Power-Telco Site Plan I I' ELECTRICAL NOTES \ FROM POWER PG~E 0J 1. ALL WORK IS TO COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE (N.E.C.) AND ANY LOCAL ORDINANCES, CODES, AND ALL OTHER ADMINISTRATIVE AUTHORITIES HAVING JURISDICTION. THE CONTRACTOR SHALL FURNISH AND PAY FOR ALL PERMITS AND RELATED FEES. 2. ALL EQUIPMENT AND MATERIAL FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE UNDERWRITERS LABORATORIES (U.L.) LISTED, NEW, FREE FROM DEFECTS, AND SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE BY OWNER OR HIS REPRESENTATIVE. SHOULD ANY TROUBLE DEVELOP DURING THIS PERIOD DUE TO FAULTY WORKMANSHIP, MATERIAL OR EQUIPMENT, THE CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND LABOR TO CORRECT THE TROUBLE WITHOUT COST TO THE OWNER. I tiQIE; ALL HARDWARE TO BE PRO~DED BY GENERAL CONTRACTOR 120/240V, 1 ph, 3W 3#3/0-2"C~) ELECTRIC SERVICE NOTE: CONTRf CTOR SHALL INSTALL NEW 200 A~ P BREAKER AND METER I, / NEW ELECTRIC METER & DISCCNNECT 0' 200 A/2P MAIN SERVICE DISCONNEC 22 KA AIC I ~ 3#3/0, 1 #2G-2"C (THWN- CU) ~ r--120/240 VAC PPC I 3. ALL WORK SHALL BE EXECUTED IN A WORKMAN LIKE MANNER AND SHALL PRESENT A NEAT MECHANICAL APPEARANCE WHEN COMPLETED. CONTRACTOR SHOULD AVOID DAMAGE TO EXISTING UTILITIES WHEREVER POSSIBLE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING RELATED TO ELECTRICAL WORK, AND SHALL RESTORE ALL EXISTING LANDSCAPING, SPRINKLER SYSTEMS, CONDUITS, WIRING, PIPING, ETC. DAMAGED BY THE ELECTRICAL WORK TO MATCH EXISTING CONDITIONS. 4. ELECTRICAL WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL LABOR, MA TERIALS AND EQUIPMENT REQUIRED TO COMPLETE ELECTRICAL POWER AND LIGHTING SYSTEMS, TELEPHONE AND COMMUNICATION SYSTEMS, PANEL BOARDS, CONDUIT, CONTROL WIRING, GROUNDING, ETC. AS INDICA TED ON ELECTRICAL ORA WINGS AND JOR AS REQUIRED BY GOVERNING CODES. 200 AMP MAIN 60A/2P C 60A/2P C 20A/1 P C 15A V1 P C tiQIE; G.C. TO PRO~DE CONDUCTORS FOR THE TRANSFORMER TO THE METER BASE 2#12, 1 #12G-3/ 4"C ~ GFI REC. ...... TO LIGHT 2#12, 1 #1 ~ G-3j 4"C ..... ...... TO B TS 3#6, 1 #6G- 2"C ..... I I 2"C, W/PULL WIRE BOND NEUTRAL & GROUND BUS IN MAIN SERVICE DISCONNECT ~ FUTURE BTS DEMAND LOAD AMPS 2.38 -- 4.42 37.6 37.6 1.0 ----~ 83.0 0.6 83.6 200 5. PRIOR TO INSTALLING ANY ELECTRICAL WORK, THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY EXISTING SITE LOCATIONS AND CONDITIONS AND UTILITY SERVICE REQUIREMENTS OF THE JOB, AND BY REFERENCE TO ENGINEERING AND EQUIPMENT SUPPLIERS DRAWINGS. SHOULD THERE BE ANY QUESTION OR PROBLEM CONCERNING THE NECESSARY PROVISIONS TO BE MADE, PROPER DIRECTIONS SHALL BE OBTAINED BEFORE PROCEEDING WITH ANY WORK. 6. PROVIDE POWER AND TELEPHONE TO SERVICE POINTS PER UTILITY COMPANY REQUIREMENTS. CONTRACTOR SHALL CONTACT UTILITY SERVICE PLANNERS AND OBTAIN ALL SERVICE REQUIREMENTS AND INCLUDE COSTS FOR SUCH IN THEIR BID. ELECTRIC LOAD SUMMARY AREA OF SPACE (164) SF SERVICE VOLTAGE 120/240 V 1~ CONNECTED LOAD DEMAND FACTOR KVA 0.57 1.06 9.0 9.0 0.12 AMPS 2.38 4.42 