DRC commentsCOPPELL
CITY OF COPPELL
DRC REPORT
Proiect Name
Proiect Type
Application Date
Case ManaRer
Proiect Description
CO??ELL
Gateway Business Park No,2, Lot 2, Block A (Ava
Site Plan Amendment (Revision)
9/22/2004
Gary Sieb
To allow for the addition of three air conditioner chillers along the east side of the existing building
Agency
Building Inspection
1 of 1
Reviewed By Review Date
Greg Jones 9/28/2004
Electric and Gas Jeff Curry 10/1/2004
Engineering Ken Griffin 9/30/2004
Fire Administration Tim Oates 10/1/2004
Parks and Recreation John Elias 9/29/2004
Planning Department Gary Sieb 9/28/2004
1. Equipmen/design must comply with energy
conservation code provisions (2000 IECC).
Site Plan Amendment Acceptable, please contact Jeff
Curry at 972-570-4126 to discuss possible upgrade of
TXU ED facilities serving the building.
1. It appears this work may impact drainage in the
2. There is both an 8" and a 3" water line in the
proposed construction area.
3. This work will require engineered drawings and a
permit from the Engineering Department
No comments
No comments.
1. Please provide dimensions of Chillers, Generators,
Transformers--I. w., h., sq ff.
2. Need dimensions of all screening walls.
3. Clearly show how spandrel glass/screening wall
elevation looks. Make sure colored exhibits are
submitted for Commission and Council packets.
4. Indicate on plan direction from which elevation
"photo" was taken.
5. Clarify statements under "Landscaping" relative to
number of trees.
6. Landscape Plan needs to provide botanical names,
size of plants, etc. in chart form.
7. It would be helpful if you could enlarge 1"=32'
exhibit-it's very difficult to read.
8. A note similar to the one you use for Generator
explanation needs to be added for
Chiller and Transformer information.
9. Verify Section 5 is properly oriented.