DRC Comments
THE.CITY.a!"
COPPELL
.~*.. -.
r ~
, "Jr. \ & q
~ 5 .
--
THE-CITY.OF
CITY OF COPPELL
ORe REPORT
COPPELL
.~*!IIP.
"Jr ?< q
.., c5 . \ &
Proiect ID
PD-09-0019
Address S Denton Tap Rd
Proiect Name
PD-241-SF/C, Red Hawk
Proiect Tvpe Re-Zoning PD
Application Date 2/20/2009
Case Manaaer Gary Sieb
Proiect Description zoning change request from 0 (Office) to PD-241-SF/C (Planned Development - 241- Single Family/Commercial) with a Detail
Plan to allow 56 single-family lots with a minimum lot size of 5,300 square feet and an average lot size of 8,291 square feet,
including the retention of the Bullock Cemetery on approximately 14.9 acres of property and a Concept Plan for two commercial
tracts containing approximately 1.5 acres of property
1 of 2
Agency Reviewed By Review Date
Building Inspection Lee Stone 2/26/2009
Electric Jeff Curry 2/26/2009
Engineering Michael Garza 2/26/2009
Fire Administration
Parks and Recreation
Tim Oates
John Elias
2/26/2009
2/23/2009
.
Comments
Design as to provide intersection for street drive sight
distance as well as visibility triangle for any walls, fences,
landscape. etc. ..
No Comments Received
1, Parking should not be allowed on a portion of
Street A. Adjacent to the commercial tract and to common
area 1,
2, The development will be responsible for
installing sidewalk along Denton Tap and Bethel School
Road.
3, Line up the driveway of lot 28 with the driveway
across the street of Bethel School.
4. There is only one point of access in and out of
this subdivision, the fire department might require another
point of access,
5, Install stamped concrete on entrance driveway,
6. Drainage will be evaluated further during engineering
plan review,
7, A flood study should be done to determine downstream
impacts,
8. What is the size of the retaining wall?
9, The fire hydrant should not be on a dead end of more
than 150',(Cul de sac)
see Engineering Comments
1, Tree Removal Permit required prior to start of
construction,
2, Tree calculations on Tree Survey are incorrect.
Ordinance does not allow credits for trees planted on
individual lots. (56 lots x 2-3" trees / lot)
3, Park Development Fees of $1285 per lot.
THE.CITY.O".
.COPPELL
...~' * "',..
~ Q
. e J( & q
! J'\ I) . \
Agency
Planning Department
Reviewed By
Gary Sieb
.
THE.CITY.OF
CITY OF COPPELL
ORe REPORT
COPPELL
.~_ * fi~.
~;-~Q
.t ..t J'\ oS . \ & q
Review Date Comments
2/24/2009 SITE PLAN
1, Density out of line with land use plan--need no more
than 3,0 dus/acre,
2, Past history has shown that 1fooU9foot side yards
difficult to successfully implement; also, 10 feet between
two-story structures tight, 15 feet recommended.
3, Dimension rear yard 20' setbacks on all rear entry
lots" all garages require 20 foot setbacks; 10' rear yard
acceptabe on lots adjacent to pilot channel.--show on
plan,
4, State how Bullock Cemetery will be maintained.
5, Identify entry landscaping as common area.
6, Clarify if temp. sales office will stay or be torn down
and new structure constructed later on lot 28, Blk, A,
7. Need additional info, on screening wall--height,
material, solid/open, color board" etc,
8, Based on info, provided on 40 ' lot dimensions, it
appears that 16 lots can not accomodate your typical floor
plan,
9. Lot widths on Wand N side need to closely
approximate widths of adjacent lots,
10, Tree Mitigation will be recommended (see Parks
comments).
11. With no front yard parking, 30' building lines ok on
lots 27, 28, Blk, A; with front yard parking, 60 ' setbacks
needed,
12, Please provide more info on retaining wall--elevations,
material, height, etc,
13, Why no sidewalk on cemetery site?
14. Staff will not support 100% stucco construction,
15. Staggered front building lines are encouraged with
none less than 15 feet.
16, Add note to plan indicating construction of temporary
sales center on Lot 28, BlkA.
17, A name more in Ine with Mr, Thweat's would be
appropriate for this property rather than Red Hawk, any
suggestions?
18, Fire Deparetment may have additional comments
regarding access to this property which will be discussed
at the March 5 DRC meeting.
LANDSCAPE PLAN
1. Italian Cypress not an approved tree, please pick
another type,
2. Please provide detail on median wall and arbor (type,
materials, elevations, size, etc,),
3, Verify the landscape area between the street curb and
the screening wall--it does not scale 15-50 feet
KADLECK & ASSOCIATES
ENGINEERING PLANNING SURVEYING
555 REPUBLIC DRIVE, SUITE 115
PLANO, TEXAS 75074
972-881-0771
972-509-1861 (FAX)
April 14, 2009
Terry Holmes
THBGP, INC. dba The Holmes Builders
1445 MacArthur Drive, Suite 200
Carrollton, Texas 75007
Re: PD-241-SF/C, Red Hawk, Northwest Comer of Denton Tap Road and Bethel School
Road, Coppell, Texas
Dear Terry:
In reviewing the staff comments for this project, I would like to clarify and expound on a
few of their comments.
