Loading...
PD178R-DR 991122ITEM: DRC DA TE: CONTACT: COMMENT S TA TUS : DE VEL OPMENT RE VIE W COMMITTEE FIRE PREVENTIONCOMMENTS PD-178R, TOWN CENTER WEST NOVEMBER 22, 1999 TRAVIS CRUMP, FIRE MARSHAL. (972) 304-3503 IIirlTr.4 ~ PRELIMINARY FIPL ~L ' 1. All portions of the building to be within 150 feet of a fire lane. 2. Fire lanes to be platted as easements. 3. An on-site fire hydrant is required. 4. This building will be required to be equipped with an automatic fire sprinkler system.