Water & Sewage Plan C5 WATER METER · SEWER SCHEDULE
I.D. TYPE SIZE N'O. SEWER'
Q IRRIGATION 2" 1 -
Q DOMESTIC 2" 1 -
.Q DOMESTIC 2" . .... 1 -. ........
CONTRACTOR SHALL REFERENCE
MECHANICAL ENGINEER'S PLANS
FOR EXACT BUILDING SERVICE
SIZE AND LOCATIONS
~ ~N 89~51" ~= 252746'
W/ 4" LINE I
D
R.
,/ F.H. ~ ~--::,? _:~ ~~' H
"~x I 7._.
2.7521 ACRE TRACT x. -
24'
F1RELANE
INSTALL:
2-2" METERS (DOMES~C)
: :_ 1-2" VAL~
-Ez - 1-3" VAL~
~ 1-12"X8" TAPPING SLEEVE
6 ~ 1-8" VALW~
1-8"X2" TAPPING SLEEVE
3" DOM. -~;' 1-8"X3" REDUCER
1-8"X6" TEE
6" FIRE O' ~
co 1
6" SAN. SEW.~
J FL 6"~ 48X.XX ~ INSTALL:
f ~ 1-6" FIRE LINE
:~omosed ~o: '? I ~ ~ 1-6" FIRE VAULT
3 oc~ o _ ~ ~ AND SERVICE
2.752~ zones o
PROPOSED ~CE
~ ~ ~ INSTALL:
mi / ~
_~' ~C~ ~ I~ . ~ ~ 0 _ ~112 LF. OF 8" SAN.
o ON SUOPZ
F1RELANE
-
SANDY LAKE ROAD
~Copyright 2003 Bro,ckette/Dams/Drake, Inc. All Rights Reserved.
This dra~r~ng is the property of t3rockette/Davds/Drake, Inc,
Any modification or use of thls dra~dng ~rithout the express
,~rritten authorization of }3rockette/Da~is/Drake, Inc. is prohibited,
0 50 60 90
0
CO
- EXISTING CURB
- PROPOSED CURB
- PROPOSED WATER LATERAL
- PROPOSED SANITARY SEWER LATERAL
- CLEANOUT
GRAPHIC SCALE
1"=50'
CITY GENERAL CONSTRUCTION NOTES:
1. THE SIZE AND LOCATION OF ALL UNDERGROUND UTILITIES ON THESE PLANS WERE OBTAINED FROM AVAILABLE
RECORDS AND ARE APPROXIMATE. THE CONTRACTOR, PRIOR TO CONSTRUCTION, MUST DETERMINE THE
EXACT LOCATION AND ELEVATION OF ALL PUBLIC UTILITIES AND SHALL BE RESPONSIBILITY FOR CONTACTING
ALL FRANCHISE AND CITY UTILITIES. THE CITY DOES NOT ASSUME RESPONSIBILITY FOR UTILITIES NOT
SHOWN OR NOT IN THE LOCATION SHOWN.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT ALL PUBLIC U'RLITIES IN THE CONSTRUCTION
OF THIS PROJECT. ALL MANHOLES, CLEANOUTS, VALVE BOXES, FiRE HUDRANTS, ETC. MUST BE ADJUSTED
TO PROPER LINE AND GRADE BY THE CONTRACTOR PRIOR TO AND AFTER THE PLACING OF FINAL GRADE
AND/OR PAVEMENT. ANY REMOVAL O.R DAMAGE TO EXISTING IMPROVEMENTS SHALL BE REPLACED OR
REPAIRED BY THE CONTRACTOR AT HIS EXPENSE AND SHALL BE APPROVED BY THE CITY. SAID EXISTING
IMPROVEMENTS INCLUDE BERMS, DITCHES, FENCES, VEGETABLE, ETC.
5. DURING THE CONSTRUCTION OF THIS PROJECT, ANY INTERPRETATIO.N OF THE STANDARD SPECIFICATIONS FOR
PUBLIC WORKS CONSTRUCTION FOR NORTH CENTRAL TEXAS, AND ANY MATTER WHICH REQUIRES THE
APPROVAL OF THE OWNER, MUST BE APPROVED BY THE CITY BEFORE ANY CONSTRUCTION INVOLVING THAT
DECISION COMMENCES. ASSUMPTIONS ABOUT WHAT THESE DECISIONS MIGHT BE, WHICH ARE MADE DURING
THE BIDDING PHASE, WILL HAVE NO BEARING ON THE DECISION.
4. ANY TEST THAT FAILS TO MEET CITY REQU!REMENTS SHALL BE RE-TESTED AT THE CONTRACTOR'S EXPENSE.
THE CITY WILL ONLY ACCEPT SIGNED ORIGINAL COPIES OF ALL TESTING REPORTS FOR REV1EW.
5. ALL MATERIALS, CONSTRUCTION, TESTING AND WORKMANSHIP SHALL CONFORM TO THE CITY OF COPPELL
STANDARD CONSTRUCTION DETAILS AND SPECIFICATIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC
WORKS CONSTRUCTION FOR NORTH CENTRAL TEXAS, LATEST EDITION, EXCEPT AS NOTED HEREIN AND
APPROVED BY THE CITY.