· As It Relates to Item #3: The main entry cannot be shifted to line up with the second
drive to the south, west of Denton Tap. This would require a shift of about 40 feet,
which would eliminate a single-family lot and make the commercial comer larger,
This drive is the second drive into Ace Hardware. It is not the primary drive into the
property and should not be generating that much traffic. Bethel School Road is not a
divided roadway and the fact that drive and entrance to the subdivision do not line
up should be insignificant.
· As It Relates to Item #4: If both drives at the southeast comer of the property off
Denton Tap are closed, that will limit the commercial comer to only one future drive
off Bethel School. I believe you should either not address this at this time or make
provision for at least an "In Only" drive off Denton Tap at a minimum?
· As It Relates to Item #8: The proposed side setback of 3 feet/7 feet provides a
minimum distance of 10 feet between structures. This is the same affect as having a
five-foot setback, except it is more beneficial since it provides more area for use
with the lot having the 7-foot setback.
· As It Relates to Item #8: We already have a 25 foot front setback on Lot 3, Block A.
To use both a 25 foot front setback and a 20 foot rear setback on Lots 3-8, Block A
would reduce the buildable area on these lots which will affect the house size that
can be placed on these lots.
· As It Relates to Item #10: The actual density of this development is 3,6 units per
acre with 54 lots. The development to the north is also 3.6 units per acre. The
. . -... .
development to the west is 2.9 units per acre. It is usually typical for the residential
density to increase as you approacn commercial property and a major thoroughfare,
.
as is the case with this development. We are matching the density of the existing
development to the north.
There was a previous comment pertaining to traffic and I believe the city engineer
indicated that the difference between 49 lots and 54 lots is negligible. I concur that this
difference should not have an impact on the traffic,
The other comments that affect the Site Plan will be addressed with on a revised copy of
the Site Plan and Preliminary Plat before they go to City Council and once we incorporate
any additional comments that may come out of the Planning and Zoning Commission
meeting.
Please contact me with any questions or comments.
Sincerely,
!l1 ~~~
L. Lynn Kadleck
Kadleck & Associates
I
THE.CiTY.OF
"
Planning Department
255 Parkway Blvd
Coppel!, Texas 75019
Phone: 972-304-3678
Fax: 972-304-7092
DRC Agenda and
Staff Comments
[PIIIQ)
~:DtMV'
PROJECT: PD-241-SF/C, Red Hawk, and Preliminary Plat
PLANNING DEPARTMENT CONTACT: Gary Sieb
DIRECT DIAL: 972-304-3678
DATE: February 27,2009
~: Terry Holmes
FAX COVER SHEET
PAGES@ (including cover)
FAX: 972-242-2931
Items Transmitted:
1. Agenda for the March 5, 2009 DRC Meeting
2. DRC Comments
Remarks:
A. Please revise all plans and plat(s) based on staff recommendations. Should
the applicant disagree with staff comments, please provide reasons why staff
recommendations should not be followed when you attend the March 5, 2009
Development Review Committee (DRC) meeting.
B. Each applicant will bring two new sets of revised plans and plat(s) to the
March 5, 2009 ORC meeting. Applicants will be asked to show, explain and
defend any revision. A representative of the project is required to attend this
meeting.
C. The applicant will have until noon, March 10, 2009 to submit 12-24' x 36'
sets, FOLDED, and three (3) reduced paper copies (8 1/2 X 11) and JPEG.
TIF. PDF OR SIMILAR ELECTRONIC FORMA T of each exhibit. Only two
sets of revised preliminary engineering and irrigation plans are required,
Reductions and electronic copies are not required of the engineering and
irrigation plans.
If you have any questions or would like additional information, please contact me at 972-304-3676 or
e-mail atQsieb(i]2cLcoooell.tx.us
.
oI'J ~
~/
THE,CITY OF
corrELL
Ii
~ 0'-.
~Ov.. 8
o
PLANNING DEPARTMENT
255 Parkway Boulevard
P.O. Box 9478
Cappelli TX 75019
(972) 304-3678
FAX: (972) 304-7092
FAX COVER SHEET
PLEASE DELIVER THE FOLLOWING PAGES TO:
NAME:~ HvJMes
FAX NO.: 912, tJ...'-I2. - 2or?,/
FIRM:
FROM: J UAfl v~ (1/1, ~ ~
DIRECT DIAL: q72 -'30'-1- 3& 7'.)
TRANSMITTED BY: ------ DATE: 03o-l0ar TIME:
NUMBER OF PAGES (INCLUDING COVER SHEET): -:3
~c1 ~k-
r~1J~~~
REMARKS: 3)rct. ~~
J- rf-ell.lWUA1~ r la.f5,
:PI)"
IF YOU DO NOT RECEIVE ALL OF THE PAGES, PLEASE CALL BACK AS SOON
AS POSSIBLE. PLEASE DIAL DIRECT TO THE PERSON SENDING THIS FAX.
THANK YOU.
This facsimile is privileged and confidential. It is intended solely for the addressee, Any unauthorized disclosure,
reproduction, distribution or action in reliance on the contents of this information by anyone other than the addressee is
prohibited. If you receive this facsimile in error, please notify us by telephone and return the original message to us via the
V,S, Postal Service. Thank You,
.