Cottonwood Elem/MP-DR 950410DEVELOPMENT REVIEW COMMI~EE
FIRE PREVENTION COM&~ENTS
DRC DATE: , ~
CONTACT: JEFF JONES, F~RE MARSHAL. (214) 304-3500
COMMENT STATUS: ~ ,~PRELIMINAR Y FtNA~
1. Key box required.
2. Fire hydrants and fire lanes to be in a nd accepted prior to construction above
foundation.
3. Sprinkler system & standpipes require separate plan review and testing prior
to Certificate of Occupancy.
4. Dead end main for fire hydrant is shown as 6" line. Increase to 8" or loop
main.
5. Fire alarm to meet NFPA 72 standards.