FIRE PREVENTION COMMENTS
I~r~ur Plaza Addition, Lot 1, Block 1, Final Plat
JUN 5 996
All fire lanes to be mark~xi per Section 901.4,2 of Ordinance 95712 (Coppell Fir~ Code).
Acoo~s Gate to have Optioom System and means of mechanical override. Keys to be secured in an
approved Knox Box.
MacArt~ur Plaza Addition, Lot 3, Block i, Final Plat
Fisal Plat to show Cue lane easement,
' ' ' All portions of the
st~cmre to be wigan 150 £~t of a water supply.
Knox Box with keys required adjacent to main entrance of building.
Fir~ L~mes to be marked per Seotion 901.4.2 of Ordinance 9~712.
MacArfltur Phza Addition, Lot 4, Block 1, Final Plat
Show lo~ation of nearest fire hydrant.
Fir~ Lanes to be marked per Section 901.4.2 of Ordinance 95712.
Knox Box with keys required adjacent to main entrance of building.
N~d size of structure iii order to properly address any Fire Dcpartmeat concerns.
MacArtbur Plaza Addition, Lot-g, Block 1, F[nal Plat
Show location of nearest fire hydrant,
Fi~ laa~ to be marked p~ Section 901.4.2 of Ordinance 95712.
l~ox Box with keys required adjacent to main entrance of building.
Summit at the Sprin~s, Final Plat
No comment. Will address location and spacing of fn'e hydrants at a later date.
Pd-14S (CH)R, Woodridge Addition, Site Plan Amendment
No commont.
Saady Lake Addition, Lot 2, Block A, Preliminary Plat
Show fire lane easement on plat and site plan,
laside turning radius for fire lanc to be a minimum of 30 feet. Outside turning radius to be a
misimum of 50 feet. (Section 902.2,2.3, Ordinance 95712)
Show location of fire hydrants.
Fire sprinkler system and alarm system required.
Knox box with keys to be located adjacent to main entrance,
An unobstmoted vertical clearance of fourt0on (14) feet is requirtxi at all fire lanes. (Section 902.2.2.1,
Ordinance 95712)
All l~rtions of the stmctur~ to be within 150 £eet of a fire lane.