Loading...
Park Place/PP-DR 891031 (2) CITY OF COPPELL PUBLIC WORKS WATER UTILITIES DIVISION ~RELIMI/~~AN REQUIREMENTS DRC Date: Review of By: Howard Pafford, Water Foreman, Phone 462-8495 Water/Sanitary Sewer Plan Please make the following additions and/or corrections, as marked: l) - Show existing water lines in adjacent areas. 2) Show proposed water lines. (Minimum water line size 8 ") 3) 4) Show proposed valve and hydrant placement - (valves - 500 ft. separation/hydrants residential areas - 500 ft. separation and Commercial/Industrial 300 ft. separation). Note on plans - Estimated daily sanitary sewer flow - Estimated daily water demand 5) - Show existing sanitary sewer lines. 6) Show proposed sanitary sewer lines. (minimum line size 8") (Lines are required to be Straight with no curves). 7) Show proposed manhole and clean out placement (manholes maximum 500 ft. separation and clean outs at a maximum of 250 ft. from manholes). 8) Ail necessary easements should have a 20 ft. width unless centered on the property lines of two lots, then 25 ft. will be allowed. Page 1/2 ^PAGE 20~ 2 / 9) ~/ All above comments must be addressed, prior to staff's recommendation for approval of the ~/ preliminary plat and plans. 10) Provide a written response on all comments, with explanations provided on items not addressed as requested above. 11) ~ No comment. DRC / COMMENTS/WAT / P R! :L I M ! Page 2/2