37.6 37.6 1.0 1.0 1.0 1.0 1.0 1.0 KVA 0.57 I 1.06 I 9.0 I 9.0 0.12 19.75 0.14 LIGHTING (175W HPS) RECEPTACLES (1) BTS #1 BTS #2 TELCO PANEL DEMAND LOAD LIGHTING x 0.25 TOTAL LOAD ---- --~_._---- --- - --- TOTAL SERVICE CAP. --- - 7. SERVICE EQUIPMENT SHALL HAVE A SHORT CIRCUIT WITHSTAND RATING EQUAL TO OR EXCEEDING THE MAXIMUM AVAILABLE FAULT CURRENT AT THE SUPPLY TERMINAL ON THE UTILITY TRANSFORMER SECONDARY, THE INSULATION SHALL BE FREE FROM ANY SHORT CIRCUITS AND GROUNDS. -- 8. ALL WIRES SHALL BE STRANDED COPPER WITH THHNjTHWN AND 600 VOLTS INSULATION. ALL GROUND CONDUCTORS TO BE PROPERLY SIZED COPPER. (STRANDED OR SOLID). 9. IN THE EVENT OF ANY CONFLICT OR INCONSISTENCY BETWEEN ITEMS SHOWN ON THE PLANS AND JOR SPECIFICATIONS, THE NOTE, SPEC/FICA TION OR CODE WHICH PRESCRIBES AND ESTABLISHES THE HIGHEST STANDARD OF PERFORMANCE SHALL PREVAIL. - - --- -T -- a~_ _0- 0 \-_ 0 -----~-~-- -- 0- _ __ _ 1/ \ 10. SERVICE CONDUITS SHALL HAVE NO MORE THAN (2) -90. BENDS IN ANY SINGLE RUN. THE CONTRACTOR SHALL PROVIDE PULL BOXES AS NEEDED WHERE CONDUIT REQUIREMENTS EXCEED THESE CONDITIONS. PULL WIRES AND CAPS SHALl_ BE PROVIDED AT ALL SPARE CONDUITS FOR FUTURE USE. 11. ALL ELECTRICAL EQUIPMENT SHALL BE ANCHORED TO WITHSTAND 100 M.P.H. WIND SPEED AND DESIGNED FOR OUTDOOR EXPOSURE. 12. ALL COAX, POWER AND TELEPHONE SYSTEM CONDUITS SHALL HAVE A MINIMUM 24" SCH. 80 PVC RADIUS SWEEPS TO EQUIPMENT, PULLBOXES, MONOPOLE, ETC., UNl_ESS OTHERWISE NOTED, OR AS REQUIRED BY UTILITY COMPANIES. 13. FUSE TYPE SHALL BE BUSSMAN RKI LOW PEAK FUSE (LPU-RK-100). 14. UPON COMPLETION OF THE JOB, THE CONTRACTOR SHALL FURNISH AS-BUILT DRAWINGS TO THE OWNER. , I I I i : 15. GENERAL GROUNDING CRITERIA 1 ST STEP: GROUND TO EXISTING BUILDING STRUCTURAL STEEL AND TO THE EXISTING COLD WATER LINE. (WHERE APPLICABLE) THEN TEST GROUNDING RESISTANCE TO WITHIN 1 TO 5 OHMS OVERA.LL GROUND RESISTANCE. WHERE THE EFFECTIVE RESISTANCE DOES NOT MEET THIS CRITERIA, PROVIDE SUPPLEMENTAL GROUNDING AND RE - TEST UNTIL GROUND RESISTANCE FALLS BELOW THIS LEVEL. SUPPLEMENTAL GROUND MAY CONSIST OF ONE OR MORE OF THE FOllOWING: 1) COUNTERPOISE, 2) UFER GROUND, 3) GROUND ROD AND JOR GROUND WELL IN EXTREMELY ADVERSE SOIL CONDITIONS. WHERE THE EXISTING BUILDING STEEL DOES NOT PROVIDE AN EFFECTIVE GROUND RESISTANCE, THEN THE CONTRACTOR SHALL PRO~DE A SEPARATE GROUND CONDUCTOR FROM ROOF MOUNTED BTS EQUIPMENT LOCATIONS EITHER DOWN THROUGH THE INSIDE OF THE BUILDING OR DOWN THE OUTSIDE OF THE BUILDING, DEPENDING UPON OWNER PREFERENCE. WHERE THE GROUND CONDUCTOR FROM THE ROOF MOUNTED EQUIPMENT IS ROUTED IN CONDUIT, THE CONDUIT SHALL BE EFFECTIVELY GROUNDED TO THE GROUND CONDUCTOR AT BOTH ENDS OF THE CONDUIT. (MONOPOLE INSTALLATIONS): FOR INSTALLATIONS WHERE WOODEN STRUCTURES, TOWERS, CONCRETE SILOS ETC. ARE ENCOUNTERED A SEP ARA TE DOWNLEAD SHALL BE PROVIDED FROM THE 3 ANTENNAS SEPARATED BY A MINIMUM OF 12 INCHES FROM THE COAXIAL CABLES. THE GROUND CONDUCTOR SHALL BE SECURELY FASTENED TO THE EXTERIOR OF OUTSIDE STRUCTURES WITH NONMETALLIC GROUND STRAPS EVERY 10 FEET. AGAIN, AS FOR TENANT IMPROVEMENT PROJECTS, TEST THE GROUND RESISTANCE FOR MONOPOLE INSTALLATIONS AND PROCEED PER THE ABOVE STEPS. 