PD133HCR3-DR010927 (5) DE VEL OPMENT R E VIE W COMMITTEE
FIRE PREVENTION COMMENTS
ITEM: PD-133R3 MA GNOLIA VILLA GE
DRC DATE: SEPTEMBER 27, 2001
CONTACT: TRA VIS CR UMP, FIRE MARSHAL. (972) 304-3503
COMMENT STATUS: l rnrrr' ~ ' ] PRELIMINARY I ~'nr ~ '
1. All portions of the structure are to be within 150 feet from a fire lane. All fire lanes to be 6" concrete on
a lime stabilized base.
2. Minimum inside radius on fire lanes is 30 feet. Minimum outside radius is 54 feet.
3. On-site fire hydrants are required.
4. This structure will be required to be equipped with an automatic fire sprinkler system.