Vlgs of C P3/PP-DR 900329 (2)DRC Date: March 29, 1990
Review of:
CITY OF COPPELL
PUBLIC WORKS
WATER UTILITIES DIVISION
FRELIMINARY PLAN REQUIREMENTS
By:
How~rd Pafford, Water Foreman, Phone 462-8495
Water/Sanitar¥[ Sewer Plan
Please make ti~.e following additions and/or corrections,
as may~: ~
1) Sho~.- existing water lines in adjacent areas.
2)
Sho~,~ proposed water lines. (Minimum water line
siz~ 8 ")
3)
Sho~,~ proposed valve and hydrant placement -
(va3ves - 500 ft. separation/hydrants
resfdential areas - 500 ft. separation and
Conm~ercial/Industrial 300 ft. separation).
4)
Not~: on plans - Estimated daily sanitary sewer'
flow
- Estimated daily water demand
5) - Sho¥~ existing sanitary sewer lines.
6)
Shov~ proposed sanitary sewer lines. (minimum
lin~ size 8") (Lines are required to be
Strg~ight with no curves).
7)
Show proposed manhole and clean out placement
(mac,holes maximum 500 ft. separation and clean
out~ at a maximum of 250 ft. from manholes).
8)
Ail necessary easements should have a 20 ft.
wid[h unless centered on the property lines of
two lots, then 25 ft. will be allowed.
Page 1/2
^PAGE ~0F 2
9) ~ All above comments must be addressed, prior to
staff's recommendation for approval of the
preOiminary plat and plans.
10) ~
Provide a written response on all comments,
wit]~ explanations provided on items ,not
addressed as requested above.
11) -
DRC/COMMENTS
No comment.
C '
SD/HP/pd
Page 2/2