7-23-19 Dust Collector Details190498-001 G.A.
26'7"
319"
57'2 34 "
686 34 "
15'2"182"
137"
30'7 34 "
367 34 "
59 58 "
AA
EE
(2) FIKE CV-S LOW BURST PRESSUREMEMBRANE 316 STAINLESSSTEEL, EXPLOSION VENT1.5 ± 0.5 PSI BURST PRESSURE1.7 PSIG VAC. RATING-40 TO 400 F36" X 44"
(2) FIKE, D3513-115-10BURST INDICATOR WITH 10FT CABLE. BURST INDICATORIS A NORMALLY CLOSED CIRCUIT.DURING BURST, THE INDICATORIS PHYSICALLY BROKEN CREATINGAN OPEN CONDITION IN THE CIRCUIT THAT CAN BE DETECTEDBY THE SYSTEM CONTROL.INPUT VOLTAGE: 24V (MAX. AC OR DC)INPUT CURRENT: 50mA MAX
X-BRACING FAR SIDE
X-BRACING
NEAR SIDE
KNEE BRACE
FAR SIDE
KNEE BRACE
FAR SIDE
50'10 58 "
610 58 "
18'8"224"
32'2 58 "
386 58 "
OUTLET FLANGESEE SHEET 2
FLEXIBLE CABE CLIMBING
SYSTEM SUPPLIED BY IMPERIAL
TO BE INSTALLED ON LADDER
(BY OTHERS)
86 18 "
87"
354 58 "
96"
200 78 "
GG
(2) AUTOMATIC SPRINKLERSMFG: GLOBE P/N: GL5651 OR TYCO P/N: TY3251ORFICE SIZE: 5.6, PENDANT MOUNTCONNECTION: 1/2"NPTWORKING PRESSURE RATING: 125PSITEMPATURE RATING: 215° F
8" WIDE X 540° INTERNAL SPIRAL
25 HP FAN, 3450 RPM, 208-230/460V3PH, 60Hz, EXP-TEFC, Class I , Groups C & D,Class II / Groups F & GACFM 8,864 @ 9.7 IN.WG
GEARMOTOR 0.25 HP. 1770RPM 490V, 3PH, 60Hz, EXPLOSION PROOFClass I , Division 2. Groups A, B, C & D,Class II / Groups F & G
SEE SHEET 2
INLET FLANGE
SEE SHEET 2
FF
LOW PRESSURELOCATION - Ø1/8"NPT
HIGH PRESSURELOCATION - Ø1/8"NPT
Ø1"NPT SPRINKLER CONNECTION1 EACH SIDE
ELECTRICAL CONDUITCONNECTION - Ø1"NPT
TOOL FREE CLEANAIR MAN DOOR (LEFT HAND)
BALL VALVE PORTØ2" NPT
LEVEL INDICATORLOCATION Ø1-1/4" NPT(OPTIONAL)
CLEAN OUTDOOR
DISCHARGE FLANGESEE SHEET 2
SEE SHEET 2
X-BRACING FAR SIDE
X-BRACING
NEAR SIDE
KNEE BRACE
NEAR SIDE
KNEE BRACE
NEAR SIDE
FIRE PROTECTION and SAFETY EQUIPMENT: The customer assumes the responsibility to contact their insurance company and or AHJ (Authority having Jurisdiction) to see what is required to meet the needs of fire protection, explosion ventilation, deflagration, isolation and any other related equipment. It is the customer’s responsibilities to relay this information to Imperial Systems so that we can properly select and size the necessary equipment to meet their requirements. The customer should adhere to any and all NFPA, OSHA, federal, state, codes, rules and regulations.
SEE SHEET 2
SEE SHEET 2SEE SHEET 2
SEE SHEET 2
SEE SHEET 2 SEE SHEET 2
NOTES:NO LOGOS OR SIGNAGE ON THE TOWER1.ALL IMPERIAL EQUIPMENT, INCLUDING TOWER 2.AND STRUCTURE ON THIS DRAWING WILL BE PAINTED RAL 7035 LIGHT GRAY TO MATCH THE BUILDING
MATERIAL SPEC:
THIS DRAWING IS A CONFIDENTIAL DISCLOSURE AND IS LOANED TO RECALL AT ANY TIME WITH THE UNDERSTANDING THAT IT WILL NOT BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF IMPERIAL SYSTEMS.
