PD136R-DR 981029 (2) DE VEL OPMENT RE VIE W C OMMI~EE FIRE PREVENTION COMMENTS ITEM: D/FW TRADE CENTER DRC DATE: OCTOBER 29, 1998 CONTACT: TRAVIS CRUMP, FIRE MARSHAL. (214) 304-3501 COMMENT STATUS: ,~,'r,~ A r oo~ ~ ov FINAL 1. A permanent fire lane is to be provided to this site. Minimum width for fire lane is 24 feet. Fire lane to be minimum six inches of concrete on a lime stabilized base. Minimum fire lane inside radius is 30 feet. Minimum outside radius is 54 feet. 2. Access gate to be provided prior to placing station in operation.. 3. Fire lanes to be platted as easements.