Loading...
Nlake 635(9)/FP-CS 870130GINN, INC. CONSULTING ENGINEERS TO: FROM: DATE: SUBJECT-. City of Coppell Attn: Shohre Daneshmand, Civil Engineer Attn: Taryon Bowman, Senior Planning Technician Ginn, Inc. January 30, 1987 Lot 2, Block D Northlake 635 Business Park In the short time frame available to us, we made a cursory review of the above referenced subject for general conformance to the City of Coppell Subdivision Ordinance, Zoning Ordinance, and applicable standards. The following sets forth our comments. We last reviewed this project October 31, 1986, prior to preliminary plat submittal. If any of the following comments have already been addressed, please advise. 1. Lot and block numbers in written description do not coincide with title block. 2. Designate fire lanes on plat. 3. Open storage areas should be "screened" in accordance with Zoning Ordinance 32.1;5. e Dock area should be screened from view from Crestside Drive. Verify with Public Works whether water mains, sewer mains, or storm drainage system needs to be located within easement or not. Verify with fire marshall that fire lane turnaround can be used in lieu of cul-de-sac turnaround. e Will adequate parking be available when future expansion is completed? Be Use technical paper 40, not TP-25, in design of storm sewer. Also 100-year design frequency is required. 9. Indicate radii on driveway. 10. Minimum 8" water lines, to dead end fire hydrants. 11. Provide concrete rip-rap or type "C" headwall at ditch and 24" storm sewer. 12. Area south of building; will area for future parking expansion overlap the TP&L easement? 17103 Preston Road · Suite 100 · LB 118 · Dallas, Texas 75248 · Phone 214/248-4900 13. Do not use ductile iron pipe for sanitary sewer. 14. PVC water mains shall be Class 200, DR 14. Gabe Favre /ss