Vlgs of C P4/PP-DR 900329 (2)DRC Date March 29, 1990
Review of
CITY OF COPPELL
PUBLIC WORKS
WATER UTILITIES DIVISION
IctREL IMINARY PLAN
o: /
REQUIREMENTS
By:
Howard Pafford, Water Foreman, Phone 462-8495
Water/Sanitary Sewer Plan
Please make the following additions and/or corrections,
as marked:
1)
2)
Show existing water lines in adjacent areas.
Showlproposed water lines. (Minimum water line
size 8")
3)
Show proposed valve and hydrant placement -
(valves - 500 ft. separation/hydrants
residential areas - 500 ft. separation and
Commercial/Industrial 300 ft. separation).
4)
Note on plans - Estimated daily sanitary sewer
flow
- Estimated daily water demand
5) - Show existing sanitary sewer lines. -
6)
7)
8)
Show proposed sanitary sewer lines. (minimum
- ~ine size 8") (Lines are required to be
/__~trai.g_~ht with no curves).
Show proposed manhole and clean out placemenf-'~--,~
( (manholes maximum SiQQ_~[~,separation and clean
outs at a maximum of 25Q_ft. fr0_~_~nholesJ-.
Ail necessary easements should have a 20 ft.
width unless centered on the property lines of
two lots, then 25 ft. will be allowed.
Page 1/2
^PAGE 2 OF 2
9)
Ail above comments must be addressed, prior to
staff's recommendation for approval of the
preliminary plat and plans.
10)
Provide a written response on all comments,
with explanations provided on items not
addressed as requested above.
11) - No comment.
SD/HP/pd