Stoneleigh 1P/PP-DR 961031 (4)DEVELOPMENT REVIEW COMMITTEE
FIP PI VENTION
~ TRAVIS CRUMP, ACTING ~ MAI~HAI. (21,0 304-3503
COMMENT STATH$: ~ PRELIMINARY
1. All portions of buildings to be within a 150 feet hose lay distance from afire
lane.
2. All portions of buildings to be within a 150feet hose lay distance from afire
hydrant.
3. All fire lanes to be dedicated on plat.
4. Minimum inside radius on fire lanes to be 30 feet. Minimum outside radius
ts to be SO feet.
5. All Group R, Division 1 Occupancies shall be equipped with an approved,
hydraulically designed automatic fire sprinkler system. Residential or quick
response standard sprinklers shall be used in the dwelling units and guest room
portions of the building.
6. An approved fire alarm system shall be installed.
7. Any gate across afire lane shall be equipped with an Opticon system with a
Knox over-ride in case of power failure.
8. No dead end fire lanes over 50 fl long allowed without an approved apparatus
turn around.