Loading...
Elevations(Adminstratively Approved)CONNECT TO UNDERGROUNDMETAL WATER PIPEPER NEC 250-30 (a) (3) (b)EXISTING GROUNDBUS (TYP.) IN MAINELECTRICAL ROOMMAIN BONDINGJUMPER PER NEC250-28BREAKERENCLOSURE(TYP.)#1/0 CUNEW GROUND RODEXTEND 3/0 G.E.C TOROD AND REBAR INFOUNDATION.PER NEC 250-24(C)CONNECT TOMETALSTRUCTUREREBAR#4/0 CU EXISTING SEDNEW GENERATORSEPERATELY DERVIVEDSERVICEC/BNGNGMAINGROUNDINGELECTRODEPER NEC 250-52(c)REFER TO ONE-LINEDIAGRAM FOREQUIPMENTGROUND SIZEDCWGRADE EXISTINGMAINELECTRICALROOMOUTSIDEMAIN BONDINGJUMPER PER NEC250-28PER NEC 250-24(C)ATS-MDPMDPREFER TO ONE-LINEDIAGRAM FOREQUIPMENT GROUNDFED FROMDOWNSTREAMTRANSFER SWITCHGENERATORDOCKINGSTATIONFORSEERE-STOPAT ENCLOSURE2#142#14 ENGINE START/STOPATS-MDP(IN MAIN ELEC)FORSEER22 AWG, TYPE CMP, CL2P2#14 ENGINE START/STOPATS-LS(IN MAIN ELEC)FORSEERRS-4852#14 ENGINESTART/STOP2#14 ENGINESTART/STOP2#14 ATS LS INHIBIT WITHATS-MDP ON SOURCE 222 AWG, TYPE CMP, CL2PFINISHED GRADEWARNING TAPE4'' MIN.(TYP.)4''MIN.6''PP7-1/2"7-1/2"4'' MIN.(TYP.). 30"EB 20 PVC CONDUIT,SIZES AS NOTED ONPLANS/SCHEDULES(TYP.)CONCRETE4''MIN.P7-1/2"ABBREVIATIONS:P = POWER CONDUITSP = SPARE CONDUITC = 1" CONTROLS CONDUIT (BAS, ATS START)L=POWER TO LOAD CENTERLS=LIFE SAFETY FEEDERS=1-1/2" SECUITYCCSPLLSSS8" CMU WALL WITH STUCO FINISHTO MATCH EXISTING BUILDINGREINFORCED AT 16" CENTERSGENERATOR ENCLOSURE ROOFSHALL BE OPEN WITH FENCINGPROVIDE FOR SECURITY. FENCINGSHALL BE RECESSED 3” BELOW WALLTO HIDE FROM EXTERIOR VIEW.8" CMU WALL WITH STUCO FINISHTO MATCH EXISTING BUILDINGREINFORCED AT 16" CENTERS72" WIDEDOUBLE DOORGENERATOR ENCLOSURE ROOFSHALL BE OPEN WITH FENCINGPROVIDE FOR SECURITY. FENCINGSHALL BE RECESSED 3” BELOW WALLTO HIDE FROM EXTERIOR VIEW.WATER SHALL DRAIN TO WARDDOOR AND ADJACNET SIDEREFER TO STRUCTURAL DRAWINGS.EQEQ72" WIDEDOUBLE DOOR8" CMU WALL WITH STUCO FINISHTO MATCH EXISTING BUILDINGREINFORCED AT 16" CENTERSGENERATOR ENCLOSURE ROOFSHALL BE OPEN WITH FENCINGPROVIDE FOR SECURITY. FENCINGSHALL BE RECESSED 3” BELOW WALLTO HIDE FROM EXTERIOR VIEW.30' - 2"10' - 0"8" CMU WALL WITH STUCO FINISHTO MATCH EXISTING BUILDINGREINFORCED AT 16" CENTERSGENERATOR ENCLOSURE ROOFSHALL BE OPEN WITH FENCINGPROVIDE FOR SECURITY. FENCINGSHALL BE RECESSED 3” BELOWWALL TO HIDE FROM EXTERIOR VIEW.17' - 4"10' - 0"72" WIDEDOUBLE DOOR8" CMU WALL WITH STUCO FINISHTO MATCH EXISTING BUILDINGREINFORCED AT 16" CENTERSGENERATOR ENCLOSURE ROOFSHALL BE OPEN WITH FENCINGPROVIDE FOR SECURITY. FENCINGSHALL BE RECESSED 3” BELOW WALLTO HIDE FROM EXTERIOR VIEW.SHEET NUMBER:DATE:PROJECT NUMBER:SCALE:DESIGNED BY:DRAWN BY:CHECKED BY:ISSUESKEYPLANTELIOSMEP&T CONSULTING ENGINEERSTELIOS146 PAYNE ST.DALLAS, TX 75207PH: 214.744.6199FX: 214.744.0770MEP&T CONSULTING ENGINEERSTHE SEAL APPEARING ON THIS DOCUMENT WASAUTHORIZED BY MASON MCPIKE, PE #103654, ON DECEMBER5TH, 2016. ALTERATION OF A SEALED DOCUMENT WITHOUTTHE PRIOR WRITTEN CONSENT OF THE RESPONSIBLEENGINEER IS AN OFFENSE UNDER THE TEXAS ENGINEERINGPRACTICE ACT. THE RECORD COPY OF THIS DRAWING IS ONFILE AT THE OFFICES OF TELIOS, INC., 146 PAYNE ST.,DALLAS, TX, 75207.11.18.17ISSUE FOR PERMITAs indicatedE04.0112/05/16ELECTRICAL DETAILS01/18/17DesignerAuthorChecker1315 S. BELTLINE ROADCOPPELL, TX 75019Scale: NONE1DETAIL - SERVICE GROUNDINGScale: NONE2DETAIL -ATS AND GENERATOR WIRINGScale: NONE3DETAIL - HOUSE POWER GENERATORDUCTBANK 1/4" = 1'-0"4YARD ELEVATION Copy 1 1/4" = 1'-0"5SCREEN WALL ELEVATION 4 1/4" = 1'-0"6SCREEN WALL ELEVATION 2 1/4" = 1'-0"7SCREEN WALL ELEVATION 1 1/4" = 1'-0"8SCREEN WALL ELEVATION 31REVISIONS1 2.20.2017 CITY COMMENTS