Loading...
Lam Lee/Re,SPRv-DR 981029 (2)DEVELOPMENT REVIEW COMMITTEE FIRE PREVENTION COMMENTS ITEM: LAM LF~E ADDITION DRC DATE: OCTOBER 29, 1998 CONTACT: TRA VIS CRUMP, FIRE MARSHAL. (214) 304-3503 COMMENT STATUS: ~ PRELIMINARY F!NAL All portions of buildings to be within 150 feet of a fire lane. Royal Lane can not be used as a fire lane. Fire lanes to be platted as easements. Fire lanes to be 6" concrete on a lime stabilized base. Fire lanes to be installed per City of Coppell engineering standards. Fire hydrants to be spaced on a maximum 300 feet on center as measured along the fire lane. !i~i OCT2r41998