Loading...
Cottonwood Elem/MP-DR 950410DEVELOPMENT REVIEW COMMI~EE FIRE PREVENTION COM&~ENTS DRC DATE: , ~ CONTACT: JEFF JONES, F~RE MARSHAL. (214) 304-3500 COMMENT STATUS: ~ ,~PRELIMINAR Y FtNA~ 1. Key box required. 2. Fire hydrants and fire lanes to be in a nd accepted prior to construction above foundation. 3. Sprinkler system & standpipes require separate plan review and testing prior to Certificate of Occupancy. 4. Dead end main for fire hydrant is shown as 6" line. Increase to 8" or loop main. 5. Fire alarm to meet NFPA 72 standards.