16. CONTRACTOR TO COLOR PHASE CONDUCTORS BLACK (B PHASE), RED (A PHASE), WHITE (NEUTRAL), AND GREEN (GROUND). 17. CONTRACTOR TO PROVIDE GUTTER TAP. NEV\ UTILI TY RACK I W/ PPC UNIT & ~ / 200A METER/DISCONNECT ~ / (L~/ ~ d ~;d-= ~ V I ~ q ~ / ~" "I~"'~ IP Pi,> P P P P '- P P P P P ) P IU I I · J T T IT T T 1, T T T T T T \ A. ___ r~ ~~r--" I - IJ f-r- - --!- - - -1- - - -- - -- I : / c:::: I FOR POWER FROM POWER POLE TO MET[R ! / - J I NOTE: G.C.!O PROVIDE CONDUCTORS FF~OM :..--) -r"--' J I TRANSFORM:.R TO METER BASE. I I I NP I I I I I > ( I ) , I , I I / / / i / I I I ~~ - - - - - - - - - - - - - - ~ i // I NEW 8' WIDE U'ILlTY EASEMENT \ ! -0: _ _ _ _ \_ _ _ J -o~~ P 1- I T~ I ------~ I 127'-7" (2) 3"rIJ BURIED SCH.40 PVC CONDUIT FOR TELCO FROM TELCO PEDESTAL TO PPC UNIT Wi MULETAPE AND CAP NP POWER/TELCO SITE PLAN SCALE: 1 /8" = l' - 0" P T o o I \J I I (E) tt 11' -9"71/ TELCO \J L "'- Ii PED ~ -~I/ , -o~- =P ' I \J I ---1 I \J 1 ---1 I \J I ---11 I \J ---11 I -0 --l I I \J ---1 I I \J ---1 I I I \J I ---1 I \J I ---1 I \J I ---1 I \J I ---1 (E) UTILITY POLE v y NEW 5' WIDE UTILITY EASEMENT ~ -o--l P T P T NEW PULL BOX ~ \~ NORTH f< ( / / --~'< \ ) / ( ~ 1 I ! < ~ 'k k ( o I <.D I / _\. I x I --/-- \\ I l I I ~; : I ~. I " I "' , >< :j ~. I I I I I i I: I I I I , , V I ~ // o I I I I o r-r) ~ I I // /v I~ ~\JG ~ 1 "L ~~ I >~ / LU C- O :r: 19 z I--t > I--t ...J :r: u 0:=:: :=) :r: u ,,~- OCLOO S'" -', (". f~ ,.,. .... .) . .... -j' lj t'i 1/ 609 SOUTH KELLY AVENUE, SUITE D EDMOND, OKLAHOMA 73003 (405) 348-5460 - OFFICE (405) 341-4625 - FAX I PROJECT NO: I DRAWN BY: l CHECKED BY: D A 1456 ] CG/DL/CEC/SZ I JMG I 11 08/26/08 RE\1SED FINAL - CITY COMMENTS 10 08/11/08 RE\1SED FINAL - CITY COMMENTS 9 08/06/08 RE\1SED FINAL - CITY COMMENTS 8 07/24/08 FINAL REVISED 7 07/14/08 REV. PRELIM CD 6 07/03/08 FINAL ZONING o~ Q) 0::: U Q) ("') z: L- 'oo:::t - LL. N O:CLO o r- CL ::l en >< C"1 o C en 0::: .c I- ex:> LO E (9 -f5 u)'oy ~ 0 ---I (9 en m M ex;> .~ Z C om ~ 'o:::t 0') - 0 N <0 U I I- -c -r- C"1 e ----I ~ C 'oo:::t en ,).... a. -J >.0 ~- en -IN Qj~ ~ ~Rgj~~~~ '-" en en CL LL. ~ 08/26/08 -~~"""~,.~.~,~,~ '" "'\' ~?-- \":- C) r T /:..-:- I ~ \ ;- \~ .........~ '1 ' - .:1" 0'" <.. , \, f"'""\ ". \5' , t ~ · ._,," ~lJ . ~.t ,~ *_ ~./'::'A.r . I' L _~ r..:. "k ., - ~Q: . : . · ~ CJ;. . .. . . .. · :.. . · . ~ ~ JOJi, MO rTACK~.L GEORGE ~ ~ ................iI " . .. . . lr . n · · · · · · . a: '" I, ~, ". 91793/ .: t-i./ .: # "0 . (" ,? ..). ~/--, t1 A'" .'CENS(.... I _'~' · '''<.'-n .... It . · .. ~j':- h \.) \,.'\/ . <'::,-- 'f.\ '~.. (iN AL v ~:e' \\..~ ' ,....~~ o '.:,,~:"<<x,~~ DA1456 LIVING HOPE CHURCH 200 SOUTH HEARTZ ROAD COPPEll, TEXAS 75019 CITY OF COPPEll SHEET TITLE POWER/TELCO SITE PLAN, POWER ONE LINE DIAGRAM & ELECTRICAL NOTES SHEET NUMBER E-1