 8M3fFdme3P8
BATTERY SPECS
SCALE: NOT TO SCALE
DETAIL NOT USED
�SCALE: NOT TO SCALE
Co 1 t1
L
d3n=ry
h
yeal3q fir- Th= i h �abzofi tl M Pnt
g.mase
r tlt�req.r:=<elf d' N dfl ms
3�d cwe rPade-rcrnf arse r:`ar];r.
i1 aavo „rr,-Ia, monNie, <,am.�.;nen,rla
a evert in,,- d mmo=rFerc ozypan
R. Ila[I Y Upetallon
r3Lad
Lfi gl v,dhly raw Nardi ry
3--11 D -,l'F rlea:a toe wrc0.loreorr�loteden lc
ofrp o> rn y°5x I
sin, E°,� a.w,�vh v�el�e.t':.;sEe m
c vuw.vM Lur1lPm+m eu1lnlrtil �.
d -. I�IFF�TMIrrtor�Lmwlz
� (Uti�[FibrY,_� inr rmn r.rn rr >f`��pr nre`iro u�
miammoNEEMEM
�ereral SFedlka;lans
565F8� 6 �31F p:1n 11.9 3)3 3k) 91L 6F In 2Ei 113 12A alGo� ME Nk 03i 1A 0.G5 1E1 A11 n0] 1EI ]]3 IFb ].�
5-111 2 m 113 m3 lio vl of N ran 13.1 Imo 1. 1 lrl GT 1. B1. i513 G12 n83 .[5 153 23b 3'4
595C11 6 £1 16 AI A.I] 106 G.I iS 61b 98 iti Fk) MEN I ix 139 1. A36 13 !fG IB A3a R]
6r51101 82 Im it 1 A 5l9b] IQ IS b7 711 539 210 'E] MfN I5V Sn3 116 Gm [ 8 1F3 ] 5 e1 .5
I - u w -nd tie
6r5111 8 I8< 1G 1 d 4i3 bA lK 08 21 11: 28 TA 2b) Mf N 2F� 3 r 85 1 A A94 .2 02 1A g1 11
G6G13[F G . 19 liC 12. £I 4T li 24 )G 1S G)) :oA ;S M[N 2l4 )i Z311: A)G ND ill 32G uA q9
s5 olr- 14f so51Wr-112r MIIMrriff nor
SBS CI IF
• �� t �-t wnxear S
THIS DETAIL HAS NOT BEEN REVIEWED BY THE STAMPING PARTY.
THEREFOR, THE STAMPING PARTY MAKES NO REPRESENTATION(S) WITH
RESPECT TO ITS CONTENTS, AND SHALL NOT BE LIABLE FOR SUCH. THIS
DETAIL IS FOR REFERENCE ONLY. ANY RELIANCE ON THIS DETAIL SHALL BE
AT THE RELYING PARTY(IES)'S OWN RISK AND HEREBY WAIVES ANY AND
ALL CLAIM(S) RELATED TO THE EXISTENCE OF THE STAMP OR OTHERWISE.
BATTERY INFORMATION (BATTERY ELECTROLYTE DATA-12V MONOBLOCS)
TOTAL # OF
TOTAL ELECTROLYTE
TOTAL ELECTROLYTE
% SULFURIC ACID VOLUME/UNIT
BATTERY MODEL
BATTERY UNITS
VOLUME (GAL.)
WEIGHT (LBS.)
ACID BY ELECTROLYTE
INSTALLED
PER UNIT
PER UNIT
VOLUME = VOLUME PER UNIT
ENERSYS POWERSAFE
SBS FRONT TERMINAL
8
2.34 GAL.
25.3 LBS.
28.2% = 0.66 GAL./2.34 GAL
(SBS 190F)
% SULFURIC TOTAL ACID WEIGHT
TOTAL TOTAL UNITS X
TOTAL TOTAL UNITS X
ACID BY TOTAL ELECTROLYTE
SULPHURIC SULPHURIC
SULPHURIC ACID
WEIGHT= WEIGHT
VOLUME (GAL.)= VOLUMEIUNITS
WEIGHT(LBS.)= WEIGHT/UNIT
5.28 GAL. = 8 UNITS X
80.8 LBS. = 8 UNITS X
39.9% = 10.1 LBS./25.3 LBS.
0.66 GAUUNIT
10.1 LBS.
NFPA 1, CHAPTER 52 COMPLIANCE
TOTAL ELECTROLYTE=
8 BATTERIES X 2.34 GAL/BATTERY
= 18.72 GAL
(SINCE -50 GAL OF ELECTROLYTE - REQUIREMENTS OF NFPA 1, CHAPTER 52 NOT APPLICABLE)
IFC, CHAPTER 12, SECTION 1206 COMPLIANCE
STATIONARY STORAGE BATTERY SYSTEMS HAVING CAPACITIES EXCEEDING THE VALUES SHOWN IN TABLE 1206.2 SHALL
COMPLY w/ SECTION 1206.2.1 THROUGH 1206.2.12.6, AS APPLICABLE.
BATTERY STORAGE SYSTEM THRESHOLD QUANTITIES
BATTERY TECHNOLOGY
CAPACITYALLOWED
LEAD ACID, ALL TYPES
70 kWh (252 MEGAJOULES)
AH = VOLTAGE (AH) / 1000
VOLTS
AH
I kWh
NO. OF BATTERIES
TOTAL kWh
12
190
1000
2.28
8
18.24
CONCLUSIONS
18.24 < 70 kWh SECTION 1206.2 DOES NOT APPLY
BATTERY DATA CHART
BATTERY DATA CHART
SCALE: NOT TO SCALE
A� DETAIL NOT USED
SCALE: NOT TO SCALE
Planning
Administrative Approval
COPPELL
03/25/2021
• w T • mMobile •
7668 WARREN PARKWAY
FRISCO, TX 75034
0 CROWN
v CASTLE
6191 N STATE HIGHWAY 161, SUITE 200
IRVING, TX 75038
GPD GROUP
Professional Corporation
5211 Main Street, Suite 2531
Akron, Olf -11
330.572.2100 1330.572.2101
T-MOBILE SITE NUMBER:
DA01328A
BU #: 876558
F3 - COPPELL MIDDLE S
1301 WRANGLER
COPPELL, TX 75017
EXISTING 71 MONOPOLE
L GPD JOB NUMBER: 2020724.78.876558.01
ISSUED FOR:
REV
DATE
DRWN
DESCRIPTION
DES./Q
0
02/09/2021
DTC
PRELIMINARY
MRL
0
03/05/2021
DTC
FINAL CDs
MRL
tp�tt �F.r• ''shI,
CHRI6TOPHER J. SCHEKS i
oi, 111I836 :�•
94e••. ��ceFLse°.�'�'
is ......
03/05/2021
GPO Group, Professional Corporation
Texas Registration No. 16477
TELECOM SEAL
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-10 0