MacPlaza1Sonic/FP-DR 960605 DRC FIRE PREVENTION COMMENTS MmeArMmr Plaza Addition, Lot 1, Block 1, Final Plat 5 996 All five lames to be marked per Section 901,4,2 of Ordinance 95712 (Coppell Fire Code). Arc,oas Gate to have Opticom System and means of mechanical ovemde, K~ys to be securext in an apl~V~ Knox Box. Mar. Arthur Plaza Addition, Lot 3, Block 1, Final Plat Fiat Pl~t to show fire lane easement, ' ' All portions of the s~ to be within 150 £e~t of a water supply. Knox Box with keys required adjacent to main entrance of building. Fire Lames to be marked per Seotion 901.4.2 of Ordinance 95712. M~e. Afflatr Plaza Addition, Lot 4, Block !, Final Plat Show looation of nearest fire hydrant, Fin Lames to be mar]~l ~ S~x~tion 901.4.2 of Ordinance 95712_ Knox Box with keys required adjacent to main ~ntrance of building. Nmmd size of structure in order to properly address any Fire D~partment concerns. Man, Arthur Plaza Addition, Lot S, Block 1, Final Plat Show location of nearest fire hydrant. Fi~e latona to be marked p~r Section 901.4.2 of Ordinance 95712. Knox ~x with keys reqnired adjacent to main entrance of building. Summit at the Sprinp, Final Plat No comment. Will address location and spacing of fu'e hydrants at a later date. Pd-14~ (CH)R, Woodridge Addition, Site Plan Amendment No commeat. Lake Addition, Lot 2, Block A, Preliminary Plat Show fire lane easement on plat and site plan. Inside turning radius for fir~ lane to be a minimum of 30 feet. Outside turning radius to be a minimum of 50 £cet. (Section 902.2,2.3, Ordinance 95712) ~zow location of fire hydrants. Fire sprinkler system and alarm system r0quirtxi. Knox box with keys to be located adjacent to main entrance. An mmimtmoted vertical clearance of fourteen (14) feet is requirtxi at all fire lanes. (Section 902.2.2.1, Oldimamc, e 95712) All peftions of the stmGture to be within 150 re, et of a f'u-e lane. ~ Fire Station, N~ 2, Lo~ 1, Block A, Preliminary Plat Show location of nearest fire hydratlt. ~ ir, side turning radius for fire lanes is 30 feet. ~ outside turning radius for fire lanes is 50 feet ~ Tow~ Cedar Addition, Prelimi~ry Plat and Replat Show fire lane easements on plat. ~ Town Center Addition, Lot 1 Block 2 ~ insid~ radius c~ fire lanes is 30 feet ~ ou~si~ radius on fire lanes is ~0 feet. JUN 5 ~996 ' , TOTAL P.03