Fire Marshal memo re dispenserFrom: Travis Crump
To: Gary Sieb, Isabelle Moro
Date: 7/27/99 1:46PM
Subject: PARK N FLY SUP
Gary and/or Isabelle,
I have reviewed the site plan for the fuel dispenser at Park n Fly and I have one major problem with the
submittal. The Fire Code (Section 7903.3.3) requires that the fuel dispenser be located at least 15 feet
from any building, combustible material, property lines, streets or alleys. In addition, the dispenser must
be at least 25 feet from any openings in a building. The plans show the dispenser only two feet from the
building. Since the roadway to the east is a fire lane, they can not move it that direction. I don't know if
you want to go ahead and notify the applicant since this will totally change his SUP site plan and wind up
wasting your valuable time discussing a project that can not go forward in its present configuration.
Please let me know if there is anything else you need from me.