DRC commentsCOl'FELL
Proiect ID MP-04-0069
Address 756 W Sandy Lake Rd
CITY OF COPPELL
DRC REPORT
Proiect Name
COl'FELL
Coppell Trade Center, Lot 1 Block 1, Minor Plat
Proiect Type
Application Date
Case Manager
Project Description
Minor Plat
10/20/2004
Gary Sieb
allow the construction of approximately 195,845-square-foot building, (Phase 1) on a podion of approximately 40,6
acres of properb/located a~ong the north side of Sandy Lake, between Ncrthpoint (extended) and the extension of
Freeport Parkway
Agency
Building inspection
Electric and Gas
1 of 2
Reviewed By Review Date
Greg Jones 10/27/2004
Jeff Curry 10/25/2004
Engineering Ken Griffin 10/28/2004
Comments
1. No comments made
Plat Unacceptable, please contact Jeff Curry at
972-570-4126 to discuss easement requirements. Aisc
please change the signature block to TXU Electric
Delivery Company,
Utility Plan -
1. Private utilities shall not be located within a public
utility easement.
2. Minimum easement width of 20' for sewer line.
Easement should be "Utility Easement."
3. Indicate FDC location for each building.
4. How will the fire hydrants located in open paving
within the truck courts be protected?
5. Provide appropriate scale on drawings.
6. We need to look at the detail of the public water on
the west side of the property.
Drainage -
1. A detailed analysis of the drainage through this site
will be requested. Any increase in flow or velocity to
the adjacent property will need to be mitigated onsite,
or an agreement with the adjacent property owner will
be required.
2. Provide detailed cross sections of the channel to
justify the 82' width for the drainage easement.
3. Provide preliminary grading and drainage plans for
onsite drainage.
Plat -
1. Remove topo and utility lines from the plat.
2. Private water lines should not be within a utility
easement. Remove that designation from the plat.
3. Provide a minimum of 20' wide easement for new
sewer line location.
4. Fire vaults and all water meters shall be located
within the ROW, or a dedicated utility easement.
5. Add Flood Plain Adiminstrators signtature block.
Additional comments may be forthcoming with the
submittal of additional information and/or final
engineering plans
COl'FELL
Agency
Fire Administration
Parks and Recreation
Planning Department
Reviewed By
Tim Oates
John Elias
Gary Sieb
CITY OF COPPELL
DRC REPORT
Review Date
10/27/2004
10/27/2004
10/25/2004
COIF'FELL
Comments
1. Curve 33 and 34 need to have radius of 30' and 54'
respectively.
No comment
1. Re-label from "Preliminary" to "Minor" Plat.
2. Rearrange signature block so that utility blocks do
not separate Mayor and Planning Chair signatures.
3. Place page and volume number at lower right
portion of plat.
4. Plat is located in city of Coppell, not Dallas.
5. Make change to TXU signature block.