876558_CD_FINAL_REV2_S&S_VRZ_5G_LSUB6_MOD_09-13-2021_v1.ADM_APPverizon)/
VERIZON SITE NUMBER: 295251 BUSINESS UNIT #:
VERIZON SITE NAME: WRANGLER SITE ADDRESS:
SITE TYPE: MONOPOLE COUNTY:
TOWER HEIGHT: 71'-6" JURISDICTION:
SITE INFORMATION
CROWN CASTLE USA INC.
F3 - COPPELL MIDDLE S
SITE NAME:
SITE ADDRESS:
1305 WRANGLER CIRCLE
COPPELL, TX 75019
COUNTY:
DALLAS
MAP/PARCEL #:
65-0056-405-005-00-000
AREA OF CONSTRUCTION:
EXISTING
LATITUDE:
32° 56' 5.32"
LONGITUDE:
-97° 0' 5.84"
LAT/LONG TYPE:
NAD83
GROUND ELEVATION:
526.5 FT
CURRENT ZONING:
----
JURISDICTION:
CITY OF COPPELL, TX
OCCUPANCY CLASSIFICATION:
U
TYPE OF CONSTRUCTION:
IIB
A.D.A. COMPLIANCE:
FACILITY IS UNMANNED AND NOT FOR
HUMAN HABITATION
PROPERTY OWNER:
COPPELL INDEPENDENT SCHOOL DISTRICT
TOWER OWNER:
CROWN CASTLE USA, INC.
1220 AUGUSTA DRIVE
HOUSTON, TX 77057
CARRIER/APPLICANT:
VERIZON WIRELESS
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
ELECTRIC PROVIDER
ONCOR
888-313-4747
TELCO PROVIDER
VERIZON
800-483-2000
PROJECT TEAM
DESIGNER FIRM:
BROADUS SERVICES
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS, TX 76016
PH: (817) 349-3449
ENGINEER FIRM:
CAA SOLUTIONS, PLLC
3400 STRATFORD ROAD
ATLANTA, GA 30326
PH: (770) 548-8268
CONTACT: ALEXANDER ABERNATHY, P.E.
CROWN CASTLE
1220 AUGUSTA DRIVE
USA INC. DISTRICT
HOUSTON, TX 77057
CONTACTS:
LAUREN WADE - PROJECT MANAGER
LAUREN. WADE@CRO WNCASTLE. COM
(972) 374-4010
JOEL MCCALL - CONSTRUCTION MANAGER
JOEL.MCCALL@CROWNCASTLE.COM
(512) 680-8108
NICK CHAPMAN - A&E SPECIALIST
NICHOLAS.CHAPMAN@CRO WNCASTLE.COM
VERIZON 5G L-SUB6 - CARRIER ADD
DRAWING INDEX
SHEET #
SHEET DESCRIPTION
T-1
TITLE SHEET
T-2
GENERAL NOTES
C-1
SITE PLAN
C-2
TOWER ELEVATION & ANTENNA PLANS
C-3
EQUIPMENT SCHEDULE
C-4
PLUMBING DIAGRAM
C-5
EQUIPMENT SPECS
C-6
EQUIPMENT SPECS
G-1
GROUNDING DETAILS
G-2
GROUNDING DETAILS
ALL DRAWINGS CONTAINED HEREIN ARE FORMATTED FOR
1X17. CONTRACTOR SHALL VERIFY ALL PLANS AND EXISTING
DIMENSIONS AND CONDITIONS ON THE JOB SITE AND SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY
DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR
BE RESPONSIBLE FOR SAME.
I CONTRACTOR PMI REQUIREMENTS 1
PMI ACCESSED Xi https://pmi.vx smut.com
SMART TOOL VENDOR
PROJECT NUMBER 10078301
VzW LOCATION CODE (PSLC) 295251
** PMI AND REQUIREMENTS ALSO EMBEDDED IN MOUNT
ANALYSIS REPORT J
MOUNT MODIFICATION REQUIRED y
VzW APPROVED SMART KIT VENDORS
REFER TO MOUNT MODIFICATION DRAWINGS PAGE FOR
VzW SMART KIT APPROVED VENDORS
876558
1305 WRANGLER CIRCLE
COPPELL, TX 75019
DALLAS
Planning Administrative
Approval
COPPELL
12/03/2021
CITY OF COPPELL, TX
LOCATION MAP
�Y9oa,
00
- Oraavasmnn
S'chml Of Sarre -g
l Vs
- The I Islrlol at Q
Cypress Womrc
x nm.0 n pea°"¢
r
s,"h 'e
fie
,:Io!India -Groceries, ge
Held IAaat 8 Restaurant 4
]1P.` 1Manw;Mns _-_ �Irvirg, Te
� � �Finc N6errr Cr ee �-Chuici �andnn.
PROJECT DESCRIPTION
THE PURPOSE OF THIS PROJECT IS TO ENHANCE
BROADBAND CONNECTIVITY AND CAPACITY TO THE
EXISTING ELIGIBLE WIRELESS FACILITY.
TOWER SCOPE OF WORK
• REMOVE (3) NOKIA - UHIE B66A RRH 4x45
• REMOVE (3) NOKIA - UHBA B13 RRH 4x30
• INSTALL (3) SAMSUNG - VZSOI INTEGRATED RRH &
ANTENNAS
• INSTALL (3) SAMSUNG - B2/B66A RRH-BR049 RRHs
• INSTALL (3) SAMSUNG - BS/B13 RRH-BR04C RRHs
• INSTALL (3) COMMSCOPE - BSAMNT-SBS-1-2 MOUNTS
• RELOCATE (E) ANDREW SBNHH-1D65 TO NEW DUAL
MOUNTS
GROUND SCOPE OF WORK
• TBD
FIELD VERIFY EXISTING
GROUND EQUIPMENT
CONFIGURATION. EXISTING
EQUIPMENT INFORMATION
NOT PROVIDED.
NOTE:
PRIOR TO ACCESSING/ENTERING THE SITE YOU MUST
CONTACT THE CROWN NOC AT (800) 788-7011 & CROWN
CONSTRUCTION MANAGER
APPLICABLE CODES/REFERENCE
DOCUMENTS
ALL WORK SHALL BE PERFORMED AND MATERIALS INSTALLED IN ACCORDANCE WITH THE
CURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNING
AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT
CONFORMING TO THESE CODES:
CODE TYPE CODE
BUILDING 2015IBC
MECHANICAL 2015IMC
ELECTRICAL 2014 NEC
'
verizon'
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS
services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./QA
CDO
05/17/2021
ND
PRELIMINARY
SN
FCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
`,�A•t 4F Tact I11
op .: ...... ... . . ....
121430
FIRM #-. 19170
STRUCTURAL ANALYSIS BY: OTHERS
DATED: CAA SOLUTIONS, PLLC
MOUNT ANALYSIS BY: TOWER ENGINEERING SOLUTIONS, LLC CONSULTING ENGINEER
DATED: JULY 7, 2021 3400 STRATFORD ROAD
ORDER ID: 558028 ATLANTA, GA 30326
REVISION: 0 (770) 548-8268
CALL TEXAS ONE CALL
(800) DIG-TESS
CALL 3 WORKING DAYS
BEFORE YOU DIGI Q5
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
T-1 FCD2
CROWN CASTLE USA INC. SITE ACTIVITY REQUIREMENTS:
GENERAL NOTES:
ELECTRICAL INSTALLATION NOTES:
1. NOTICE TO PROCEED- NO WORK SHALL COMMENCE PRIOR TO CROWN CASTLE USA INC. WRITTEN NOTICE
TO PROCEED (NTP) AND THE ISSUANCE OF A PURCHASE ORDER. PRIOR TO ACCESSING/ENTERING THE
SITE YOU MUST CONTACT THE CROWN CASTLE USA INC. NOD AT 800-788-7011 & THE CROWN CASTLE
USA INC. CONSTRUCTION MANAGER.
2. "LOOK UP" - CROWN CASTLE USA INC. SAFETY CLIMB REQUIREMENT:
THE INTEGRITY OF THE SAFETY CLIMB AND ALL COMPONENTS OF THE CLIMBING FACILITY SHALL BE
CONSIDERED DURING ALL STAGES OF DESIGN, INSTALLATION, AND INSPECTION. TOWER MODIFICATION, MOUNT
REINFORCEMENTS, AND/OR EQUIPMENT INSTALLATIONS SHALL NOT COMPROMISE THE INTEGRITY OR
FUNCTIONAL USE OF THE SAFETY CLIMB OR ANY COMPONENTS OF THE CLIMBING FACILITY ON THE
STRUCTURE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO: PINCHING OF THE WIRE ROPE, BENDING OF
THE WIRE ROPE FROM ITS SUPPORTS, DIRECT CONTACT OR CLOSE PROXIMITY TO THE WIRE ROPE WHICH
MAY CAUSE FRICTIONAL WEAR, IMPACT TO THE ANCHORAGE POINTS IN ANY WAY, OR TO IMPEDE/BLOCK ITS
INTENDED USE. ANY COMPROMISED SAFETY CLIMB, INCLUDING EXISTING CONDITIONS MUST BE TAGGED OUT
AND REPORTED TO YOUR CROWN CASTLE USA INC. POO OR CALL THE NOC TO GENERATE A SAFETY CLIMB
MAINTENANCE AND CONTRACTOR NOTICE TICKET.
3. PRIOR TO THE START OF CONSTRUCTION, ALL REQUIRED JURISDICTIONAL PERMITS SHALL BE OBTAINED.
THIS INCLUDES, BUT IS NOT LIMITED TO, BUILDING, ELECTRICAL, MECHANICAL, FIRE, FLOOD ZONE,
ENVIRONMENTAL, AND ZONING. AFTER ONSITE ACTIVITIES AND CONSTRUCTION ARE COMPLETED, ALL
REQUIRED PERMITS SHALL BE SATISFIED AND CLOSED OUT ACCORDING TO LOCAL JURISDICTIONAL
REQUIREMENTS.
4. ALL CONSTRUCTION MEANS AND METHODS; INCLUDING BUT NOT LIMITED TO, ERECTION PLANS, RIGGING
PLANS, CLIMBING PLANS, AND RESCUE PLANS SHALL BE THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR RESPONSIBLE FOR THE EXECUTION OF THE WORK CONTAINED HEREIN, AND SHALL MEET
ANSI/ASSE A10.48 (LATEST EDITION); FEDERAL, STATE, AND LOCAL REGULATIONS; AND ANY APPLICABLE
INDUSTRY CONSENSUS STANDARDS RELATED TO THE CONSTRUCTION ACTIVITIES BEING PERFORMED. ALL
RIGGING PLANS SHALL ADHERE TO ANSI ASSE A10.48 LATEST EDITION AND CROWN CASTLE USA INC.
STANDARD CED-STD-10253, INCLUDING THE REQUIRED INVOLVEMENT OF A QUALIFIED ENGINEER FOR
CLASS IV CONSTRUCTION, TO CERTIFY THE SUPPORTING STRUCTURE(S) IN ACCORDANCE WITH ANSI/TIA-322
(LATEST EDITION).
5. ALL SITE WORK TO COMPLY WITH OAS-STD-10068 "INSTALLATION STANDARDS FOR CONSTRUCTION
ACTIVITIES ON CROWN CASTLE USA INC. TOWER SITE," CED-STD-10294 "STANDARD FOR INSTALLATION OF
MOUNTS AND APPURTENANCES," AND LATEST VERSION OF ANSI/TIA-1019-A-2012 "STANDARD FOR
INSTALLATION, ALTERATION, AND MAINTENANCE OF ANTENNA SUPPORTING STRUCTURES AND ANTENNAS."
6. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR
SHALL PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY CROWN CASTLE USA INC. PRIOR TO
PROCEEDING WITH ANY SUCH CHANGE OF INSTALLATION.
7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE
CODES, REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND
COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC
AUTHORITY REGARDING THE PERFORMANCE OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH
ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES,
ORDINANCES AND APPLICABLE REGULATIONS.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
9. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION.
10. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES WHERE ENCOUNTERED IN THE
WORK, SHALL BE PROTECTED AT ALL TIMES AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE
WORK, SHALL BE RELOCATED AS DIRECTED BY CONTRACTOR. EXTREME CAUTION SHOULD BE USED BY THE
CONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHALL
PROVIDE SAFETY TRAINING FOR THE WORKING CREW. THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL
PROTECTION B) CONFINED SPACE C) ELECTRICAL SAFETY D) TRENCHING AND EXCAVATION E)
CONSTRUCTION SAFETY PROCEDURES.
11. ALL SITE WORK SHALL BE AS INDICATED ON THE STAMPED CONSTRUCTION DRAWINGS AND PROJECT
SPECIFICATIONS, LATEST APPROVED REVISION.
12. CONTRACTOR SHALL KEEP THE SITE FREE FROM ACCUMULATING WASTE MATERIAL, DEBRIS, AND TRASH AT
THE COMPLETION OF THE WORK. IF NECESSARY, RUBBISH, STUMPS, DEBRIS, STICKS, STONES AND OTHER
REFUSE SHALL BE REMOVED FROM THE SITE AND DISPOSED OF LEGALLY.
13. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH THE
EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR OTHERWISE DISCONTINUED
AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, SUBJECT TO THE APPROVAL
OF CONTRACTOR, TOWER OWNER, CROWN CASTLE USA INC., AND/OR LOCAL UTILITIES.
14. THE CONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION FOR
SITE SIGNAGE REQUIRED BY LOCAL JURISDICTION AND SIGNAGE REQUIRED ON INDIVIDUAL PIECES OF
EQUIPMENT, ROOMS, AND SHELTERS.
15. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE CARRIER'S EQUIPMENT
AND TOWER AREAS.
16. THE SUB GRADE SHALL BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO FINISHED
SURFACE APPLICATION.
17. THE AREAS OF THE OWNERS PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER,
EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT
EROSION AS SPECIFIED ON THE CONSTRUCTION DRAWINGS AND/OR PROJECT SPECIFICATIONS.
18. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION CONTROL
MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE LOCAL GUIDELINES
FOR EROSION AND SEDIMENT CONTROL.
19. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND
STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION
OF OWNER.
20. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL
CABLES AND OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE
RETURNED TO THE OWNER'S DESIGNATED LOCATION.
21. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED
FROM SITE ON A DAILY BASIS.
22. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS, SNOW
OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
GREENFIELD GROUNDING NOTES:
1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
CONTRACTOR: GENERAL CONTRACTOR RESPONSIBLE FOR CONSTRUCTION
CARRIER: VERIZON
TOWER OWNER: CROWN CASTLE USA INC.
2. THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY
EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE ENGINEERS IN THIS OR SIMILAR LOCALITIES. IT IS
ASSUMED THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKPEOPLE
WHO HAVE A WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY
ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN
ON THESE DRAWINGS, THE CONTRACTOR SHALL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR
MISCELLANEOUS WORK NOT EXPLICITLY SHOWN.
3. THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF
CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES, AND PROCEDURES. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY FOR
PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE BUT NOT BE LIMITED
TO, BRACING, FORMWORK, SHORING, ETC. SITE VISITS BY THE ENGINEER OR HIS REPRESENTATIVE WILL NOT INCLUDE
INSPECTION OF THESE ITEMS AND IS FOR STRUCTURAL OBSERVATION OF THE FINISHED STRUCTURE ONLY.
4. NOTES AND DETAILS IN THE CONSTRUCTION DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL
DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT,
AND/OR AS PROVIDED FOR IN THE CONTRACT DOCUMENTS. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS,
GENERAL NOTES, AND SPECIFICATIONS, THE GREATER, MORE STRICT REQUIREMENTS, SHALL GOVERN. IF FURTHER
CLARIFICATION IS REQUIRED CONTACT THE ENGINEER OF RECORD.
5. SUBSTANTIAL EFFORT HAS BEEN MADE TO PROVIDE ACCURATE DIMENSIONS AND MEASUREMENTS ON THE DRAWINGS TO
ASSIST IN THE FABRICATION AND/OR PLACEMENT OF CONSTRUCTION ELEMENTS BUT IT IS THE SOLE RESPONSIBILITY
OF THE CONTRACTOR TO FIELD VERIFY THE DIMENSIONS, MEASUREMENTS, AND/OR CLEARANCES SHOWN IN THE
CONSTRUCTION DRAWINGS PRIOR TO FABRICATION OR CUTTING OF ANY NEW OR EXISTING CONSTRUCTION ELEMENTS.
IF IT IS DETERMINED THAT THERE ARE DISCREPANCIES AND/OR CONFLICTS WITH THE CONSTRUCTION DRAWINGS THE
ENGINEER OF RECORD IS TO BE NOTIFIED AS SOON AS POSSIBLE.
6. PRIOR TO THE SUBMISSION OF BIDS, THE BIDDING CONTRACTOR SHALL VISIT THE CELL SITE TO FAMILIARIZE WITH THE
EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS SHOWN ON THE CONSTRUCTION
DRAWINGS. ANY DISCREPANCY FOUND SHALL BE BROUGHT TO THE ATTENTION OF CROWN CASTLE.
7. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES,
REGULATIONS AND ORDINANCES. CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND COMPLY WITH ALL LAWS,
ORDINANCES, RULES, REGULATIONS AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY REGARDING THE PERFORMANCE
OF THE WORK. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY
SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.
8. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES AND
LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
9. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
10. IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL
PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CARRIER AND CROWN CASTLE PRIOR TO PROCEEDING
WITH ANY SUCH CHANGE OF INSTALLATION.
11. CONTRACTOR IS TO PERFORM A SITE INVESTIGATION AND IS TO DETERMINE THE BEST ROUTING OF ALL CONDUITS FOR
POWER, AND TELCO AND FOR GROUNDING CABLES AS SHOWN IN THE POWER, TELCO, AND GROUNDING PLAN
DRAWINGS.
12. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND STRUCTURES. ANY
DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF CROWN CASTLE USA INC.
13. CONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL CABLES AND
OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE RETURNED TO THE OWNER'S
DESIGNATED LOCATION.
14. CONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION. TRASH AND DEBRIS SHOULD BE REMOVED FROM SITE ON
A DAILY BASIS.
CONCRETE, FOUNDATIONS, AND REINFORCING STEEL:
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301, ACI 318, ACI 336, ASTM A184, ASTM A185 AND
THE DESIGN AND CONSTRUCTION SPECIFICATION FOR CAST -IN -PLACE CONCRETE.
2. UNLESS NOTED OTHERWISE, SOIL BEARING PRESSURE USED FOR DESIGN OF SLABS AND FOUNDATIONS IS ASSUMED
TO BE 1000 psf.
3. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) OF 3000 psi AT 28 DAYS, UNLESS NOTED
OTHERWISE. NO MORE THAN 90 MINUTES SHALL ELAPSE FROM BATCH TIME TO TIME OF PLACEMENT UNLESS
APPROVED BY THE ENGINEER OF RECORD. TEMPERATURE OF CONCRETE SHALL NOT EXCEED 90'f AT TIME OF
PLACEMENT.
4. CONCRETE EXPOSED TO FREEZE -THAW CYCLES SHALL CONTAIN AIR ENTRAINING ADMIXTURES. AMOUNT OF AIR
ENTRAINMENT TO BE BASED ON SIZE OF AGGREGATE AND F3 CLASS EXPOSURE (VERY SEVERE). CEMENT USED TO BE
TYPE II PORTLAND CEMENT WITH A MAXIMUM WATER -TO -CEMENT RATIO (W/C) OF 0.45.
5. ALL STEEL REINFORCING SHALL CONFORM TO ASTM A615. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM
A185. ALL SPLICES SHALL BE CLASS "B" TENSION SPLICES, UNLESS NOTED OTHERWISE. ALL HOOKS SHALL BE
STANDARD 90 DEGREE HOOKS, UNLESS NOTED OTHERWISE. YIELD STRENGTH (Fy) OF STANDARD DEFORMED BARS ARE
AS FOLLOWS:
#4 BARS AND SMALLER.................................................................................... 40 ksi
#5 BARS AND LARGER...................................................................................... 60 ksi
6. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS SHOWN OTHERWISE
ON DRAWINGS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ....................... 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 BARS AND LARGER.....................................................................................2"
#5 BARS AND SMALLER.......................................................................... 1-1/2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABAND WALLS.........................................................................................3/4"
BEAMS AND COLUMNS............................................................................. 1 -1/2..
7. A TOOLED EDGE OR A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE, UNLESS NOTED
OTHERWISE, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4.
1. ALL GROUND ELECTRODE SYSTEMS (INCLUDING TELECOMMUNICATION, RADIO, LIGHTNING PROTECTION AND AC POWER GES'S) SHALL BE BONDED TOGETHER AT OR BELOW GRADE, BY TWO OR MORE COPPER BONDING CONDUCTORS IN
ACCORDANCE WITH THE NEC.
2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING (PER IEEE 1100 AND 81) FOR GROUND ELECTRODE SYSTEMS, THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND
ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND PROVIDE
TESTING RESULTS.
4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH #6 COPPER WIRE ILL APPROVED GROUNDING TYPE CONDUIT
CLAMPS.
5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALL BE FURNISHED AND INSTALLED
WITH THE POWER CIRCUITS TO BTS EQUIPMENT.
6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES, #6 STRANDED COPPER OR LARGER FOR INDOOR BTS; #2 BARE SOLID TINNED
COPPER FOR OUTDOOR BTS.
7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE GROUND BUS ARE PERMITTED.
8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE #2 SOLID TINNED COPPER UNLESS OTHERWISE INDICATED.
9. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
10. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45' BENDS CAN BE ADEQUATELY SUPPORTED.
11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE.
12. ALL GROUND CONNECTIONS ABOVE GRADE (INTERIOR AND EXTERIOR) SHALL BE FORMED USING HIGH PRESS CRIMPS.
13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS.
14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR.
15. APPROVED ANTIOXIDANT COATINGS (i., CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS.
16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL.
17. MISCELLANEOUS ELECTRICAL AND NON -ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC.
18. BOND ALL METALLIC OBJECTS WITHIN 6 ft OF MAIN GROUND RING WITH (1) #2 BARE SOLID TINNED COPPER GROUND CONDUCTOR.
19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS,
METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, NON-METALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE
USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (i-, NONMETALLIC CONDUIT PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT.
20. ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE #2 BARE SOLID TINNED COPPER IN 3/4" NON-METALLIC, FLEXIBLE CONDUIT FROM 24" BELOW GRADE TO WITHIN 3" TO 6" OF CAD -WELD TERMINATION
POINT. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH SILICONE CAULK. (ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL).
21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE, THE CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP, TOWERS, AND WATER TOWERS GROUNDING RING, T_
THE EXISTING GROUNDING SYSTEM, THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER. ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING GROUNDING SYSTEM, THE BUILDING STEEL COLUMNS,
LIGHTNING PROTECTION SYSTEM, AND BUILDING MAIN WATER LINE (FERROUS OR NONFERROUS METAL PIPING ONLY).
1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, NEC AND ALL APPLICABLE
FEDERAL STATE AND LOCAL CODES ORDINANCES.
2. CONDUIT ROUTINGS ARE SCHEMATIC. CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED
AND TRIP HAZARDS ARE ELIMINATED.
3. WIRING, RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF THE NEC.
4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC.
4.1. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL, AND SHALL CONFORM TO
REQUIREMENT OF THE NATIONAL ELECTRICAL CODE.
4.2. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT
CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, 22,000 AIC MINIMUM. VERYIFY AVAILABLE SHORT CIRCUIT CURRENT DOES
NOT EXCEED THE RATING OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT
ADOPTED CODE PRE THE GOVERNING JURISDICTION.
5. EACH END OF EVERY POWER PHASE CONDUCTOR, GROUNDING CONDUCTOR, AND TELCO CONDUCTOR OR CABLE SHALL BE
LABELED WITH COLOR -CODED INSULATION OR ELECTRICAL TAPE (3M BRAND, 1/2" PLASTIC ELECTRICAL TAPE WITH UV
PROTECTION, OR EQUAL). THE IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA.
6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE, PHASE
CONFIGURATION, WIRE CONFIGURATION, POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS (i., PANEL BOARD AND
CIRCUIT ID'S).
7. PANEL BOARDS (ID NUMBERS) SHALL BE CLEARLY LABELED WITH PLASTIC LABELS.
8. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES.
9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR (#14 OR LARGER)
WITH TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR (#6 OR LARGER) WITH
TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
11. POWER AND CONTROL WIRING IN FLEXIBLE CORD SHALL BE MULTI -CONDUCTOR, TYPE SCOW CORD (#14 OR LARGER) UNLESS
OTHERWISE SPECIFIED.
12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE MULTI -CONDUCTOR TYPE TO CABLE (# 14 OR LARGER), WITH
TYPE THHW, THWN, THWN-2, XHHW, XHHW-2, THW, THW-2, RHW, OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED.
13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP -STYLE, COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND
BETTS (OR EQUAL). LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION NOT LESS THAN 75' C (90' C IF AVAILABLE).
14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, ILL, ANSI/IEEE
AND NEC.
15. ELECTRICAL METALLIC TUBING (EMT), INTERMEDIATE METAL CONDUIT (IMC), OR RIGID METAL CONDUIT (RMC) SHALL BE USED FOR
EXPOSED INDOOR LOCATIONS.
16. ELECTRICAL METALLIC TUBING (EMT) OR METAL -CLAD CABLE (MC) SHALL BE USED FOR CONCEALED INDOOR LOCATIONS.
17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE
GRADE PVC CONDUIT.
18. LIQUID -TIGHT FLEXIBLE METALLIC CONDUIT (LIQUID-TITE FLEX) SHALL BE USED INDOORS AND OUTDOORS, WHERE VIBRATION
OCCURS OR FLEXIBILITY IS NEEDED.
19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION -TYPE AND APPROVED FOR THE LOCATION USED. SET
SCREW FITTINGS ARE NOT ACCEPTABLE.
20. CABINETS, BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA, ILL, ANSI/IEEE AND
THE NEC.
21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER, DESIGNED TO SWING OPEN DOWNWARDS
(WIREMOLD SPECMATE WIREWAY).
