Loading...
PD194-DR010927 (5) DE VELOPMENT RE VIE W COMMITTEE FIRE PREVENTION COMMENTS ITEM: AMBERPOINT BUSINESS PARK, LOT 1 BLK A DRC DATE: SEPTEMBER 27, 2001 CONTA CT: TRA VIS CR UMP, FIRE MARSHAL. (9 72) 304-3 503 COMMENT S TA TUS: l t~rrr,,~ , I PREI, IMINARY 1. All portions of the structure are to be within 150 feet from a fire lane. All fire lanes to be 6" concrete on a lime stabilized base. 2. Minimum inside radius on fire lanes is 30 feet. Minimum outside radius is 54 feet. 3. On-site fire hydrants are required. $ EP 2 7 2001 4. This structure will be required to be equipped with an automatic fire sprinkler system.