DRC comments City of Coppell
Development Review Committee Comments
Planning Department
ZC-599, Carrollton-Farmers Branch ISD,
Riverchase Elementary School, A Zoning
Change Request from 'TH-I" tO "SF-7'
DRC Date: April 29, 1999
Planning & Zoning Commission Meeting:
City Council Meeting: June 8, 1999
May 20, i999
Show existing and proposed zoning on this site.
Show all adjacent zoning (City of Coppell site, zoningiis missing).
A reminder that the zoning change request sign must be placed on the property by
May 10th and remain on site through June 8th.
Note:
A.
B.
Staff written comments will be faxed to each applicant.
Please revise plats, landscape plans, and utility plans based on ~taff recommendations. Should
applicant disagree with staff comments please provide reasgns why staff recommendations
should not be followed when you attend the May 6th Develo@ment Review Committee (DRC)
meeting.
Each applicant will bring one new set of revised plats and t[lans to the May 6th DRC meeting.
Applicants will be asked to show, explain and defend any revisibn. An Engineer for the project
or other representative is urged to attend the meeting.
Applicant will have till noon Tuesday, May llth to resubmit e~ghteen (18) folded copies of
revised plans and three (3) reduced paper copies (8 1/2 X 11) of each exhibit to the Planning
Department
,6.
DEVELOPMENT REVIEW COMMITTEE
FIRE PREVENTION COM tENTS
ZC-599, CI~ISD, EI..EI~ARY SCHOOL
DATE: APRIL 29, 1~9~
TRA VI$ CRUMP, FIRE MARSHAL.
Minimum inside radius on fire lanes is 30 feet, minimum outside radius is 54 feet.
Fire lanes can not be located in floodplain.
Bus and parent drop offs can not encroach into fire lane.
Any gates across fire lanes to be automatic gates equil~pcd with opticom devices with
KNOX overrides.
Additional fire hydrants are required. Maximum spacing for fire hydrants is 150 feet as
measured along the fire lanes.
Fire Department Connection (FDC) can not be located dn the building. Locate between
three and six feet from a fire lane and within fifty feet Of a fire hydrant.
No lay down curbs allowed in fire lane.
All fire lanes to be installed and stripped per Coppell Fire Code standards.
DE VEL OPMEN T RE VIE W COMMITTEE
ENGINEERING COMMENTS
ITEM:
ZC-599, Carrollton-Farmers Branch LS.D., Ri~erchase Elementarl~ School, a
zoning change request from "TH-I" Townhoure-1 to "SF-7" Single-Family-
7, to allow the construction of an elementary school on 8.897 acres of
property and the dedication of the Starleaf Str~et right-of-way, located at the
northeast corner of MacArthur Boulevard and Starleaf Street, at the request
of Glenn Engineering.
DRC DA TE: April 29, 1999 and May 6, 1999
CONTACT: Mike Martin, P.E., Assistant City Engineer (97~.-304-3679)
COMMENT STATUS:
,'"PR EL IMINA R Y
1. No improvements will be allowed in the floodplain until approved by the City Engineer.
~'~ T~Electric ~
Lone Star Gas ~
Comments for the City of Coppell
Development Review Committee
April 29, 1999
ZC-599, Carrollton-Farmers Branch ISD, Riverchase Element
Zoning change acceptable
Tim Brancheau
try School
14400 Josey Lane Farmers Branch, Texas 75234i
0?:42 CITY OF COPPELL a CITY OF CDPPELL
NO.151
DEVELOPMENT REVIEW COMMITTEE
LEISURE SERVICES COMMENTS
I'1~: CFB-ISD Riverehase Eiementand, Zoning Change
DRC DATE: At, all 29, 1999 and May 6, 1999
CONTACT: Brad Reid, Park Planning and Landscape Manager
COMMENT STATUS: _~PRELIMINARY
DRC42999~
Q09
DEVELOPMENT REVIEW COMMITTEE
FIRR PREVENTION COMMENTS
ZC-$~, CFBISD, F. LRMENTARY SCHOOL
Z DATE: APRIL 29, 1999
CONTACT: TRAVI$ CRUMP, FIRE MARSHAL. (972~) 304-3503
COMMENT STATUS: ,,,~,,r~ ~,
FIN??
No Comments.