Loading...
Vlgs of C P4/PP-DR 900329 (2)DRC Date March 29, 1990 Review of CITY OF COPPELL PUBLIC WORKS WATER UTILITIES DIVISION IctREL IMINARY PLAN o: / REQUIREMENTS By: Howard Pafford, Water Foreman, Phone 462-8495 Water/Sanitary Sewer Plan Please make the following additions and/or corrections, as marked: 1) 2) Show existing water lines in adjacent areas. Showlproposed water lines. (Minimum water line size 8") 3) Show proposed valve and hydrant placement - (valves - 500 ft. separation/hydrants residential areas - 500 ft. separation and Commercial/Industrial 300 ft. separation). 4) Note on plans - Estimated daily sanitary sewer flow - Estimated daily water demand 5) - Show existing sanitary sewer lines. - 6) 7) 8) Show proposed sanitary sewer lines. (minimum - ~ine size 8") (Lines are required to be /__~trai.g_~ht with no curves). Show proposed manhole and clean out placemenf-'~--,~ ( (manholes maximum SiQQ_~[~,separation and clean outs at a maximum of 25Q_ft. fr0_~_~nholesJ-. Ail necessary easements should have a 20 ft. width unless centered on the property lines of two lots, then 25 ft. will be allowed. Page 1/2 ^PAGE 2 OF 2 9) Ail above comments must be addressed, prior to staff's recommendation for approval of the preliminary plat and plans. 10) Provide a written response on all comments, with explanations provided on items not addressed as requested above. 11) - No comment. SD/HP/pd Page 2/2