Cottonwood Elem/MP-DR 950323(6)DEVELOPMENT REVIEW COMMI~EE
FIRE PREVENTION COMMENTS
ITEM: Cottonwood Creek Elementary School
DRC DATE: March 23, 1995
CONTACT: JEFF JONES, FIRE MARSHAL. (214) 304-3500
COMMENT STATUS: ,/INITIAL pD~', ,~,n~A ~>v
1. Key Box required, per UFC 10.302. Key box may contain electrical
disconnect but must also include access keys to building.
- 2. Fire hydrants andfire lanes to be in and accepted prior to construction
above foundation. UFC 10-203.
3. Sprinkler system requires separate plan review and testing prior to
Certificate of Occupancy.
4. Post address visible from Minyard Drive.
5..Fire Extinguishes provided and installed according to UFC 10-1.
6. Dead end main for fire hydrant requires 8" main.
- 7. Fire Alarm to meet NFPA 72 standards.
Class I or H Standpipes required in lieu of access road.