22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER (PANDUIT TYPE E OR EQUAL).
23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON -PERFORATED STRAPS AND HANGERS. EXPLOSIVE
DEVICES (i., POWDER -ACTUATED) FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED. CLOSELY FOLLOW THE
LINES OF THE STRUCTURE, MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES. CHANGES
IN DIRECTION TO ROUTE AROUND OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES. CONDUIT SHALL BE INSTALLED IN
A NEAT AND WORKMANLIKE MANNER. PARALLEL AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES. ALL CONDUIT
SHALL BE FISHED TO CLEAR OBSTRUCTIONS. ENDS OF CONDUITS SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO
PREVENT CONCRETE, PLASTER OR DIRT FROM ENTERING. CONDUITS SHALL BE RIGIDLY CLAMPED TO BOXES BY GALVANIZED
MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE AND INSIDE.
24. EQUIPMENT CABINETS, TERMINAL BOXES, JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY -COATED SHEET
STEEL. SHALL MEET OR EXCEED ILL 50 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND NEMA 3R (OR
BETTER) FOR EXTERIOR LOCATIONS.
25. METAL RECEPTACLE, SWITCH AND DEVICE BOXES SHALL BE GALVANIZED, EPDXY -COATED OR NON -CORRODING; SHALL MEET OR
EXCEED UL 514A AND NEMA OS 1 AND BE RATED NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED
(WP OR BETTER) FOR EXTERIOR LOCATIONS.
26. NONMETALLIC RECEPTACLE, SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2 (NEWEST REVISION) AND BE RATED
NEMA 1 (OR BETTER) FOR INTERIOR LOCATIONS AND WEATHER PROTECTED (WP OR BETTER) FOR EXTERIOR LOCATIONS.
27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR CROWN CASTLE USA INC.
BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS.
28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS, CABLES AND DISTRIBUTION PANELS IN ACCORDANCE
WITH THE APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY.
29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW "VERIZON".
30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED.
CONDUCTOR COLOR CODE
SYSTEM
CONDUCTOR
COLOR
120/24OV, 10
A PHASE
BLACK
B PHASE
RED
NEUTRAL
WHITE
GROUND
GREEN
120/208V, 30
A PHASE
BLACK
B PHASE
RED
C PHASE
BLUE
NEUTRAL
WHITE
GROUND
GREEN
277/48OV, 30
A PHASE
BROWN
B PHASE
ORANGE OR PURPLE
C PHASE
YELLOW
NEUTRAL
GREY
GROUND
GREEN
DC VOLTAGE
POS (+)
RED**
NEG (-)
BLACK**
* SEE NEC 210.5(C)(1) AND (2)
** POLARITY MARKED AT TERMINATION
ABBREVIATIONS:
ANT ANTENNA
IE EXISTING
TT FACILITY INTERFACE FRAME
GEN GENERATOR
GPS GLOBAL POSITIONING SYSTEM
GSM GLOBAL SYSTEM FOR MOBILE
LTE LONG TERM EVOLUTION
MGB MASTER GROUND BAR
MW MICROWAVE
(N) NEW
NEC NATIONAL ELECTRIC CODE
(P) PROPOSED
PP POWER PLANT
QTY QUANTITY
RECT RECTIFIER
RBS RADIO BASE STATION
PET REMOTE ELECTRIC TILT
RFDS RADIO FREQUENCY DATA SHEET
RRH REMOTE RADIO HEAD
RED REMOTE RADIO UNIT
SIAD SMART INTEGRATED DEVICE
TMA TOWER MOUNTED AMPLIFIER
TYR TYPICAL
"MIS UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM
W.P. WORK POINT
APWA UNIFORM COLOR CODE:
WHITE PROPOSED EXCAVATION
- TEMPORARY SURVEY MARKINGS
-ELECTRIC POWER LINES, CABLES,
CONDUIT, AND LIGHTING CABLES
GAS, OIL, STEAM, PETROLEUM, OR
GASEOUS MATERIALS
-COMMUNICATION, ALARM OR SIGNAL LINES,
CABLES, OR CONDUIT AND TRAFFIC LOOPS
- POTABLE WATER
RECLAIMED WATER IRRIGATION AND
SLURRY LINES
® SEWERS AND DRAIN LINES
Planning Administrative
Approval
COYYEI.I,
12/03/2021
E
verizon/
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCASCROWN
TLE
v
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS
services
/51
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CD0
05/17/2021
ND
PRELIMINARY
SN
PCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
�AKs0Fr ,
C2
.. ............ . ..... .�
12 14 3 0fj
1t /01V CE 4�
i�
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 54B-8268
IT IS A VIOLATION OF I.AW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
T-2 FCD
J
FIELD VERIFY EXISTING GROUND
EQUIPMENT CONFIGURATION.
EXISTING EQUIPMENT INFORMATION
NOT PROVIDED.
GROUND EQUIPMENT TO REMAIN:
(2) RXXDC-3315—PF-48 OVP-6.
GROUND EQUIPMENT TO BE REMOVED:
NONE
(E) 12'-6" SITE (E) 12'-0" SITE (E) 12'-0" SITE
ACCESS GATE ACCESS GATE ACCESS GATE
BRIDGE (TYR)
(TYP)
SITE PLAN
SCALE: 3/e6'(FULL srze) N
2' 1' 0 2' 3/16"=1-0" (11.17)
(E) FENCE
(E) UTILITY FRAME
(E) 10'-0"x16'—O"
PAD IN
11'-0"x19'-0" AREA
(OTHER CARRIER)
(E) UTILITY FRAME
(E) GPS ANTENNA
(TYR)
(E) 10'-11"x16' O"
PLATFORM IN
10'-0"x16'—O" AREA
(OTHER CARRIER)
Planning Administrative
Approval
COFPELL
12/03/2021
' J
verizon
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS� services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 401 4234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
FCDO
08/10/2021
ND
FINAL
SN
FCD1
08/12/2021
ND
FINAL.
SN
FCD2
09/13/2021
ND
FINAL.
SN
�
xAKs�F......
01
f; "
1 21 4 3 0
(�ii4,c�SZ!C� NS��•��2��r
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL. ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
REVISION:
C_1
CD
L
I
TIPLEV OF IPM-6"ENT
� E= EQU78'
TOP OF MONOPOLE
ELEV = 71 —6"
VERIZON ANTENNA BAD CENTER
ELEV = 0
VERIZON EQUIPMENT
ANTENNA CL: 55'-0"
MOUNT CL 55'-0"'
NEW VERIZON EQUIPMENT:
(3) COMMSCOPE — 3SAMNT—SBS-1-2
(3) SAMSUNG — VZSO1 INTEGRATED RRH &
ANTENNAS
(3) SAMSUNG — B2/B66A RRH—BR049
(RFV01U—D1A)
(3) SAMSUNG — B5/B13 RRH—BR04C
(RFV01U—D2A)
INSTALLED ON EXISTING MOUNTS
(1) VZWSMART—PLK7 MONOPOLE COLLAR MOUNT
ASSEMBLY
(3) VZWSMART—PLK6 V—BRACING KIT FOR
MONOPOLE
(3) OST2875-10 2 1/2" PST (2.875" O.D. X
0.203" THK) X 10'-0" A53 GR—B 35KSI
(3) PV—XP-2530—HD PERFECT VISION
CROSSOVER CHANNEL BRACKET
(3) PV—XA—U PERFECT VISION CROSSOVER
ANGLE
(2) PIN 115-203 SAFETY CABLE GUIDE
(TUF—TUG OR EQUIV.)
TOWER ELEVATION
( JSCALE: NOT TO SCALE
THE MOUNT ANALYSIS INDICATES THE (E
MOUNTS ARE SUFFICIENT CONTINGENT
UPON COMPLETION OF MODIFICATIONS
DETAILED IN MOUNT MODIFICATION
DESIGN DRAWINGS PREPARED BY TOWER
ENGINEERING SOLUTIONS, LLC, PROJECT
#16226318 (SMART TOOL PROJECT
10078301), DATED JU LY 7, 2021
(E) VERIZON EQUIPMENT TO BE REMOVED:
(3) NO KIA — UHBA B13 RRH 4x30
(3) NOKIA — UHIE B66A RRH 4x45
(E) VERIZON EQUIPMENT TO REMAIN:
(61 ANDREW — SBNHH-1D65C ANTE
(2) RAYCAP — RXXDC-3315—PF-48
OVP-6
INSTALLED ON EXISTING MOUNTS
(E) 71-6" MONOPOLE
(E) VERIZON FEEDLINES
(2) RFS — HYBRIFLEX (6X12)
NOTE:
ANTENNA ORIENTATION AND VERIZON
EQUIPMENT SHOWN HAVE NOT BEEN FIELD
VERIFIED. CONTRACTOR SHALL VERIFY THE
SITE PLAN AND EQUIPMENT LAYOUT SHOWN
AGAINST PRESENT FIELD CONDITIONS. IF
PLANS DO NOT MATCH UP WITH SITE
CONDITIONS AT TIME OF CONSTRUCTION,
CONTACT VERIZON CM IMMEDIATELY.
TOWER & ANTENNA STANDARD NOTES:
A. TOWER STRUCTURAL ANALYSIS BY OTHERS, DATED
##. PROJECT # ##/ NO NEW ANTENNAS OR
EQUIPMENT INSTALLED WITHOUT APPROVAL OF
STRUCTURAL ENGINEER AND VER170N.
B. INSTALLED EQUIPMENT MUST HAVE A MATCHING
CROWN CASTLE USA INC. APPLICATION AND
STRUCTURAL ANALYSIS.
C. VERIFY AZIMUTHS WITH RFDS
D. 2" ANTENNA SEPARATION REQUIRED. CONTRACTOR
TO MOVE (E) ANTENNAS TO ENDS OF MOUNT AS
REQUIRED.
E. MOUNT COMPLIANCE IS BY TOWER ENGINEERING
SOLUTIONS, LLC, ANALYSIS DATED JULY 07, 2021. NO
NEW ANTENNAS OR EQUIPMENT INSTALLED ON
MOUNTS WITHOUT THE APPROVAL OF A STRUCTURAL
ENGINEER.
F. PRIOR TO ATTACHING ANTENNAS AND MOUNTING
SECTIONS, (E) TOWER AND TOWER FOUNDATION MUST
BE ANALYZED BY A LICENSED STRUCTURAL ENGINEER
TO VERIFY TOWER IS CAPABLE OF SUPPORTING THE
PROPOSED LOADS. REFER TO STRUCTURAL ANALYSIS
BY OTHERS.
G. PROPOSED ANTENNA PLACEMENT LOCATION TO BE
FIELD VERIFIED BY GENERAL CONTRACTOR PRIOR TO
CONSTRUCTION TO AVOID ANY INTERFERENCE OR
SHADOWING OF EXISTING ANTENNAS. IF INTERFERENCE
OR SHADOWING OF EXISTING ANTENNAS IS
DISCOVERED DURING FIELD VERIFICATION, PLEASE
CONTACT (A&E VENDOR) FOR DESIGN REVISION PRIOR
TO ANY NEW ANTENNA INSTALLATION.
H. DO NOT OBSTRUCT BEACON IF TOWER LIT.
THE MOUNT ANALYSIS INDICATES THE (E)
MOUNTS ARE SUFFICIENT CONTINGENT
UPON COMPLETION OF MODIFICATIONS
DETAILED IN MOUNT MODIFICATION
DESIGN DRAWINGS PREPARED BY TOWER
ENGINEERING SOLUTIONS, LLC, PROJECT
#16226318 (SMART TOOL PROJECT
10078301), DATED JULY 7, 2021
Planning Administrative
Approval
COFPELL
12/03/2021
IL) V-1—IN --N U — R�
ONTO NEW
ANDREW — SBNHH
(6 TOTAL, 2 PER
(E) VERIZON RRU TO BE REMOVED:
NOKIA — UHIE B66A RRH 4x45
(3 TOTAL, 1 PER SECTOR)
(E) VERIZON SECTOR
MOUNT TO REMAIN
(3 TOTAL, 1 PER SECTOR)
(E) VERIZON RED TO BE REMOVED:
NOKIA — UHBA B13 RRH 4x30
(3 TOTAL, 1 PER SECTOR)
(E) VERIZON ANTENNA
ANDREW — SBNHH-1D65C
(6 TOTAL, 2 PER SECTOR)
NEW VERIZON SIDE BY SIDE MOUNT
COMMSCOPE — BSAMNT—SBS-1-2
(3 TOTAL, 1 PER SECTOR)
NEW VERIZON RRH
SAMSUNG — 32/1366A RRH-13R049
(3 TOTAL, 1 PER SECTOR)
NEW VERIZON RRH
SAMSUNG — 35/1313 RRH—BR04C
(3 TOTAL, 1 PER SECTOR)
(E) VERIZON SECTOR
MOUNT TO REMAIN
(3 TOTAL, 1 PER SECTOR)
NEW VERIZON VZWSMART—PLK7
MONOPOLE COLLAR MOUNT
ASSEMBLY (1 TOTAL)
ALPHA)
(E) VERIZON OVP-6 TO REMAIN:
RAYCAP — RXXDC-3315—PF-48
(2 TOTAL)
(E) 71'-6" MONOPOLE
TOWER
JTH
EXISTING ANTENNA LAYOUT
SCALE: NOT TO SCALE N
NEW VERIZON INTEGRATED RRH & ANTENNA:
SAMSUNG — VZS01
(3 TOTAL, 1 PER SECTOR)
(E) VERIZON OVP-6 TO REMAIN:
RAYCAP — RXXDC-3315—PF-48
(2 TOTAL)
NEW VERIZON OST2875-10 2 1/2" PST
(2.875" O.D.xO.203" THK)x10'—O" A53
GR—B 35KSI (3 TOTAL, 1 PER SECTOR)
(E) 71'-6" MONOPOLE
TOWER
NEW VERIZON VZWSMART—PLK6 V—BRACING
KIT FOR MONOPOLE
(3 TOTAL, 1 PER SECTOR)
I
UTH
NEW VERIZON PV—XP-2530—HD PERFECT
VISION CROSSOVER CHANNEL BRACKET
(3 TOTAL, 1 PER SECTOR)
NEW VERIZON PV—XA—U PERFECT
VISION CROSSOVER ANGLE
(3 TOTAL, 1 PER SECTOR)
NEW ANTENNA LAYOUT
SCALE: NOT TO SCALE N
m
verizom/
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS�
services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
PCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
�
xAK��F•rE�gdIow
. .. ...... ... . . ....
