Loading...
Cpl HS Ad/AmPSPRv-DR 990624(09)DE VEL OPMENT RE VIE W COMMITTEE FIRE PRE VENTION COMMENTS ITEM: COPPELL HIGH SCHOOL ADDITION, SITE PLAN AMENDMENT DRC DATE: JUNE 24, 1999 CONTACT: TRAVIS CRUMP, FIRE MARSHAL. (972) 304-3503 COMMENT STATUS: I FINAL Additional fire lanes and fire hydrants will be required. All portions of the buildings to be within 150 feet of a fire lane. Fire hydrants to be spaced at no more than 300 feet on center as measured along the fire lanes. THE FOLLOWING IS INFORMATIONAL ONLY a. All buildings to be equipped with an automatic fire sprinkler system. Any building over 20,000 sq. ft. to be equipped with a standpipe system. b. All buildings will be required to have an automatic fire alarm system installed and monitored. c. KNOX boxes will be required.