RAL 7035 LIGHT GRAY
UNLESS OTHERWISE SPECIFIED:1. NO BURRS OR SHARP EDGES2. MACHINED SURFACES 125 Ra, DRILLED HOLES 250 Ra
TOLERANCES UNLESS OTHERWISE INDICATED .0 .020 .00 .010.000 .005
FRACTIONS: 1/8ANGULAR: 1
NJL 7/15/2019 34112.42
1:54 1 2
GF PUHL COMPANYBRF REVERSE AIR CLEANING12BRF360-10
1
DO NOT SCALE DRAWING
A
3/16" CARBON STEEL
234
B
C
D
C
B
A
D
34 12
SCALE
DRAWN BY DATE WEIGHT (lbs)
SHEET DRW. NO.OF
IMPERIAL SYSTEMS, INC7320 WEST MARKET STEETMERCER, PA 16137T: 724-662-2801F: 724-662-2803www.isystemsweb.com
PAINT COLOR:
FINISH: ALL SHARP EDGES TO BE ROUNDED TO A SMOOTH RADIUS. ALL BURRS, WELD SPATTER AND ALL OTHER SHARP PROJECTION TO BE GROUND SMOOTH.
190498-001 G.A.
23°
20° 20°
60" 60" 72" 72"
72"
72"
17'6 1516 "
210 1516 "
23'4"280"
SECTION A-A
SEE SHEET 1
SECTION G-G
SEE SHEET 1
(360) Polyester Bags Glazed, 5" Diameter x 10' Bags for BRF, 16 oz, Snap band Top No-tool Design
(360) Tool-Free Top Removal Zinc Plated Cages
60" 72" 72" 60"
23 916 "
40" 93"
SECTION F-F
SEE SHEET 1
264"
12 1116 "
100 1116 "
28 14 "
144"
SECTION E-E
SEE SHEET 1
16"
8"
16" 8" 13"
6 12 "
13"
6 12 "
78 " TYP
DETAIL H
SCALE 1 : 27
44 316 "
2"
46 38 " B.C.
OUTLET FLANGE DETAILINLET FLANGE DETAIL (90°)SEE SHEET 1
38 316 " I.D.
2"
40 38 " B.C.
DISCHARGE
FLANGE
SEE SHEET 1
78 "
78 "
31"
35"
64"
68"
78 "
6 18 "
1"
4 58 " 4 @ 6"= 24" 4 58 "
9 @ 6"
= 54"
6"
716 "
INLET FLANGE
SEE SHEET 1
FIRE PROTECTION and SAFETY EQUIPMENT: The customer assumes the responsibility to contact their insurance company and or AHJ (Authority having Jurisdiction) to see what is required to meet the needs of fire protection, explosion ventilation, deflagration, isolation and any other related equipment. It is the customer’s responsibilities to relay this information to Imperial Systems so that we can properly select and size the necessary equipment to meet their requirements. The customer should adhere to any and all NFPA, OSHA, federal, state, codes, rules and regulations.
MATERIAL SPEC:
THIS DRAWING IS A CONFIDENTIAL DISCLOSURE AND IS LOANED TO RECALL AT ANY TIME WITH THE UNDERSTANDING THAT IT WILL NOT BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF IMPERIAL SYSTEMS.
RAL 7035 LIGHT GRAY
UNLESS OTHERWISE SPECIFIED:1. NO BURRS OR SHARP EDGES2. MACHINED SURFACES 125 Ra, DRILLED HOLES 250 Ra
TOLERANCES UNLESS OTHERWISE INDICATED .0 .020 .00 .010.000 .005
FRACTIONS: 1/8ANGULAR: 1
NJL 7/15/2019 34112.42
1:54 2 2
GF PUHL COMPANYBRF REVERSE AIR CLEANING12BRF360-10
1
DO NOT SCALE DRAWING
A
3/16" CARBON STEEL
234
B
C
D
C
B
A
D
34 12
SCALE
DRAWN BY DATE WEIGHT (lbs)
SHEET DRW. NO.OF
IMPERIAL SYSTEMS, INC7320 WEST MARKET STEETMERCER, PA 16137T: 724-662-2801F: 724-662-2803www.isystemsweb.com
PAINT COLOR:
FINISH: ALL SHARP EDGES TO BE ROUNDED TO A SMOOTH RADIUS. ALL BURRS, WELD SPATTER AND ALL OTHER SHARP PROJECTION TO BE GROUND SMOOTH.