1 21 4 3 0
(ji
IIIS�!C� NS��•C5
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-2 FCD
J
WERT>SouthCIltNWCOF9taC0ntNWTa11FesNar6Ll7cr 111PARCAER
M-0. Wacp5-waLtas.ahmed@v iro Mfeles5.com-3R7202111:27.39
Projort Details location Information
Carrier Aggregation: false
MPT Id:
.GIP-0: ra15e
Project Name: 50 L-5v46 - CarrieF Add
FUZEProject IIT. 1522631.8
Designed Sector Carrier 46: 15
Designed Sector Caviler SG: 3
Additional Sector Carder 4G: N/A
Additional Sector Carrier SG: N/A
SiteTraker Project Id!
FP Solution Type & Tech Type: MODIFiCATION;4G PCs, 5G_L-Su68-
Prep,SG_PCS,5G_Radio Swap
SNHIxr
Site ID: 2623133
E-Noda810: 0132290,1329290,132290
PSL0:295251
SMIL0 News: Euless
Tower Owner:
TawerType: Other
Site Type: MACRO
Street Addressr 1305 Wrangler Circle
Clty: CDppell
Stater Tx
Zip Code: 75019
County: Dallas
Latitude: 32.934811111 32° 56' 5.32" N
LongRude:-97.00162222197' 0' 5.84• W
REDS Project 80epea 5GNW and 5G L-Sup6 Larner Add. RRli Upgrada5-
Ybb 190C -S A- .1.
TCb 190C AWL AW53 Meka
A.ienna s,rnm.Tr;
Motlx [adedfre np HerFM All- OLT SaW I... Typ. &I
12S01IP(M vdN
d9DC11
NAePded Anlwm- w Sa.l ta010Po41 tore bue PHY9LAl a
.,aaw ne I
- SG L-[ LTs ArmRFvl ,auHwtr.2ar:
EI Lacrdon TOC rtIW A- 9wS
kb�mt Tw'n LTF LTE LTE LTE
ma Torn 64 L- LTE
Fn T.... vIr L...�w.. T[tn Nat Ates .t1rR-
RRIIN Tim LR LTF LTF
jlntenl I- La:adw. ]OC tFOD A- 9WS
Dwe� T4ra
awl5a tAMY.
INSTALLER NOTE:
CONTRACTOR SHALL CONFIRM EQUIPMENT
CONFIGURATION WITH FINAL VERIZON RE
DWS BEFORE PROCEEDING WITH ANTENNA
MODIFICATIONS.
C-4e ilpTldlkRl AA. NET W4 N.l Ty OWah
Caaedm Np.... AemnN 1- 4Rx -Tal CkMMF
d9DDn
WI)
1501400Y1
.0 .an TFMMi r.t... rove. PHt'Mru a
x4dld°NI
RIDIO55
FGr®] FrrCo IwueaS
Equipment Summary
Moles ModN Ca -4Ib [eGe Lln Ineffi'ITrp. -Ift
l]omlra:•pe ESAYNr3B9-1S PHYSICAL 3
Sww� � � epbeo PHYSICAL 3
aRIM3 RRIrew4C PHYFICAI 3
Sa' M mPV9Tu-R9A1
vzssl SaPllwla
sanr'� '"eBR'°`F°•Ida""°- MY.ICAL a
save .P
mnenlrne.adml
YNm anaa LMre ,y [NYc 3iee Ina[ m h,.nliry
Mlle U-11111-1. PHTSILAL 3
Metre IIHIkeLrAHR.14e4R RIYSM.0 3
Mabe ModA Labe LeryM [oNe.41[e Irrstol Typr w.ntny
R."I L-09P T�LAL z
RFYLW 609P PHYSILAl T
,dn XIa Ll�
,�-�VERIZON EQUIPMENT SCHEDULE
SCALE: NOT TO SCALE
s.m9r
a,k"dX
der Fx,d.Flp
AnHnn. uelm
k.1Fn
LIm oo.e.ntXO.R.2
Repdnery Paver
TYA2d.b
TYA 4PdeI
aRuuMa
MYIYOM
t;.rB�dTT,roIANr
F.O.
Tr.r.rdlf.I
akrFwa.Nro
Lr'm N,RR
n..am.Cem.dkalPn
LIe<1�d Lle..e.anunw.l
D.ndw ueYa.Txe
TkP x.19M1y
RW WIM'Parx�
T W McRe
w'�iuurx.a' a
rrmrntlOxrla
A Ih
f-.a/Exeee 0
ANwIn.Nrke
MMne Cenadlelro
Yee oerr.TRXCeR.}
F� eem.,Rt
Tip Herr
Rive Nadel
ILmuerNTx, Rem
T�
A:.,etln
S.F! FXe4 Flo
MMtuYW
Mlwne. rar'Ier1l'epe
M.cM1AnlcFl bawn.nLlfn m
El.ctrlul CbrmTrl
RepJSlerp Paw
IYAYeke
rYANRdY
IIIII Wb
4M1mdn 1`1Ax LYe,
adr Fx.c. FID
deletFta Yodel
AnmurO�Fnle.4w.IPn
krs nLtloeai
Fkeldplmw-RI
TIPXe1pM
FAP4YMYPeuw
TYAxeke
mnYedb
2Y.rtaef T.'�Rx u,w
Trn. Ild
AiIM
A CNr FI3eM NOIO
4.dn.e..m. cl-wo
FIRFNMW 9� B rH9eN)
Tp Hey,t
kLepuMlaPPaw
TLW Yek.
TLL4 ueeY
RRuu.k.
RAM YodN
lAmdera Ti RxtNx
mM ld Tree Sd�[e
Service Info
m
m
m
nx°x99
i31W3o
li�o
SeHMY1De5C
SaYNIFlfatSC
mnXriLT c
A.4oRLw
d5
AN.-
o
wDRrw
C5
3
9
9
59
1543
I5394
Lax.9a
rbm
x
x.Ya
NIBA N33 P[W Ix3C
IlX8A F13 31 Pp.i 4K3tr
aNLA a1Z. ia3C
sw
z.1
z.
+00P254
46C325F
+CCF35fl
A39LL A>'I
ATmi_4n1
A _
woRew
0
z
59
1FL69
ndkV
I.9IN F6FA RRH 4a4S
."255
ATOLLAPi
m
F
ilR90
5&AH1.7pdAC
MDRFW
a
2
A579
NRkh
IHIN 86rA RAN 4.45
4.1
400112151)
ATOLL_API
ddnF
53219D
SaMN41Od5C
AND"
a
2
mi.
NOkl3
CMF BFdA Apx Iy5
4CM57
ATOI.L_API
R�
in
132290
W IDW
AND"
Ss
17zz90
SDHFFX]DSSC
wDREw
ss
3
59
ICC.63
N9xR
aI3� lIFM 8AH 4Ra5
4A
IOC M
ATOLL MI
DH
]Ad
132x4d
SeNHIF1D1I5C
ANDPEW
a
59
3M1fi2
N
HIrE 368A RAW 4.45
4.4
`C053di1
6696 TRI COUNTY PARKWAY, SUITE 100
b
U.
240
SCHERTZ, TX 78154
133x90
13x]98
L3x,So
SBNIX141O65C
SSIIHi-1rM5[
58NIH-Lslfix
AN.-
wOREW
AN-.
05
SCS
55
a
3
s9
54
CROWN
ie7n
3FTn
wim
c
5a�m9
5�naro
CASTLE
G9A13 RPJ4kR61[IRPM141-02A1
B5�313 APH41RC4[ljtF4C1U-02A}
FSRI3 PRH43RC4C frdTNla-0bll
+.4
T+ssaeF
1I55+8k
7-
1220 AUGUSTA DRIVE, SUITE 500
ATOLL _API
ATOµ_AM
ATOLLAN
HOUSTON, TX 77057
a
1zD
x46
sevRlLLzoeac
sFMlwaodu
sexwut,5x
B R O A D U S
°"°"F"
•";�w
services
a
e
3
a
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
samwn9
saln:tlm
seplFt.9
OFFICE: (817) 349 3449
821B6&k P1W-00.C191PFVDla-0lA1
al/kedA RRHA0.C4910.FVC1LLDIA1
R2R3drw RRiiCRP191RFVb1U-0LA}
A4
..,
a.4
FAX: 800 4014234
]9166C0
n7M*
]910898
AT _
ATOLL
CCCI
CCOe
8088
0
120
740
]31929C
SFMMF3DFSC
stxiHx tits
- x
mwx�
.]pfi
Maim
wMNW
ANDMW
VERIZON SITE NUMBER:
55
55
0
3
295251
t4eu
e4a.Fz
14s9.
SFm n9
Semwnp
Same g
BU #: 876558
BilaFbl RRNa0.019IRFYDIH-0u3
92RRFA FWI-0R049 RLFNDLII-0IA]
RLTidMRAXdRO991RF401Mt11A7
4.4
14
F3 - COPPELL MIDDLE S
9a333dR
.3-1
993070
ATOLL API
ATOLL An
ATOLL An
1305 WRANGLER CIRCLE
0
126
216
COPPELL, TX 75019
132296
113399
i3229a
sexlRuodsc
sexwx.lDFx
saNrw-]neu
N195
AH 55
A"DREW
55
EXISTING 71'-6" MONOPOLE
2
2
8
3
59
59
59
11607
1SF.C1
I1531
Sam9u19
$amsun0
Sanyttn9
axaFU RNx;R049 L.r491uniAl
3RlFdu RHry-Fpoe9luvollr-out
e,�sceA RRHa3os4 fRrvmuLu}
41
4.1
ISSUED FOR:
TNS-7
7455+0
745WI
ATOLL_AFI
ATOLL_A.,
wroLLAPt
REV
DATE
ERVIN
DESCRIPTION
DES./Q
0'
m
PCDO
05/17/2021
ND
PRELIMINARY
SN
13Rm
zd
13
a3s;9F
PCDO
08/10/2027
ND
FINAL
SN
5Nxwl.1Rm Dpsr
sB11M1-ioRsc
seww.inPSc
wDRlw
wDRFw
ANDRsw
FCDl
08/12/2021
ND
FINAL
SN
ss
0
s5
C
ss
b
CD2
09/13/2021
ND
FINAL.
SN
]3LR
732i1
Ini,LR
Semzwq
Semwnq
-.N
82Rd60. APN4fAR491RrUC1LLb14) BLBddA PRi.NN19IRMCl146LV
kLD6dA PRti8R059;RNO]VLkAt
4.1
745545Z
745503
10m"
rE �y
-ATOLL "I
ATOLL--
AmLLAw
••
�p�( Y:•
•
009i
013]294
9pgp
d133911
am
C132�290
ow y/�),�' • •�� 111
nLdWdAr4euru
nL-iWd Mttruu
nL-5'lbF wxema
r ^"}-iZ��1� •�
T"D
TBD
TRD
/ T .... .
Z
0
Z
0
55
0
�
3
3
57
MAN,
Mal4•;
1 21 4 3 0 i
Samevng
Semwny
Suns��g
■+ /4�� n ` ((,�
t,y�laJ�o
YLSCI
VZ501
V2581
•� VjC•e ,1c •��`I
AA
4.1
4.4
�(\•�••....... VC5
TI55535
k
.
]I55539
1y
` 0
AlIX1JIR1
ATIlLl�idrl
TOU;
0.715
�VVS;/�`:=���7y
`
FIRM #-. 19170
Planning Administrative
Approval
COFFELL
' `I "'PIWI
12/03/2021
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF I.AW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
C-3 FCD
W IJ PL=j2j
5Zjb4f8 f&3 RVUW�y 3
d71� R a�idp
INSTALLER NOTE:
CONTRACTOR SHALL CONFIRM EQUIPMENT
CONFIGURATION WITH FINAL VERIZON RE
DWS BEFORE PROCEEDING WITH ANTENNA
MODIFICATIONS.