6. ALL WATER MAINS 12" AND SMALLER SHALL HAVE A MINIMUM COVER OF 48", OR SUFFICIENT COVER TO
CLEAR OTHER UTILITIES AS MEASURED FROM TOP OF PIPE TO EXISTING GROUND LEVEL OR FINISHED GRADE,
WHICHEVER IS GREATER. ALL WATER MAINS 12" AND SMALLER SHALL BE PVC A.W.W.A. C900, DR-14, CLASS
200 WATER PIPE.
7. ALL TAPPING SLEEVES AND VALVES SHALL BE FULL BODY DUCTILE IRON. FITTINGS SHALL BE OF THE
MECHANICAL jiOINT TYPE OR SLIP dOINT, AND SHALL BE CLASS D, OR CLASS 2,50 ON SIZES 12" AND SMALLER
IN ACCORDANCE WITH A.W.W.A. SPECIFICATION C-110-64 AND C-11-64. ALL FITTINGS SHALL BE RESTRAINED
BY THE USE OF MECA-LUGS OR APPROVED EQUAL AND CONCRETE THRUST BLOCKING.
8. CONCRETE BLOCKING SHALL BE PROVIDED ON WATER MAINS AT ALL TEES, WYES, BENDS, CROSSES AND
FIRE HYDRANTS PER THE CITY STANDARDS. ALL CONCRETE FOR BLOCKING SHALL BE MINIMUM 2000 PSI
CONCRETE. POLYETHYLENE WRAP SHALL BE INSTALLED AROUND ALL DUCTILE IRON FITTINGS AND VALVES.
THE WRAP SHALL HAVE AN 8 MIL. THICKNESS AND BE WRAPPED AND HELD IN PLACE BY 2" WIDE PLASTIC
BACKED ADHESIVE TAPE (POLYKEN 900, SCOTCHRAP NO. 50 OR CITY APPROVED EQUAL). THE WRAP SHALL
BE INSTALLED W~THOUT BREAKS, TEARS OR HOLES IN THE FILM,
9. WATER LINES CROSSING UNDER STORM SEWER AND SANITARY SEWER LINES SHALL HAVE A MINIMUM
VERTICAL CLEARANCE OF 24" OR AS GOVERNED BY TNRCC CHAPTER 290 REQUIREMENTS. PARALLEL WATER
LINES SHALL BE AT LEAST 9' CLEAR HORIZONTALLY TO SANITARY SEWER LINES AND MANHOLES. WHERE
MINIMUM CLEARANCE CANNOT BE ACHIEVED, WATER LINES SHALL BE ENCASED BY A MINIMUM 6" ~000 PSI
CONCRETE TO 10' EITHER SIDE OF UTILITY CROSSING. WHERE WATER LINES CROSS CREEKS OR DITCHES, THE
WATER LINE SHALL BE PROTECTED BY CONCRETE ENCASEMENT AT LEAST 10' PAST THE EMBANKMENT SLOPE
ON EACH SIDE.
10. UNLESS OTHERWISE APPROVED BY THE CITY, ALL WATER VALVES SHALL BE RESILIENT SEAT GATE VALVES
(RSOV) &: VALVE BOXES SHALL BE BASS &: HAYS MODEL NO. .340-1 WITH A CAST-IRON LID OR CITY
APPROVED EQUAL "NO-FLOW" PROTECTORS/INSERTS SHALL BE INSTALLED IN ALL VALVE BOXES. AFTER THE
FINAL CLEAN UP AND ALIGNMENT HAS BEEN COMPLETED, THE CONTRACTOR SHALL POUR A REINFORCED
CONCRETE BLOCK AROUND ALL VALVE BOXES SO THAT THEY ARE FLUSH WITH THE FINAL GRADE.
11. ALL WATER METER VAULTS/BOXES SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AND LOCATED
IN A NON-PAVED AREA.
12. ANY PLUMBING INSTALLED OUTSIDE OF R.O.W. OR AN EASEMENT SHALL BE INSTALLED BY A LICENSED
PLUMBER AND INSPECTEB BY BUILDING INSPECTIONS.
1~. ALL WATER LINES SHALL BE STERILIZED AND PRESSURE TESTED TO 20'0 PS~ FOR A ;5-HOUR CONTINUOUS
PERIOD. ALL TESTING AND STERILIZATION SHALL BE MEET OR EXCEED NCTCOG SPECIFICATIONS.
14. ALL SANITARY SEWER PIPES 4" TO 15" SHALL BE PVC S:DR $5 OR 26 MEETING ASTM D3054 AND HAVE
RUBBER GASKET JOINTS. ALL SANITARY SEWER PIPES 18" AND LARGER SHALL BE PVC MEETING ASTM F679.
15.
ALL SANITARY SEWER LINES SHALL BE TESTED FOR INFILTRATION AND EXF1LTRATION IN ACCORDANCE WITH
CITY STANDARDS. TV INSPEOTIONS, LOW PRESSURE AIR TESTING, VACUUM TESTING OF THE MANHOLES, AND
MANDREL TESTING ARE REQUIRED O.N ALL SEWER LINES.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR PRODUCING ANY TRENCH SAFETY PLAN OR TRAFFIC CONTROL PLAN.
THIS DOCUMENT IS RELEASED FOR THE PURPOSE
OF INTERIM REVIEW UNDER THE AUTHORITY O:F
GLENN HITT, P.E. NO. 40566 ON 06-16-0,3.
IT IS NOT TO BE USED FOR CONSTRUCTION,
BIDDING. OR PERMIT PURPOSES.
BENCHMARK:
SQUARE CUT FOUND ON TOP CURB RETURN ON EAST SIDE OF MOORE STREET
AT SOUTH SIDE ENTRANCE OF TEXACO STATION :k. 160' SOUTH OF SANDY
LAKE ROAD. (BENCHMARK SHOWN ON SHEET 53 OF SANDY LAKE ROAD
RECONSTRUCTION PAVING/DRAINAGE PLANS BY KIMLEY-HORN ASSOCIATES)
ELEVATION: 492.04'
WATER &
SEWER
PI AN
COPPELL MEDICAL OFFICE BUILDING
COPPELL, TEXAS