Magnolia Fish/MP,SP-DR010125 City of Coppell
Development Review Committee Comments
Planning Department
Magnolia Fisheries - Minor Plat and Site Plan Approval
217 Coppell Road, North of Sandy Lake Road
DRC Date: January 25, 2001 & February 1, 2001
Planning & Zoning Comm[qsion Meeting: February 15, 2001
City Council Meeting: March 6, 2001
*Please note that the site plan submittal package falls below the City's standards
with regard to the information necessary for staff review. Staff strongly
recommends against review by the Planning Commission until all issues have
been resolved. If the applicant wishes to proceed, any outstanding issues may
result in a recommendation of denial. The following is a list of items to be
addressed; however, additional comments may be generated at a later date.
Site Plan
o
10.
Parking required would be, at a minimum, one space per 1000 square feet of
warehouse and one space per 300 square feet of office, therefore a minimum of 5
spaces will be required. Additional parking may be needed depending on number
of employees.
· Parking, maneuvering and fire lanes are required to be concrete.
· Minimum parking space is 9' x 19'
· Where is the loading to occur? This area also needs to be concrete.
What is permitted to be constructed/paved and/or planted in the easement area?
Will there be a dumpster? If so, needs to be shown on the site plan. The dumpster
need to be screened and not facing the street.
How will this facility be lighted?
Will there be any attached or detached signage? If so, need specification of color,
materials, fonts, size, etc.
Need Elevations of all four sides of the building, including materials, colors,
heights, roof materials, etc.
A color board needs to be submitted for the February 1st DRC.
Information is needed about the proposed fountain, location, size, depth of pond.
Need to submit a Landscape Plan per Section 34 of the Zoning Ordinance. Some
landscaping credit may be available for the preservation of existing trees.
Fire Department Requirements: The fire lane needs to be concrete, minimum
inside radius, 30 feet, outside radius 54 feet. On-site fire hydrant required. All
parts of the building needs to be within 150 feet of a fire lane.
Minor Plat
Need to plat fire lane
Need Franchise Utility Signature Block - see attached.
Page 1 of 2
Need Flood Plain Administrator's signature block.
Remove the notation for the existing electric line from plat.
Remove the curb cuts from plat.
Bo
Please revise plats, site plans, landscape plans, and building elevations based
on staff recommendations. Should applicant disagree with staff comments please
provide reasons why staff recommendations should not be followed when you
attend the February PtDevelopment Review Committee (DRC) meeting.
Each applicant will bring two new sets of revised plats and plans to the
February 1st DRC meeting. Applicants will be asked to show, explain, and
defend any revision. A representative for this project is required to attend the
meeting.
Applicant will have till noon Tuesday, February 6th to resubmit sixteen (16)
folded copies of revised plans and three (3) reduced paper copies (8 1/2 X 11) of
each exhibit to the Planning Department
Page 2 of 2