/��VERIZON PLUMBING DIAGRAM
SCALE: NOT TO SCALE
s�,:ur+ #e�Crti
S#eeller
mm ruu
Oidm rm a
r L FUN 1 Fpl►1fyii IrJ7a
orb
0-0S HM
.D�IAC,
i+lE�des�nEtee� p.ar_
IW F-A
I foaxhil-prr
L
liawjump;r
jftd15Gs momgium
Jki5ra lurAper
Note&:
-H" iRitimm5 afarY0um dwrch W&-%-5ideu C m
- &`Rmft weim i3 b am She hack 0 the We ma%
II d foAri0i114e arm 0A1 #r difrrlC 0Dn
-Sim of tlhfQt#s in drawing docetill reflect egr*prnent ime
duA&%.SNn
- EKb!Wur C5 009101
- Fbeii & pvxd are the Sin& paps farm am 1ybTlf1IeR (mn
rie�r��ozitatire ialIII rI.0 IIS,, iwaolf.,
- tY fhidRca and DVN are nat sk*wn
Planning Administrative
Approval
COFFELL
12/03/2021
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS�
services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
FCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
�
xAK��F•rE�gd'�il
i
... ...............
1 21 4 3 0
(jii4,c�S��C� NSE�•��e1��r
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: rSION:
C-4 D
SAMSUNG
Dual -Band Radio Unit
AWS/PCS (B66/B2)
RFVOIU-DI.A
Sam un g's RF V01U-D1A is a compact remote Radio Unit (RU) designed for deployments
that require Flexibility in installation and rapid onlining, without compromising on coverage,
capacity or operational expenses.
y:15no"EX
Dual -Band Radio Unit
700/850MHz (B 13B5)
RFVOlU-D2A
Samsung's RF VOI U-D2A is a compact remote Radio Unit (II designed for deployments
that require flexibility in installation mid rapid onlining, without compromising on coverage, 41
capacity or operational expenses.
Technical Specifications
The RFVOIU-D1A RU targets dud -band support across Baud
-
66 (AWS) and Rand 2 (PCS), making it an ideal product for
\
The RFV01 U-132A RU targets dual -band support across Band
broad coverage footprints across multiple common mid -range
13 (70OMHz) and Band 5 (850MHz), making it an ideal
frequcncies.
product for broad coverage footprint, across multiple
-
`°manou low -end, long-range frequencies.
Tech
LTE/SG NR
The RU haudles¢Il Radio Frequency
qncy (RE) processing in
ready (Support eCPRI)
single, compact unit, and is designed m interface via CPRI
The RU handles all Radio Frcqucncy (RF) processing in a
with Samsung's CDU baseband offerings, in both distributed-
single, compact unit, and is designed to interface via CPRI
and central -RAN configurations.
with Samsung's CDU baseband offerings, in both distributed-
Band
Band48 (3.5 G Hz)
and central -RAN configurations.
In addition to its minimal footprint and case of . allafion,
the RU is also designed to reduce cost of ownership through
In addition to its minimal footprint and ease of installation,
Frequency Band
3550-3700MHz
as integrated spectrrm analyzer, which allows for remote RF
the RU is also designed to reduce cost o£ownership through
'� 0\
omorring, greatly reducing the need for on -site maintenance
, s integrated spectrum analyzer, which allows for remote RF
visits,
monitoring, greatly reducing the need fox on -site maintenance
RF Power
Total 20 W =43 dBm (4 x 5 W)
visits.
tBW/OBW
150 MHz / 80 MHz
Feature, and Benefits
Key T.Wc.1Spmifieatiou
Installation
Pole/Wall/Tower (Pack to back, Side by side)
Fealuras cord Benefit,
Key Tecluilcal 6pecifca[ions
• Dual -band support for broad frequerwyc-exage
Duplex Type: FDD
• Minimal footprbn,edaces site costs
OpcAW Frequencies:
• Dual.baod support fox broad fr quency coverage
Duplex Type: FDD
Rapid, ea,y i-11ati on
1366:Du2,D0-2,18oldFlz),UU 1,710-1,790MIU)
Mii=l fuutpiut xcduce„eau,
DPemting Faq ies:
Weight/Size
RRH: B_S x 12 x 4.2 inches(7.OQ. 17.6 lbs
Flexibly deployable in any
• location
A2: DLC,930-1,9Whm,,)4J" 1,H50-1,91 DWI.)
• Rapid, easy installatior.
B13-D4746-756N1eUt UH777-i87MHz)
• Remote RF morriW,ing wpnbilit
Instantaneous tlandwidlh:
�2)
• Plexibly deployable in any location
A5: DL(869-R94MH7)gR4924-849MRx)
Ise
•q lbs
Antenna: 8. x1G-3 x1_3i es 2.3L, 3.3
. Convention cooled silent opuefiou
RF C'lui.. 47R/6T4A/2T2R
Remote RFmonitmingcapxbdity
>
Chneon4R'2T4R'2:lOMDzctl13)+25MHz(B5)
RF Clwin: 4T4Ri2T4Ri2T2R
• Anat-in Broadcast Auxiliary Sevices(BAS)fRer
DutputPo Tod1320W
• Cmn tion000led.,JmtWemtion
OmputP.—Tnta112OW
ACAIX:4.1x115x3.3inches (2.6Q,5.51bs
anuplianl AW 6 operation without impaolh�g
DU-RU Interface: CPR] (10(ibps)
DU.RU Interfi CPRF (I0KJWs)
Woyalnt
Dimensions: 380. 380. 255mm (36.8L)
Dimensions: 380. 380 x 207mm (29.91.)
31.9kg
RRH + antenna _ 8.7 x 12.3 x SS inches (9.6t)
Weight: 38.3kg
Input Power: 48V ➢C
Opernting Temp.: Ao - ss (w;n ,ewx maa)
Weight:
Input Power: 48V DC
Op—nig Temp.: 40 - 55'(W. al. load)
RRH + AC/DC : 11.2 x 12.1 x 4.2 inches (9.3L)
Cooling: Natural convstion
Cooling: Natural o—doa
RRH + antenna + AC/DC =11.3 x 12.3 x S.5 inches (1251L)
RRU SPECIFICATIONS
SCALE: NOT TO SCALE
Figure 3. Systsrn View (whh CNpon Antenna +AGOC Power Unit)
RRU SPECIFICATIONS
L SCALE: NOT TO SCALE
13SAMNT-SBS-1-2
Side-By-S l? Mounting Cttn mounttwa an-ennas on a pre with 2375-451nch (6U - 1L5 ram)
diartleter
IUrdt: U.lttint pw seNia andn,.H Es=a,ma5'anre„„a
General 5pecif cat]o ns
1 � m \ appllxaee,! a�manr
ree. 5
Dime tsions
Crop View] re.w•,�d. a•mn.r. n.a,lm�m tla, ram , 4—
ryriniea,m.r•r.m:.r:n•am 51 ram saran
11.4(2894)
Matedal5pecificdion5
eaeenN type ts—ved soee'
Packaging and 1Waghts
I IR��4.d l�d�ek I P�,a.ar.
• _ I wrllamna quemiN I
• I Regulatgry Compliance./Cw't]firacions
1 1A • 11 Ill Araaw� 4 Hr ,e, en, a nn tact
Q..... o. Ixo yaal::ors o,s5^•a.m3n.ammee�wa d„ab�pa �,ae a+.nwuy,.a�.9an,.�n,y<le.,
�, � I AACF !VXC=wnVl�nu a�Vn STIC,uvcix���i mnv,unnm,uV•'.-�neVFm�lu.l'.a�iryliurn
Act
[Le" View] [Front View] .R.Ohi e:.[ [Rear s: ierv;
Included Products
4iAaWR- _ wi ket seta!M xlie tio:mm brac6er sct9 cot Forz4-45in Wl-Its mmlW mui,imm,�rf gt �zm oees,.usw top
(,Doom ViI
-\VZS01 SPECIFICATIONS (2) �-BSAMNT—SBS-1-2 SPECIFICATIONS
`fi SCALE: NOT TO SCALE J SCALE: NOT TO SCALE
(-:��VZSO1 SPECIFICATIONS (1)
�SCALE: NOT TO SCALE
III■ e
311AEE: ��,
„-
I t
(IIII ���'.► .
I �Iili51•
Planning Administrative
Approval
COFFELL
12/03/2021
rea�xvsbemni - iAuir �aimniw smm
sun �-aure n, � rprmeuy
.- 4e. tip �0 iSY'A� lair i A
�-�VZWSMART—PLK6 V—BRACING KIT FOR MONOPOLE
v SCALE: NOT TO SCALE
' J
verizon
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS� services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 401 4234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
FCDO
08/10/2021
ND
FINAL
SN
FCDI
08/12/2021
ND
FINAL.
SN
FCD2
09/13/2021
ND
FINAL.
SN
��AK�oF.rE�gs��l
/ ...... ....... .....
121430
ills�o•C5����r
FIRM #-. 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL. ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
REVISION:
C-5
CD
ban
x. INAwrimo. eta.
00 00
®� O A
'\VZWSMART—PLK7 MONOPOLE COLLAR MOUNT
SCALE: NOT TO SCALE
/ n
SCALE: NOT TO SCALE
�� CROSSOVER ANGLE
L SCALE: NOT TO SCALE
�� NOT USED
�SCALE: NOT TO SCALE
a=
if
MYLL� ®[MEV
HMo• •V'a�0
E-1 �
z� CROSS OVER CHANNEL BRACKET
�SCALE: NOT TO SCALE
NOT USED
v SCALE: NOT TO SCALE
Planning Administrative
Approval
COFFELL
12/03/2021
'
verizont
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS� services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 401 4234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
FCDO
08/10/2021
ND
FINAL
SN
FCDI
08/12/2021
ND
FINAL.
SN
FCD2
09/13/2021
ND
FINAL.
SN
A.t�4F.rE�gs�1,
i
... ...............
1 21 4 3 0
(jii4,c�S�!C� NS��•��2��r
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL. ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
REVISION:
C-6
CD
J
TO ANTENNA COAX TO ANTENNA COAX
COPPER/GALVANIZED GROUND BAR COPPER/GALVANIZED GROUND BAR
0� 0 �00000000000000 j o�� 0000000000000
00000000000000 0 0 0000000000000
DOo0 o000000000000000@ 00000000000000000' 0
#2 SOLID TINNED COPPER
CONDUCTOR TO TOWER/SHELTER
TWO HOLE LONG BGROUND RING (2 TYR. FORARREL COMPRESSION LUG BOTTOM GROUND BAR ONLY)
TWO HOLE LONG BARREL
COMPRESSION LUG (TYP) (TYP)
NOTES:
1. DOUBLING UP "OR STACKING" OF CONNECTIONS IS NOT PERMITTED.
2. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
3. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO ANTENNA MOUNT STEEL.
/'-7'\ANTENNA SECTOR GROUND BAR DETAIL
SCALE: NOTTO SCALE
TO TOWER MOUNTED EQUIPMENT
(TYR)
TO ANTENNA —
STANDARD COAX
CABLE GROUND KIT
(TYR)
#6 STRANDED CU WIRE WITH
GREEN, 60OV, THWN
INSULATION (OR AS PROVIDED
WITH GROUND KIT) (TYR)
COAX CABLE
(TYP FOR ALL)
TO BTS EQUIPMENT VIA
TRAY OR ICE BRIDGE
MONOPOLE
ANTENNA GROUND BAR
LOCATED AT MCL
(BONDED TO TOWER STEEL)
2 HOLE LUG (TYP)
MECHANICAL CONNECTION
(TYR)
COAX GROUND BAR WITH
INSULATORS, CONNECTED
DIRECTLY TO THE BOTTOM
OF MONOPOLE. SEE NOTE 1
2/0 TINNED BARE
COPPER WIRE
MONOPOLE PIER
GROUND WIRE
SEE NOTE 3
GROUND WIRE
NOTE 3
Z4�_-- - 1L--�-i-��
INSPECTION WELL I EXOTHERMIC WELD (TYP)
I
NOTES:
1. NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA
LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON THE
TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED.
2. ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE USA INC.
TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI —OXIDANT COATING.
3. ALL TOWER GROUNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE
RECOGNIZED EDITION OF ANSI/TIA 222 AND NFPA 780.
