Loading...
ParkW CC-7/Re-DR 971030 (4)0CT-30-1997 15:45 CITY OF COPPELL P.04 I DEVELOPMENT REVIEW COMMITTEE FIRE PREVENTION COMM ITEM: PAl~ S'F, ST COMnOtttCtt ~ fi, OrS 1-2,, CONTACT: IRAVlS CRUMP, ACTING ~ MARSHAi~ - I I Il lll COMMI~NT STA~_ _ S_;_ ~ P~AR¥ I Fire hydrants required 300 ft. on center along fLre lanes. Additional fire hydrants wiU be required. Fire Department Connection (FDC) can not be located on the building. Ixxaate between 3 and 6 feet from the f'u-e lane and within 50 feet of a fire hydrant. o Ali portions of the building will be required to be protected by a fully automatic f~rc sprinkler system. A Class III standpipe system is also required. 4. A fixe alarm system will be required.