DRC Comments
THE-CITY.OF
THE-CITY-OF
COPPELL
..~*.
~ ~
I: q
X 1'\ & _ \ e.
CITY OF COPPELL
ORC REPORT
COPPELL
..~* '" .
~ Q
I: q
..t 1'\ & . \ &
Proiect 10
PD-07 -0072
Address Park Ln
Proiect Name
Pd-108r10~h, Coppell Senior Center
Proiect Type Re-Zoning PD
Application Date 8/23/2007
Case Manaaer Gary Sieb
Proiect Description zoning change request from PD-108-H (Planned Development 108-Historic) and H (Historic) to PD-108~R10-H (Planned
Development 1 08-Revised 10-Historic) to allow the construction of a 13,560-square-foot Senior Recreation/Community
Center building on 26.09 acres of property
Agency
Building Inspection
Electric
Engineering
Reviewed By
Greg Jones
Jeff Curry
Michael Garza
1 of
Review Date
8/29/2007
8/30/2007
8/28/2007
Fire Administration
Tim Oates
8/30/2007
Parks and Recreation
Planning Department
John Elias
Gary Sieb
8/29/2007
8/27/2007
Comments
1. No comments.
No Comments Received
1. Turn the tree layer off on the utility plan to make it
easier to read.
2. A manhole would not be needed for the sanitary
sewer at station 3+00 if you make it straight.
3. The existing 16" water line on Bethel Rd. is RCCP,
this may be difficult to tap into.
4. The 2" water is on the west side of Park Rd. and
there is an existing 8" on the east side of Park
Rd.
5. Drainage design will be evaluated further during
plan review process.
1. Fire hydrant on west side is on a dead-end that
exceeds 150'.
2. Location of the DOC vault for fire sprinkler system?
3. Location of the fire department connection (FDC)?
Needs to be within 50' of a fire hydrant and on the
same side of the fire lane as said hydrant.
4. Fire lanes shall be within 150' of all exterior walls.
Fire lane, with proper turning radii, will need to be
provided on the west side.
No comments
1. Explain how building meets Old Coppell Design
Guidelines.
2. Parking spaces are 19 feet long, not 18, unless
additionall.s. is provided.
3. Tree well required between each 15 parking
spaces.
4. Enhanced paving should be shown at main entry.
5. Monument signage dimensions far in excess of
permitted signage, are dimensions wrong?
6. Need color board exhibit of all building materials.
7. Following plants not on Plant Palette; justify
Foster's Feather Reed Grass, Mexican Feather Grass,
and Mountain Pea.
pro-fonna architecture, inc.
17000 N. Dallas Parkway
SUite 115
Dallas. Texas 75248
City of Coppell Development Review Committee
REVIEW OF SENIOR RECREA nON / COMMUNITY CENTER - RE.ZONING PD
September 6, 2007
Design Team Response to DRC Comments
Engineering Comments
1) Turn the tree layer off the utility plan to make it easier to read.
Tree layer changed to half.tone line for easier reading. We prefer to leave the tree
layer on to illustrate the need to consider the existing trees when installing utilities.
2) A manhole would not be needed for the sanitary sewer at station 3 +00 if you make it
straight.
Line is bent to save existing trees.
3) The existing 16" water line on Bethel Road is RCCP, this may be difficult to tap into.
Revised connection.
4) The 2" water is on the west side of Park Road and there is an existing 8" on the east side
of Park Road.
Existing 2' water line is now noted "to be maintained".
5) Drainage design will be evaluated further during plan review process.
Understood.
Fire Administration Comments
1) Fire hydrant on west side is on a dead-end that exceeds 150'.
Refer to Meeting Notes (Item No.7) from December 1, 2006 meeting with Chief
Oates.
2) Location of the DDC vault for fire sprinkler system?
Provided. Located in median of north parking lot.
3) Location of the fire department connection (FDC)? Needs to be within 50' of a fire
hydrant and on the same side of the fire land as said hydrant.
Relocated fire hydrant to the south and specified installation of FDC.
4) Fire lanes shall be within 150' of all exterior walls. Fire lane, with proper turning radii,
will need to be provided on the west side.
Fire land provided on west side. Regarding 150' distance, refer to Meeting Notes
(Item No. 10) from December 1, 2006 meeting with Chief Oates.
Jeff D. Bulla III. AlA
President
VOice 972.713.7100
Fax 972.713.7070
Planning Department
1) Explain how building meets the Old Coppell Design Guidelines.
We will discuss this with the DRC.
2) Parking spaces are 19 feet long, not 18, unless additional landscape provided.
Parking spaces are noted to be 19 feet at double rows, and 18' at head-in to
landscaping.
3) Tree well required between each 15 parking spaces.
16-space row reduced to 15 spaces.
4) Enhanced paving should be shown at main entry.
Main entry to site will be accomplished by Bethel Road improvements project.
5 ) Monument signage dimensions far in excess of permitted signage, are dimensions wrong?
Landscape Architect understood that in a "non-business" zoning district, we are
allowed one monument sign on the public right-of-way that cannot exceed 36 square
feet.
Assuming that this applies to the "effective area" for a detached monument sign -
which is the imaginary rectangle of the horizontal and vertical lines that fully
contain all extremities of the sign location for the above ground area of the sign -
our sign currently exceeds the 36 square feet (taking in the columns on the ends).
Thus, we detached the sign panel from the columns on the end and then slightly
reduced the now freestanding sign panel to meet the 36 square foot criteria.
Further, we are only allowed one sign per 750 of street frontage. However, we
believe this does not apply to our secondary, internal sign. We adjusted this sign in
a similar manner as the main entry sign to meet the max. 36 s.f. criteria
6) Need color board exhibit of all building materials.
Provided.
7) Following plants not on Plant Palette; justify Foster's Feather Reed Grass, Mexican
Feather Grass, and Mountain Pea.
The Foerster's Feather Reed Grass, Mexican Feather Grass, and Mountain Pea are
all Texas native and/or drought tolerant plants adapted for our area. Our
landscape architect has successfully used these plants on numerous projects in the
past and would be more than glad to give locations where they can be seen and/or
take photographs for distribution.
The concept for the landscape design for the senior center is to complement the
natural setting of the site and the adjacent park utilizing plants that will blend in
Page 2 of 3
PFAI Rcs[mnsc to DRC COllllllcnts ()()()h()7.dol
and not look out-of-place. We feel the plant material selection accomplishes the
drought tolerant criteria for the LEED certification while providing interesting
seasonal interest - even though some of the materials are not on the city's plant list.
Page 3 of 3
PFAI RL'spollse to I)RC COIllIllL'llts O()Oh07.dm
pro-fonna architecture, inc.
17000 N. Dallas Parkway
Suite 115
Dallas. Texas 75248
City of Coppell Development Review Committee
REVIEW OF SENIOR RECREATION I COMMUNITY CENTER - PLAT
September 6, 2007
Design Team Response to DRC Comments
Engineering Comments
1) All utility easements should be 20'.
Corrected.
2) Boundaries of the service center which is located to the south of the senior center will
need to be coordinated with City of Coppell Engineering department.
Need more direction on what is needed from design team.
Fire Administration Comments
1) Fire lane shall be extended to the west side. Provide proper turning radii.
Done.
Planning Department
1) Street address is not needed on plat document.
Removed.
Jeff D. Bulla III. AlA
President
VOice 972.713.7100