TYPICAL ANTENNA CABLE GROUNDING
4 SCALE: NOT TO SCALE
NOTES:
1. EXTERIOR ANTIOXIDANT JOINT COMPOUND TO BE USED ON ALL EXTERIOR CONNECTIONS.
2. GROUND BAR SHALL NOT BE ISOLATED FROM TOWER. MOUNT DIRECTLY TO TOWER STEEL (TOWER ONLY).
3. GROUND BAR SHALL BE ISOLATED FROM BUILDING OR SHELTER.
---\TOWER/SHELTER GROUND BAR DETAIL
Z SCALE: NOT TO SCALE
STAINLESS STEEL BOLT
(TYR)
STAINLESS STEEL
FLAT WASHER
2—HOLE CRIMP/ (TYP)
COMPRESSION
CONNECTOR
GROUND
BAR
STAINLESS STEEL
FLAT WASHER
STAINLESS STEEL (TYR)
BELLVILLE WASHER STAINLESS STEEL NUT
(TYP) (TYP)
SINGLE CONNECTOR AT GROUND BARS
STAINLESS STEEL BOLT
STAINLESS STEEL
FLAT WASHER
DRAGON TOOTH WASHER
(TYP)
STEEL
2—HOLE CRIMP/
COMPRESSION STAINLESS STEEL
CONNECTOR J::�LFLAT WASHER
YP)
STAINLESS STEEL STAINLESS STEEL NUT
BELLVILLE WASHER (TYP)
(TYP)
SINGLE CONNECTOR AT STEEL OBJECTS
STAINLESS STEEL
SELF —DRILLING STAINLESS STEEL
METAL SCREW
FLAT WASHER
(TYP)
(TYP)
2—HOLE CRIMP/
COMPRESSION
CONNECTOR
DRAGON TOOTH
METALLIC OBJECT
WASHER
(TYP)
SINGLE CONNECTOR AT METALLIC/STEEL
OBJECTS
HARDWARE DETAIL FOR EXTERIOR CONNECTIONS
5 SCALE: NOT TO SCALE
T/FINISH GRADE
<25T l �
w
0
0
z
z
o EXOTHERMIC WELD
IT
CADWELD TEST LOOP TO
GROUND RING WIRE
NOTES:
8" PVC PLUG
/-- 8" PVC PLUG CPLG. (THIRD.)
#2 SOLID (TEST LOOP)
NOTCH SIDES OF 8" PVC SCH
40 PIPE TO ALLOW EXIT/
ENTRANCE OF GROUND RING
WIRE
TRENCH BOTTOM
2/0 TINNED CU EXTERNAL
TOWER GROUND RING WIRE
5/8" 0 x 10'-0" LONG
COPPER CLAD GROUND ROD
1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D)
INSPECTION WELL DETAIL
SCALE: NOT TO SCALE
6" WIDE METALLIC HTEL
GRADE WARNING/LOCATOR TAPE AT
12" DEPTH
0
0
z
c�
EXOTHERMIC WELD
0
w
GROUND RING #2 COPPER WIRE
SOLID, TINNED FOR CARRIER AND ICE
BRIDGE GROUND LOOP
GROUND RING 2/0 FOR
TOWER GROUND LOOP
GROUND ROD COPPER
CLAD STEEL ROD W/MIN.
5/8 0 x 10'-0" LONG
NOTES:
1. GROUND ROD SHALL BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM THE
VERTICAL
2. GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE.
(WHICH EVER IS GREATER) AS PER N.E.C. ARTICLE 250-50(D)
GROUND ROD DETAIL
6 SCALE: NOT TO SCALE
Planning Administrative
Approval
--C-APPELL
12/03/2021
E
verizon/
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS�
services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
PCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
�F.... q,q
. .. ...... ... . . ....
l
.. ............. . ..... .�
1 21 4 3 0
NS�.C5�2��r
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
REVISION:
G-1
FCD
.I&
/-\
im
\
*
TYPE HS
TYPE 2—YA-2
TYPE XA
TYPE YA-2
TYPE GY
Z:� F44
TYPE NO TYPE SS TYPE OR
WIRE SIZE
BURNDY LUG
BOLT
SIZE
#6 AWG GREEN INSULATED
YA6C-2TC38
3/8"
— 16 NO
S 2
BOLT
#2 AWG SOLID TINNED
YA3C-2TC38
3/8"
— 16 NO
S 2
BOLT
#2 AWG STRANDED
YA2C-2TC38
3/8"
— 16 NO
S 2
BOLT
#2/0 AWG STRANDED
YA26-2TC38
3/8"
— 16 NO
S 2
BOLT
#4/0 AWG STRANDED
BURNDY
YA28-2N
GROUND LUG W/
1/2"
— 16 NO
S 2
BOLT
TYPE VS TYPE VB
TYPE PT
TYPE GT'
NOTE:
1. ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES.
CONSULT WITH
CONSTRUCTION MANAGER FOR SPECIFIC
MOLDS TO BE USED FOR THIS PROJECT.
2. MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN CONNECTING GROUND RING
TO GROUND ROD.
CADWELD GROUNDING CONNECTIONS
SCALE: NOT TO SCALE
WEATHERPROOFING KIT
(SEE NOTE 3)
ANTENNA CABLE
#6 AWG STRANDED COPPER GROUND WIRE
(GROUNDED TO GROUND BAR). SEE NOTE 1 & 2
CABLE GROUND KIT
CABLE CONNECTOR
NOTES:
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND
WIRE DOWN TO GROUND BAR.
2. GROUNDING KIT SHALL BE TYPE AND PART NUMBER AS SUPPLIED OR
RECOMMENDED BY CABLE MANUFACTURER.
3. WEATHER PROOFING SHALL BE TWO—PART TAPE KIT, COLD SHRINK SHALL NOT
BE USED.
CABLE GROUND KIT CONNECTION
3 SCALE: NOT TO SCALE
3/8-11x1" TAMPER
RESISTANT BOLT
(TYP)
INSULATORS
SEE NOTE 2.
(TYP)
TO ANTENNAS
COAX JUMPER (TYP.)
CONNEC
WEATHERPROOFING
(TYP. SEE Nor[
ANTENNA CA
TO BTS EQUIPMENT (T
WEATHERPROOFING
KIT
(TYR)
GROUND KIT
(TYR)
#6 AWG
COPPER/GALVANIZED
COAX GROUND BAR
BONDED DIRECTLY TOWER
LONG BARREL HEAT SHRINK
(SEE CHART) (CLEAR)
NUT GROUNDING
(TYE) CONDUCTOR
LOCK WASHER
(TYP)
GROUND BAR BOLT
(SEE CHART)
(TYR)
BURNDY TWO HOLE LUG W/
LONG BARREL
(SEE CHART)
BARE WIRE TO BE
NO—OX AT BOTH ENDS
STRANDED (GREEN INSULATED) ONLY FOR #6 AWG
(SEE CHART)
NOTES:
1. ALL GROUNDING LUGS ARE TO BE INSTALLED PER MANUFACTURERS SPECIFICATIONS.
ALL HARDWARE BOLTS, NUTS, LOCK WASHERS SHALL BE STAINLESS STEEL. ALL
HARDWARE ARE TO BE AS FOLLOWS: BOLT, FLAT WASHER,GROUND BAR, GROUND LUG,
FLAT WASHER AND NUT.
/---\ MECHANICAL LUG CONNECTION
� SCALE: NOT TO SCALE
#6 AWG MIN. FROM ANTENNA
CABLE GROUND KIT
NOTES:
1. DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND
WIRE DOWN TO ANTENNA GROUND BAR. GROUND BAR ON SHELTER. ICE
2. WEATHER PROOFING SHALL BE TWO—PART TAPE KIT. COLD SHRINK SHALL NOT BE BRIDGE, OR ON ANTENNA TOWER
USED.
GROUND CABLE CONNECTION
SCALE: NOT TO SCALE
*TWO HOLE LUG, OR
EXOTHERMIC WELD TO BE USED
WITH #2 AWG BARE CONDUCTOR
WIRE TO BUILDING SERVICE
GROUND OR GROUND RING
o
WALL BRACKET
(TYP) ® ®
NOTE: MINIMUM OF
S/S NUT
®
® ® ®
3 THREADS TO BE
VISIBLE
(TYR)
(TYR)
®
S/S SPLIT
L9
®
WASHER
O
®
2 HOLE LONG
(TYR)
#2 TINNE
® ® UNIVERSAL COPPER
BARREL TINNED
SOLID COPPER
CONDU
® GROUND BAR (4%20")
LUG
S/S FLAT
v
(TYP)
WASHER
TERMIN/
LOCK WASHER
®
(TYE)
THE L
P/N M10
(TYP)
TWO —HOLE
COMPRESSION LUG
TIN COATED SOLID
NOTES:
COPPER BUS BAR
S/S FLAT
WASHER
1. DOWN LEAD (HOME RUN) CONDUCTORS ARE NOT TO BE INSTALLED ON CROWN CASTLE
(TYR)
USA INC. TOWER, PER THE GROUNDING DOWN CONDUCTOR POLICY GAS—STD-10091. NO
CHERRY INSULATOR
INSTALLED IF REQUIRED
MODIFICATION OR DRILLING TO TOWER STEEL IS ALLOWED IN ANY FORM OR FASHION,
S/S BOLT
CAD —WELDING ON THE TOWER AND/OR IN THE AIR ARE NOT PERMITTED.
(TYR)
2. OMIT INSULATOR WHEN MOUNTING TO TOWER STEEL OR PLATFORM STEEL
USE INSULATORS WHEN ATTACHING TO BUILDING OR SHELTERS.
GROUND BAR DETAIL
SCALE: NOT TO SCALE
LUG DETAIL
SCALE: NOT TO SCALE
GROUNDWIRE INSTALLATION
SCALE: NOT TO SCALE
GROUNDING SHALL BE
ELIMINATED WHEN GROUND BAR
IS ELECTRICALLY BONDED TO
METAL TOWER
6696 TRI COUNTY PARKWAY, SUITE 100
SCHERTZ, TX 78154
CCCROWN
CASTLE
1220 AUGUSTA DRIVE, SUITE 500
HOUSTON, TX 77057
BROADUS�
services
4 COUNTRY PLACE CIRCLE
DALWORTHINGTON GARDENS
TEXAS 76016
OFFICE: (817) 349 3449
FAX: 800 4014234
VERIZON SITE NUMBER:
295251
BU #: 876558
F3 - COPPELL MIDDLE S
1305 WRANGLER CIRCLE
COPPELL, TX 75019
EXISTING 71'-6" MONOPOLE
ISSUED FOR:
REV
DATE
DAWN
DESCRIPTION
DES./Q
CDO
05/17/2021
ND
PRELIMINARY
SN
PCDO
08/10/2021
ND
FINAL.
SN
FCD1
08/12/2021
ND
FINAL
SN
CD2
09/13/2021
ND
FINAL.
SN
�r'%>%,
F.
rE1�l
op . .. ...... ... . . .... ..
1 21 4 3 0
Ns�•C5�2��r
FIRM #: 19170
CAA SOLUTIONS, PLLC
CONSULTING ENGINEER
3400 STRATFORD ROAD
ATLANTA, GA 30326
(770) 548-8268
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER: REVISION:
G-2 FCD
)I
ES
MOUNT MODIFICATION DRAWINGS
PROPOSED CARRIER: VERIZON
verizon
TOWER OWNER: CROWN CASTLE
TOWER OWNER SITE #: 876558
CARRIER SITE NUMBER: 295251-VZW
CARRIER SITE NAME: WRANGLER
COORDINATES (LATITUDE: 32.934811 °, LONGITUDE:-97.001622°)
dw
FUZE ID # 16226318
10177
Planning Administrative
Approval
coPPEi%
12/03/2021
c
SGN-1 GENERAL NOTES 0
0
o�
w
F—
N
0
T
0
U
Contractor PMI Requirements
SHEET SHEET TITLE REV
ST-1 TITLE SHEET 0
PMI Accessed At https://pmi.vzwsmart.com
SBOM BILL OF MATERIALS 0
Smart Tool Vendor Project 10078301 Post MOD Analysis Report
SCF-1 CLIMBING FACILITY DETAILS 0
10078301
Number Project Number
SS-1 ANTENNA MOUNT MODIFICATION DETAILS 0
SS-2 MOUNT PHOTOS 0
VzW Location Code (PSLC) 295251 Report Dated 07/07/2021
SPECIFICATION SHEETS
*** PMI and Requirements embedded in Mount Analysis Report
VzW APPROVED SMART KIT VENDORS
0
Refer to Mount Modification Drawings Page for VzW SMART KIT Approved Vendors
-
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
TES JOB NO-
10078301
CUSTOMER SITE N0:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Exp.og/3o/aoai
s�
o /o /aoai
)RAWN BY,BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
TITLE SHEET
This drawing document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER: REV #:
ST-1 0
SGN-1 GENERAL NOTES 0
0
o�
w
F—
N
0
T
0
U
Contractor PMI Requirements
SHEET SHEET TITLE REV
ST-1 TITLE SHEET 0
PMI Accessed At https://pmi.vzwsmart.com
SBOM BILL OF MATERIALS 0
Smart Tool Vendor Project 10078301 Post MOD Analysis Report
SCF-1 CLIMBING FACILITY DETAILS 0
10078301
Number Project Number
SS-1 ANTENNA MOUNT MODIFICATION DETAILS 0
SS-2 MOUNT PHOTOS 0
VzW Location Code (PSLC) 295251 Report Dated 07/07/2021
SPECIFICATION SHEETS
*** PMI and Requirements embedded in Mount Analysis Report
VzW APPROVED SMART KIT VENDORS
0
Refer to Mount Modification Drawings Page for VzW SMART KIT Approved Vendors
-
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
TES JOB NO-
10078301
CUSTOMER SITE N0:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Exp.og/3o/aoai
s�
o /o /aoai
)RAWN BY,BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
TITLE SHEET
This drawing document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER: REV #:
ST-1 0
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
TES JOB NO-
10078301
CUSTOMER SITE N0:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Exp.og/3o/aoai
s�
o /o /aoai
)RAWN BY,BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
TITLE SHEET
This drawing document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER: REV #:
ST-1 0
BILL OF MATERIALS
QUANTITY
COUNTED
QUANTITY
PROVIDED
PART NUMBER
DESCRIPTIONS
SHEET LIST
PIECE
WEIGHT
(LBS)
WEIGHT(LB)
NOTES
MATERIAL& HARDWARE
1
1
VZWSMART-PLK7
MONOPOLE COLLAR MOUNTASSEMBLY
A-1, VZWSMART-PLK7
150.0
150.0
Galvanized
3
3
VZWSMART-PLK6
V-BRACING KIT FOR MONOPOLE
A-1, VZWSMART-PLK6
109.0
327.0
Galvanized
FOLLOWING ITEMS ARE"CUSTOM" PARTS
3
3
PST2875-10
2 1/2" PST (2.875" O.D. X 0.203" THK) X 10'-0" A53 GR-B 35KSI
SS-1
59.31
177.9
GALVANIZED
3
3
PV-XP-2530-HD
PERFECTVISION CROSSOVER CHANNEL BRACKET
SS-1
12.50
37.5
GALVANIZED
3
3
PV-XA-U
PERFECT VISION CROSSOVER ANGLE
SS-1
9.00
27.0
GALVANIZED
2
2
PN 115-203
SAFETY CABLE GUIDE (TUF-TUG OR EQUIV.)
