Loading...
PD162-DR 970731 (4)DEVELOPMENT VIEW ¢OMMI EE FIRE PREVENTION ITEM: PD-162, ARCHON APARTMENTS DRC DATE: JULY31, 1997 CONTACT: TRA VIS CRUMb, ACTING FIRE MARSHAL. COMMENT STA TI]S: 997 (214) 304-3503 PRELt'Jt~:,,~ 2. 3. 4. 5. 6. All portions of all buildings to be within 150 feet of a fire lane. Fire hydrants to be lllllllllt on maximum 300' spacing along all fire lanes. Additional means of egress/ingress required for population of development. Opticom devices required at all control gates. No three story apartments will be supported by the Fire Department. Fire sprinkler systems required on all apartments and any accessory buildings over 5,000 sq. ft. Full fire alarm system required. Minimum inside radius on fire lanes is 30 feet. Minimum outside radius is 50 feet. Minimum width of fire lane is 24 feet.