PD178R-DR 991122ITEM:
DRC DA TE:
CONTACT:
COMMENT S TA TUS :
DE VEL OPMENT RE VIE W COMMITTEE
FIRE PREVENTIONCOMMENTS
PD-178R, TOWN CENTER WEST
NOVEMBER 22, 1999
TRAVIS CRUMP, FIRE MARSHAL. (972) 304-3503
IIirlTr.4 ~ PRELIMINARY
FIPL ~L
' 1. All portions of the building to be within 150 feet of a fire lane.
2. Fire lanes to be platted as easements.
3. An on-site fire hydrant is required.
4. This building will be required to be equipped with an automatic fire sprinkler system.