SCF-1
0.00
0.0
GALVANIZED
TOTAL WEIGHT (LBS)=
719.4
VzW Mount Modification Kits - Approved Vendors
PerfectVision
Metrosite Fabricators, LLC
Sabre Industries Inc
Contact: Wireless Sales wirelesssales@perfect-vision.com
Phone Number 844.887.6723
Website www.perfect-vision.com
Contact: Kent Ramey kent@metrositellc.com
Phone Number (0) 706.335.7045 (M) 706.982.9788
Website metrositefabricators.com
Contact: Angie Welch akwelch@sabreindustries.com
Phone Number 866.428.6937
Website www.sabresitesolutions.com
SiteProl
CommScope
Contact: Paula Boswell Paula.boswell@vaImont.com
Phone Number 972.236.9843
Website www.siteprol.com
Contact: Salvador Anguiano Salvador.Anguiano@commscope.com
Phone Number 817.304.7492
Website www.commscope.com
The manufacturers listed are the approved vendors for the VzW Mount Kits. Each manufacturer will be aware of which kits have been through the VzW approval process and they are in turn approved to sell. Please note that the material utilized on the mount
modifications will be reviewed as a part of the Desktop PMI completed by the SMART tool vendor. It will be required that the VzW kits specified are utilized in the modification. All materials required for the designed modifications but not list in this sheet are
assumed to be provided by the contractor. All parts are galvanized unless noted otherwise.
►►I
ES
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
verizon
TES JOB NO-
10078301
CUSTOMER SITE NO:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Planning Administrative
Approval
COFFEii
12/03/2021
DRAWN BY:BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
AO FIRST ISSUE BS 07 07 21
0
0
0
0
SHEET TITLE:
BILL OF MATERIALS
This drawing/document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing/document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER:
RED/ #:
SBOM
0
GENERAL NOTES
1. ALL WORK SHALL COMPLY WITH THE ANSI/TIA-222—H, ANSI/ASSP A10.48, AND ANY OTHER GOVERNING BUILDING CODES AND OSHA
SAFETY REGULATIONS.
2. ALL WORK INDICATED ON THE DRAWINGS SHALL BE PERFORMED BY QUALIFIED CONTRACTORS EXPERIENCED IN TELECOMMUNICATIONS
TOWER, POLE AND FOUNDATION CONSTRUCTION.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND FABRICATION OF ALL MISCELLANEOUS PARTS (SUCH AS SHIMS),
TEMPORARY SUPPORTS, AND GUYINGS, ETC., PER ANSI/ASSP A10.48, TO COMPLETE THE ASSEMBLY AS SHOWN IN THE DRAWINGS.
4. CONTRACTOR SHALL PROCEED WITH THE INSTALLATION WORK CAREFULLY SO THE WORK WILL NOT DAMAGE ANY EXISTING CABLE,
EQUIPMENT OR THE STRUCTURE.
5. THE USE OF GAS TORCH OR WELDER, ARE NOT ALLOWED ON ANY TOWER STRUCTURE WITHOUT THE CONSENT OF THE TOWER
OWNER.
6. GENERALLY THE CONTRACTOR IS RESPONSIBLE TO CONDUCT AN ONSITE VISIT SURVEY OF THE JOB SITE AFTER AWARD, AND
REPORT ANY ISSUES WITH THE SITE TO TES BEFORE PROCEEDING CONSTRUCTION.
7. TEMPORARILY RELOCATE ANY EXISTING COAX ATTACHED TO THE LEGS AND/OR ANY OTHER MEMBERS WHERE OBSTRUCTION WITH
THE PROPOSED MODIFICATION MAY OCCUR.
8. IT IS THE RESPONSIBILITY OF THE GC TO VERIFY THAT THERE IS NO INTERFERENCES (WITH SAFETY CLIMB BRACKETS, TRANSMISSION
LINES, ETC.) PRIOR TO MOBILIZATION AND INSTALLATION OF THESE MODIFICATIONS.
9. PLEASE NOTIFY TES IMMEDIATELY IF ANY INSTALLATION ISSUES OCCUR RELATED TO THIS DRAWING @ 972-483-0607 OR
EMAIL—TESORDERS@TESTOWER.US
FABRICATION
1. ALL STEEL SHALL MEET OR EXCEED THE MINIMUM STRENGTH AS SPECIFIED IN THE DRAWINGS. IF YIELD STRENGTH WAS NOT NOTED
IN THE DRAWINGS, CONTRACTORS SHALL CONTACT TES FOR DIRECTION.
2. ALL FIELD CUT EDGES SHALL BE GROUND SMOOTH. ALL FIELD CUT AND DRILLED SURFACES SHALL BE REPAIRED WITH A MINIMUM
OF TWO COATS OF ZINGA COLD GALVANIZING COMPOUND PER ASTM A780 AND MANUFACTURER'S RECOMMENDATIONS.
WELDING
1. ALL WELDING SHALL BE PERFORMED BY AWS CERTIFIED WELDERS AND IN ACCORDANCE WITH THE LATEST EDITION OF THE AWS
WELDING CODE D1.1. ALL ELECTRODES TO BE LOW HYDROGEN, MATCHING FILLER METAL, PER AWS D1.1, UNO. (E70XX UNLESS
NOTED OTHERWISE).
2. PRIOR TO FIELD WELDING GALVANIZED MATERIAL, CONTRACTOR SHALL GRIND OFF GALVANIZING APPROX. 0.5" BEYOND THE
PROPOSED FIELD WELD SURFACES.
3. ALL WELDS SHALL BE INSPECTED VISUALLY. A MINIMUM OF 25% OF WELDS SHALL BE INSPECTED WITH DYE PENETRANT OR
MAGNETIC PARTICLE TO MEET THE ACCEPTANCE CRITERIA OF AWS D1.1. 100% OF WELDS SHALL BE INSPECTED IF DEFECTS ARE
FOUND.
4. WELD INSPECTIONS SHALL BE PERFORMED BY AN AWS CERTIFIED WELD INSPECTOR.
5. AFTER INSPECTION, ALL FIELD WELDED SURFACES SHALL BE REPAIRED WITH A MINIMUM OF TWO COATS OF ZINGA COLD
GALVANIZING COMPOUND PER ASTM A780 AND MANUFACTURER'S RECOMMENDATIONS.
BOLTED ASSEMBLIES AND TIGHTENING OF CONNECTIONS
1. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO THE PROVISIONS OF THE SPECIFICATIONS FOR STRUCTURAL JOINTS USING A325
OR A490 BOLTS AS APPROVED BY THE RCSC.
2. FLANGE BOLTS SHALL BE TIGHTENED BY THE AISC "TURN —OF —THE —NUT" METHOD. THE FOLLOWING TABLE SHOULD BE USED FOR
THE "TURN —OF —THE —NUT" TIGHTENING.
3. SPLICE BOLTS AND ALL OTHER BOLTS IN BEARING TYPE CONNECTIONS SHALL BE TIGHTENED TO A SNUG —TIGHT CONDITION.
4. THE SNUG —TIGHT CONDITION IS DEFINED AS THE TIGHTNESS ATTAINED BY EITHER A FEW IMPACTS OF AN IMPACT WRENCH OR THE
FULL EFFORT OF AN IRONWORKER WITH AN ORDINARY SPUD WRENCH TO BRING THE CONNECTED PLIES INTO FIRM CONTACT.
VERIFICATION AND INSPECTION
1. IF APPLICABLE, VERIFICATION INSPECTION TO BE PERFORMED SHALL BE IN ACCORDANCE TO IBC-2018 SECTION 1705.2 FOR STEEL
CONSTRUCTION AND TABLE 1705.3 FOR CONCRETE CONSTRUCTION.
TYPICAL BOLT ASSEMEBLY
BOLT
FLAT WASHER
LOCK WASHER
NUT
NOTES
1. ALL DIMENSIONS REPRESENTED IN THIS SHEET ARE AISC
MINIMUM REQUIREMENTS. CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS IN FIELD AND NOTIFY ENGINEER IF DISTANCES
ARE LESS THAN THOSE PROVIDED.
2. THE DIMENSIONS PROVIDED ARE MINIMUM REQUIREMENTS.
ACTUAL DIMENSIONS OF PROPOSED MEMBERS WITHIN THESE
DRAWINGS MAY VARY FROM THE AISC MINIMUM REQUIREMENTS.
3. SHORT SLOT HOLES SHALL ONLY BE USED WHEN DEPICTED IN
THE DRAWINGS.
4. MATCH EXISTING GAGES WHEN APPLICABLE, UNLESS MINIMUM
EDGE DISTANCE ARE COMPROMISED.
TABLE 8.2 NUT ROTATION FROM SNUG —TIGHT
CONDITION FOR TURN —OF —NUT PRETENSION ING
DISPOSITION OF OUTER FACE OF BOLTED PARTS
ONE FACE NORMAL TO
BOTH FACES SLOPED
BOLT LENGTH`
BOTH FACES
BOLT AXIS, OTHER
NOT MORE THAN 1:20
NORMAL
SLOPED NOT MORE THAN
FROM NORMAL TO BOLT
BOLT AXIS
1:20
AXIS d
NOT MORE THAN
1/3 TURN
1/2 TURN
2/3 TURN
4db
MORE THAN 4d6
BUT NOT MORE
1/2 TURN
2/3 TURN
5/6 TURN
THAN 8db
MORE THAN 8db
BUT NOT MORE
2/3 TURN
5/6 TURN
1 TURN
THAN 12db
° NUT ROTATION IS RELATIVE TO BOLT REGARDLESS OF THE ELEMENT (NUT OR BOLT)
BEING TURNED. FOR REQUIRED NUT ROTATIONS OF 1/2 TURN AND LESS, THE
TOLERANCE IS PLUS OR MINUS 30 DEGREES; FOR REQUIRED NUT ROTATIONS OF
2/3 TURN AND MORE, THE TOLERANCE IS PLUS OR MINUS 45 DEGREES.
b APPLICABLE ONLY TO JOINTS IN WHICH ALL MATERIAL WITHIN THE GRIP IS STEEL.
° WHEN THE BOLT LENGTH EXCEEDS 12db, THE REQUIRED NUT ROTATION SHALL BE
DETERMINED BY ACTUAL TESTING IN A SUITABLE TENSION CALIBRATOR THAT
SIMULATES THE CONDITIONS OF SOLIDLY FITTING STEEL.
d BEVELED WASHER NOT USED.
SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, JUNE 30, 2004
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS
NOMINAL HOLE DIMENSIONS
BOLT DIAMETER
STANDARD HOLE
SHORT LOT
1/2"
9/16"
9/16" X 11/16"
5/8"
11/16"
11/16 X 7/8"
3/4"
13/16"
13/16" X 1"
7/8"
15/16"
15/16" X 1 1/8"
1"
1 1/16"
1 1/16" X 1 5/16"
BOLT EDGE AND SPACING
BOLT DIAMETER
MIN EDGE
SPACING
MIN. _
EDGE
1/2»
7/8"
1 1/2"
5/8"
1 1/8"
1 7/8"
3/4"
1 1/4"
2 1/4"
7/8"
1 1 1/2"
1 2 5/8"
1 "
1 1 3/4„
1 3„
WORKABLE GAGES
ANGLE SIZE
GAGE
G! AGE
1
1 3/4"
1"
2'
1 1/8"
2 1/2"
1 3/8"
3"
1 3/4"
3 1/2"
2'
4'
2 1/2"
WORKABLE GAGES
1.5 X L LIMIT OF ALLOWABLE COPED
(MAX) S
PORTION OF ANGLE WITHOUT
ENGINEERS PRIOR WRITTEN
�,E::ll
APPROVAL J
�11
ES
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
verizon
TES JOB N0:
10078301
CUSTOMER SITE NO:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Planning Administrative
Approval
COFFEii
12/03/2021
DRAWN BY:BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
AO FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
GENERAL NOTES
This drawing/document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing/document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER:
REV #:
SIGN
0
1 LOCATION OF SAFETY CLIMB
SCF-1
NOTE:
1. INSTALL SHALL NOT CAUSE HARM TO THE STRUCTURE, CLIMBING FACILITY, SAFETY
CLIMB OR ANY SYSTEM INSTALLED ON THE STRUCTURE.
