Loading...
Town Center SC/PP-DR 960328 (2)DEVELOPMENT REVIEW COMMYI'KEE FIRE PREVENTION COMMENTS ITEM: Tow~ ~nter ~opp~ C.e~t~r, Prdimtnary Plat COMMENT STATUS: 1. fire lane width is 24' minimum 2. fire lane required on east side of Tom Thumb 3. Buildings w~ gross sq. ft > than 5,000' must have approved automatic spk system 4. Buildings w~ gross sq fi > than 20,000' must have Class III standpipe system 5. On site utilities and fire lanes must be in and accepted prior to construction above foundation 6. On site fire hydrants required 7. Fire lanes can not be asphalt