April 1, 2020
Mary Paron-Boswell
City of Coppell
265 E Parkway Blvd,
Coppell, Texas 75019
PO Box 9478
Re: Comment Response Letter – PD Zoning Review
Plan Case ID #PD20-03-000415
Hilton Garden Inn
Coppell, Dallas County, Texas
Dear Mary Paron-Boswell:
We are requesting approval of the above referenced PD Zoning submittal and have addressed the comments received on 03/27/2020. Below are
the comments and our responses.
Agency Reviewed By Review Date Plan Review Details
Building Suzanne Arnold 03/25/2020 No comments
Engineering Cole Baker 03/27/2020 Site Plan:
- 30' minimum inside radius for fire lanes
The entryway is 29’ wide. It was discussed with staff during the
pre-development meeting that the fire radius could be reduced if
the drive aisle was wider than 24’. We have run a vehicle
tracking software to demonstrate that a 40’ fire truck can
comfortably make the turn. The vehicle tracking is shown on the
detail site plan.
Landscape Plan:
- Move tree away from storm drain inlet, wrap shrubs around
inlets
Addressed.
- Move tree in northeast corner off of top of water line
Addressed.
- Recommend not placing trees near private water loop
Addressed.
Utility Plan:
- No DCDA required for fire service, private fire line already has
DCDAs
Addressed.
- Domestic service can't come from the fire line, needs to come
from the city line to the north
Addressed.
- Move nothern FH line 10' away from proposed tree
Addressed.
- Move storm sewer line away from proposed trees
Addressed.
- Move fire service, FDC, and southern FH 10' away from
proposed trees
Addressed.
- Recommend moving sanitary sewer service away from proposed
tree
Addressed.
2 of 3
2805 Dallas Parkway, Suite 600
Plano, Texas 75093
Tel: 972.488.3880
Fax: 972.488.3882
www.jonescarter.com
Engineering Kumar Gali
Fire Tim Oates 03/24/2020 1. Utility plan - if building is less than 100,000sf, FDC line to be
4-inch.
Addressed.
2. Utility plan - fire hydrants required every 300lf along fire lane
easement; water line loop around the building will be required
with additional fire hydrants
Addressed.
3. Fire riser room shall be minimum of 64sf with direct access
from the exterior, show on site plan
Addressed.
Parks John Elias 03/25/2020 No comments
Planning Mary Paron-Boswell Elevations
- provide a colored exhibit
Addressed.
- label materials on the elevations
Addressed.
- provide a dumpster detail
Addressed.
- brick screening wall for dumpster enclosure
Addressed. Dumpster enclosed with stone.
- add pedestrian gate for dumpster
Addressed.
- provide a sign plan
Signage to conform to city standards.
- add more masonry to bldg.
Addressed.
- Review Sec. 12-22-5 (2) & (3)
Will comply.
- review pool screening requirements
Will comply.
- provide a material color board
Please clarify – material board was provided at submittal.
- Need to rename project we already have a Whitestone
project
Addressed.
Landscaping
- adjust title block for all sheets:
- project name
- plat name
- lot #, Block #
- acreage and zoning
- label setbacks and utility easements
Addressed.
- Point West, not Whitestone
Whitestone removed.
- Landscape calculations provide not only what is required but
also what is provided
Addressed.
- Accent trees are 3:1 for canopy trees
Addressed.
3 of 3
2805 Dallas Parkway, Suite 600
Plano, Texas 75093
Tel: 972.488.3880
Fax: 972.488.3882
www.jonescarter.com
Detail site plan
- provide fire lane radii
Fire lane radii are provided. The entryway is 29’ wide. It was
discussed with staff during the pre-development meeting that the
fire radius could be reduced if the drive aisle was wider than 24’.
We have run a vehicle tracking software to demonstrate that a 40’
fire truck can comfortably make the turn. The vehicle tracking is
shown on the detail site plan.
- provide dumpster detail - brick wall dumpster required with
pedestrian pass thru
Please reference the elevations.
- list width of porte cochere
Addressed.
- add to amenity table: Provide staff on-site 24 hrs/day
Addressed.
- provide ratio for parking count
Addressed.
- FIRE LANES ARE REQUIRED TO BE PLATTED, THEREFOR
A PLAT WILL BE REQUIRED. IN SPEAKING WITH
ENGINEERING THE UTILITY EASEMENT ON THE WESTERN
PORTION OF THE ISTE CAN POSSIBLY BE ABANDONED IF I
IS NOT BEING USED.
Can the fire lane easement be dedicated by separate
instrument? The lot is already platted. The utility easement on
the western portion of the site contains an underground electric
line.
- The easement on the northern portion of the site can have
accent trees placed in it, however, slide them as far south as
possible away from the waterline.
Addressed.