EXISTING OR NEN
EXISTING MONC
Ti
NEW SAFETY CLIMB CAE
GUIDE (PART# PIN 115-21
(TUF-TUG OR EQU
EXISTING SAFETY CL
CAE
COLLAR MO�INI
THREADED ROD
PICTURE OF SAFETY CLIMB
2 DETAIL
SCF-1
LOCATION OF
_IMB
�11
ES
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
verizon
TES JOB N0:
10078301
CUSTOMER SITE NO:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Planning Administrative
Approval
COPPELL
12/03/2021
DRAWN BY:BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
CLIMBING FACILITY
This drawing/document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing/document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER:
REV #:
SCF-1
0
�I
J
0
n
c
ISOMETRIC VIEW
EXISTING ANTENNA MOUNT @ 55' ELEV.
11
MOUNT MODIFICATION SCHEDULE
SL. NO. MOUNT MODIFICATION DESCRIPTION REFERENCE SHEET
NO.
REPLACE EXISTING ANTENNA MOUNT PIPE WITH 2 1 2 PST PIPE PST2875-10 ,
1 PER SECTOR. SS-1
2 INSTALL NEW PERFECT VISION CROSSOVER CHANNEL BRACKET (PV-XP-2530-HD) PV-XP-2530-HD
3 INSTALL NEW PERFECT VISION CROSSOVER ANGLE (PV-XA-U) E-1/PV-XA-U
INSTALL NEW VZWSMART MONOPOLE COLLAR MOUNT ASSEMBLY VZWSMART-PLK7
INSTALL NEW VZWSMART V-BRACING KIT TO MONOPOLE VZWSMART-PLK6
6 INSTALL NEW SAFETY CLIMB GUIDE SCF-1
FIELD CUTTING AND FIELD DRILLING MAY BE NECESSARY TO ACHIEVE THE REQUIRED DIMENSIONS
TEE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CLEAN-UP, REMOVAL AND DISPOSAL OF EXCESS MATERIALS
EL AND REMOVED FROM THE STRUCTURE AT THE COMPLETION OF THE PROJECT.
MEMBERS IN BLUE COLOR ARE NEW REINFORCEMENTS AND MEMBERS IN AQUA COLOR (IF SHOWN) ARE RELOCATED
MEMBERS
Z)iUL Vitw
)I
ES
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
verizon
TES JOB N0:
10078301
CUSTOMER SITE NO:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Planning Administrative
Approval
COPPELL
12/03/2021
DRAWN BY:BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
FIRST ISSUE BS 07 07 21
0
0
SHEET TITLE:
ANTENNA MOUNT
MODIFICATION DETAILS
This drawing/document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing/document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER:
REV #:
SS-1
0
hOE-
EXISTING RRUS/EQUIPMENT MAY BE RELOCATED
ALONG THE MEMBER TO ACCOMMODATE THE
INSTALLATION OF NEW MOUNT MODIFICATION
4
EXISTING ANTENNA MOUNT
® 55' ELEV
PHOTO 1
PHOTO 2
1"
_i
o e
o
c
w
oRa
.
N PHOTO 3
PHOTO 4
T
o
U
�)I
ES
Tower Engineering Solutions
1320 GREENWAY DRIVE, SUITE 600
IRVING, TX 75038
PH: 972 483-0607
verizon
TES JOB NO-
10078301
CUSTOMER SITE NO:
295251—VZW
CUSTOMER SITE NAME:
WRANGLER
1305 WRANGLER CIRCLE
COPPELL, TX 75019
TOWER ENGINEERING SOLUTIONS, LLC
TEXAS REGISTERED ENGINEERING FIRM
F-15688
Planning Administrative
Approval
COPPELL
12/03/2021
DRAWN BY:BS CHECKED BY: KSP/SK
REV. DESCRIPTION BY DATE
AFIRST ISSUE BS 07 07 21
0
0
A
SHEET TITLE:
MOUNT PHOTOS
This drawing/document is the property of
Tower Engineering Solutions, LLC. Information
contained herein is considered confidential in
nature and is to be used only for the
specific site that it was intended for.
Reproduction, transmission, publication or
disclosure by any method is prohibited
except by express written permission from
Tower Engineering Solutions, LLC. Without
exception, the information on this
drawing/document remains the property of
Tower Engineering Solutions, LLC.
SHEET NUMBER:
REV #:
SS-2
0
THE FOLLOWING DRAWINGS ARE INCLUDED FOR REFERENCE ONLY
PLEASE REFER TO THE INSTALLATION DRAWINGS FOR ACTUAL INSTALLATION DETAILS
CROSS OVER CHANNEL BRACKET
CROSS OVER CHANNEL BRACKET
WEIGHT: SEE TABLE 1
2
TOP VIEW
7 1/2"
PIPE 1
SEE TABLE 1
SIDE VIEW
TABLE 1: PIPE COMPATABILITY
PART#
PIPE 1 SIZE
PIPE 2 SIZE
WEIGHT
PV-XP-2030-HD
2-3/8" OD
3-1/2" OD
12.5 LBS
PV-XP-2530-HD
2-7/8" OD
3-1/2" OD
12.5 LBS
PV-XP-3030-HD
3-1/2" OD
3-1/2" OD
12.5 LBS
PV-XP-3040-HD
3-1/2" OD
4-1/2" OD
12.5 LBS
PfiRFECrV6M1
M A N U h A G: 1 u n r N G
16101 La Grande Dr.
Little Rock, AR 72223
(630)-201-4012
STAMP:
Planning Administrative
Approval
COPPELL
`� ,
12/03/2021
The information contained in this set of
documents is proprietary by nature. any
use or disclosure other than that which
relates to the client named is strictly
prohibited.
REVISIONS:
to
�
a
�
Y
=
Q
U
Z
}
O
m
w
a
w
J
Z
0
LU
n
J
Of
a
U
m
z
o
w
Q
0
0
SITE INFORMATION:
DESIGN TYPE:
CROSS OVER
CHANNELBRACKET
SHEET TITLE:
ENGINEERING DETAIL
SHEET TITLE:
REVISION:
E-1
Q
PV-XA
I
PV-XA-2020
PIPE COMPATIBILITY: SEE TABLE 1
WEIGHT: 6.5 LBS
qn
PV-XAU-2
PIPE COMPATIBILITY: SEE TABLE 1
WEIGHT: 7.8 LBS
In
PV-XA-U
PIPE COMPATIBILITY: SEE TABLE 1
WEIGHT: 9.0 LBS
TABLE 1: PIPE COMPATIBILITY
PART# I
PIPE 1 COMPATIBILITY
PIPE 2 COMPATIBILITY
WEIGHT
PV-XA-2020
2-3/8" OD
2-3/8" OD
6.5 LBS
PV-XAU-2
2-3/8" OD
UP TO 4" OD
7.8 LBS
PV-XA-U
UP TO 4" OD
UP TO 4" OD
9.0 LBS
F&qFECTVi RM..
I'dA I'dU h A G: 1 u n r N G I
16101 La Grande Dr.
Little Rock, AR 72223
(630)-201-4012
STAMP:
Planning Administrative
Approval
COPPELL
12/03/2021
The information contained in this set of
documents is proprietary by nature. any
use or disclosure other than that which
relates to the client named is strictly
prohibited.
REVISIONS:
U
�
a
�
Y
=
Q
U
Z
o
m
w
a
w
J
Z
0
uJ
n
J
Of
a
U
m
z
o
w
Q
0
0
SITE INFORMATION:
DESIGN TYPE:
CROSSOVER
ANGLE
SHEET TITLE:
ENGINEERING DETAIL
SHEET TITLE:
REVISION:
E-1
Q
I
EXISTING MONOPOLE
O
O
(TYP)
i
O
O
O
O
O
O
2 3 4 5
(TYP)
O O
PLAN VIEW
MONOPOLE
COLLAR MOUNT ASSEMBLY
6"
co
1
(TYP)
VZWSMART-PLK7 (MONOPOLE COLLAR MOUNT ASSEMBLY)
ITEM N0.
QTY.
PART NO. DESCRIPTION SHEET # WT
1
3
CM-1245 COLLAR MOUNT ASSEMBLY PLK7—F1 147
2
6
--- THREADED ROD 5/8" X 4'-0" A193-37 ---
FRONT VIEW
3
12
FW-625 5/8" HDG USS FLAT WASHER 1
NOTES:
4
=1
LW-625 5/8" HDG LOCK WASHER --- 0
1. FIT 12" TO 45" DIA MONOPOLE.
5 1
12
NUT-625 5/8" HDG HEX NUT --- 1
2. HOT —DIPPED GALVANIZED PER ASTM A123.
GALVANIZED WT 150
V9h)
z
V'r
SMART Tool'
Vendor
verizon
Planning Administrative
Approval
COPPELL
12/03/2021
DRAWN BY:BT CHECKED BY: HMA/KW
REV. DESCRIPTION BY DATE
FIRST ISSUE BT 05 11 20
0
0
0
0
SHEET TITLE:
VZWSMART-PLK7
MONOPOLE COLLAR
MOUNT ASSEMBLY
SHEET NUMBER: REV #:
VZWSMART-PLK7 Q
V'r
SMART Tool'
Vendor
verizon
Planning Administrative
Approval
COPPELL
12/03/2021
DRAWN BY:BT CHECKED BY: HMA/KW
REV. DESCRIPTION BY DATE
FIRST ISSUE BT 05 11 20
0
0
0
0
SHEET TITLE:
VZWSMART-PLK7
MONOPOLE COLLAR
MOUNT ASSEMBLY
SHEET NUMBER: REV #:
VZWSMART-PLK7 Q
VZWSMART MONOPOLE COLLAR M�
ASSEMBLY. (NOT INCLUDED IN THIS
EXISTING MONO
0
6
(TYP) (TYP)
8 9 10
/Tvn\ . 4r
(TYP)
V—BRACING TO BE FIELD CUT
AND DRILLED AS PER DETAIL "A"
q 111,
V
"SEE INSTALLATION DRAWING" "SEE INSTALLATION DRAWING"
V—BRACING KIT FOR MONOPOLE
PLAN VIEW
(TYP) FIELD CUT & TRIM TO MATCH
THE REQUIRED LENGTH
O
O
2
EXISTING MONOPOLE
V—BRACING KIT — VERTICAL (OPTION-2)
SIDE VIEW
NOTES:
1. HOT —DIPPED GALVANIZED PER ASTM A123.
SUPPORT RAIL
(FIT 1.66" TO 4.5" O.D. PIPE)
(NOT INCLUDED IN THIS KIT)
V—BRACING KIT — HORIZONTAL (OPTION-1)
SIDE VIEW
FIELD DRILL 11/16" DIA. HOLE
FRONT VIEW
DETAIL "A"
1 1/8"
N
N
M
nnnr it nrnURED.
KISTING ANTENNA
OUNT PIPE
UPPORT RAIL
(FIT 1.66" TO 4.5" O.D. PIPE)
(NOT INCLUDED IN THIS KIT)
�J
(TYP)
5 8 9 10
(TYP)
3
(NP)
EXISTING ANTENNA
MOUNT PIPE
SUPPORT RAIL
(FIT 1.66" TO 4.5" O.D. PIPE)
(NOT INCLUDED IN THIS KIT)
VZWSMART—PLK6 (V—BRACING KIT FOR MONOPOLE)
ITEM
N0.PART
QTY.
NO.
DESCRIPTION
SHEET #
WT
1
1
BRKW-6A
WELDMENT BRACKET
PLK6—F1
16
2
2
L252525-8
L 2 1/2" X 2 1/2" X 1/4" X 8'-0" A36
PLK6—F2
67
3
L
BP6875-10
PL 3/8" X 6 7/8" X 10" A36 BENT PLATE
PLK6—F2
20
4
2
AL—333
L 3" X 3" X 1 /4" X 3" A36
PLK6
5
4
THREADED ROD 5/8" DIA. X 10" F1554-36 HDG
-F2
6
5
— — —
BOLT 5/8" X 2 1 /4" A325
7
4
— — —
BOLT 5/8" X 1 3/4" A325
— — —
--
8
17
FW-625
5/8" HDG USS FLAT WASHER
— — —
2
9
17
LW-625
5/8" HDG LOCK WASHER
---
0
10
17
NUT-625
5/8" HDG HEX NUT
---
GALVANIZED
WT
109
Vzw
SMART Tool'
Vendor
Planning Administrative
Approval
COPFELL
'(-7 e
12/03/2021
DRAWN BY: FL CHECKED BY: KL/BT
REV. DESCRIPTION BY DATE
FIRST ISSUE FL 04 13 21
0
ZAI
0
SHEET TITLE:
VZWSMART-PLK6
V-BRACING KIT FOR
MONOPOLE
SHEET NUMBER:
REV #:
VZWSMART-PLK6
Q