Magnolia Vill/MP-DR001130 (4)DE VEL OPMENT RE VIE W COMMITTEE
FIRE PRE VENTION COMMENTS
ITEM:
DRC DATE:
CONTA CT:
MAGNOLIA VILLAGE, LOT 1, BLK A, MINOR PLAT
NOVEMBER 30, 2000
TRAVIS CRUMP, FIRE MARSHAL. (972) 304-3503
COMMENT STATUS:
PRELIMINARY
I. Minimum inside radius for fire lanes is 30 feet, minimum outside radius is 54 feet.
2. This building will be required to have an automatic fire sprinkler system.
3. On site fire hydrants will be required.