Loading...
Fire Stat 2/PP,SP-DR 960605 DRC FIRE PREVENTION COMMENTS M~Ar~ur Plaz~ Addition, Lot 1, Block l, Finn] Plat JUN 5 1996 All fire lanes to be marked per Section 901,4,2 of Ordinance 95712 (Coppoll Fire Code). Access Gate to have Optioom System and means of mechanical override, Keys to be secured in an agq~oved Knox Box. M~,Ar~hur Plaza Additlou, Lot :3, Block 1, Final Plat Final Plat to show fire lane easement, ' ' All portions of the sJmciure to be within 150 feet of a water supply. Knox Box with keys required adjacent to main entxancc of building. Fi~ Lan~ to be marked per Section 901.4.2 of Ordinance 95712. Ma~Artlmr Plaza Addition, Lot 4, Block I, Final Plat Show location of nearest fire hydrant. Fips Lan~s to be marked per Section 901.4.2 of Ordinance 95712. Knox Box with keys required adjacimt to main entrance of building, Need size of structure in order to properly address any F/re Department concerns. MacArl~r Plaza Addition, Lot S, Block 1, Final Plat Sitow location of nearest fire hydrant, Fife lane~ to be marked p~r Section 901.4,2 of Ordinance 95712. Knox Box with keys required adjacent to main enlrance of building, Summit at the Springs, Final Plat No comment, Will address location and spacing of fu'e hydra~ts at a latc~ date. Pd-146 (CH)R, Woodridge Addition, Site Plan Amendment No commo~t. ~dy Lake Addition, Lot 2, Block A, Preliminary Plat Show ~ lane casement on plat and site plan. Inside turning radius for fire lane to be a minimum o£ 30 feet. Outside turning radius to be a mis/mum of $0 £eet. (Section 902,2.23, Ordinance 95712) Show location of fire hydrants. Fire sprinkler system and alarm system required. Knox box with keys to be located adjacent to main entrance, An Knobstmot~d vertical clearance of fourt~x,'n (14) feet is required at all fire lanes, (Section 902.2.2.1, Oldimm~ 95712) All p~tions of the stmctu~ to be within 150 feet of a fixe lane. Show location of nearest fire hydrant. Sax~e to have fire sprinkler system. ~ i~.side turning radius for fire lanes is 30 feec Mhairmm outsicie ttrning radius for fire lanes is 50 feet ~ Tmvn Center Addition, Prellrnlrmry Plat and Replat Show fire lane ~ on plat. ~ Town Cemer Addition, Lot 1 Block 2 lVfmimmn inside radius co fire lanes is 30 feet ~ outside rad~ on fire lanes is 50 feet. I,,IL IN 5 1996 ' TOTAL P.O~